Plan Review Details - Permit 18050756
Plan Review Stops For Permit 18050756
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-01-09 Cont ID  
Sent By rmcdouga Date 2019-01-09 Time 09:56 Rev Time 0.00
Received By rmcdouga Date 2019-01-09 Time 09:52 Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-05-25 Cont ID  
Sent By rmcdouga Date 2018-05-25 Time 09:22 Rev Time 0.00
Received By rmcdouga Date 2018-05-25 Time 09:22 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-01-08 Cont ID  
Sent By jleahy Date 2019-01-08 Time 18:08 Rev Time 0.00
Received By jleahy Date 2019-01-08 Time 18:08 Sent To Z
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-05-29 Cont ID  
Sent By jleahy Date 2018-05-29 Time 08:51 Rev Time 0.00
Received By jleahy Date 2018-05-29 Time 08:51 Sent To  
Notes
2018-05-29 08:53:31FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 RISER SHOW GENERATOR FEEDING THE PANELS NOT THE
 TRANSFER SWITCHES.
  
 175 AMP MAIN ON GENERATOR FEEDING #2 CONDUCTORS.

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2019-01-10 Cont ID  
Sent By tklarge Date 2019-01-10 Time 04:47 Rev Time 0.00
Received By tklarge Date 2019-01-10 Time 04:13 Sent To I
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-05-31 Cont ID  
Sent By tklarge Date 2018-05-31 Time 11:44 Rev Time 0.00
Received By tklarge Date 2018-05-31 Time 10:41 Sent To I
Notes
2018-05-31 11:44:301) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FLEX
 CONNECTOR FOR THE GENERATOR. THE FLEX CONNECTOR SHALL
 BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE
 GENERATOR. 2017 FBCR SEC. G2422.1 (8).
 2) THE CONTRACT STATES THAT 80 FEET OF PIPE WILL BE
 INSTALLED BUT THE SURVEY AND GAS DRAWING STATES 50 FEET
 OF PIPE. CLARIFY.
 3) SHOW THE TYPE OF EXISTING PIPE TO THE POOL HEATER
 AND THE COOKTOP.
 4) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLE FOR
 THE LOW PRESSURE GAS SYSTEM.
 5) THE SHUTOFF VALVE AT THE GENERATOR SHALL BE UPSTREAM
 OF THE REGULATOR.
 6) MEDIUM PRESSURE REGULATORS ARE REQUIRED AT THE POOL
 HEATER AND THE COOKTOP.
 7) SHOW THE TYPE OF MATERIAL FOR ALL PIPING ON THE GAS
 PLAN.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-01-10 Cont ID  
Sent By tklarge Date 2019-01-10 Time 04:48 Rev Time 0.00
Received By tklarge Date 2018-12-27 Time 11:26 Sent To  
Notes
2018-12-28 11:26:47RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-31 Cont ID  
Sent By tklarge Date 2018-05-31 Time 11:44 Rev Time 0.00
Received By tklarge Date 2018-05-16 Time 14:13 Sent To  
Notes
2018-05-17 14:13:23ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 2 Status P Date 2019-01-08 Cont ID  
Sent By mcruz Date 2019-01-08 Time 11:25 Rev Time 0.00
Received By mcruz Date 2019-01-08 Time 11:01 Sent To E
Notes
2019-01-08 11:25:38VARIANCE WAS GRANTED, GENERATOR SHALL BE AT LEASE 3.5'
 FROM REAR PROPERTY LINE.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By mcruz Date 2018-05-22 Time   Rev Time  
Received By   Date 2018-05-22 Time   Sent To PC
Notes
2018-05-22 10:51:32ZONING REVIEW FAILED,
  
 1) INDICATE ON SURVEY SETBACK FROM GENERATOR TO REAR
 PROPERTY LINE. MUST BE AT LEAST 8.6 FEET.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 561-822-1442
 [email protected]
  