| 2018-05-22 08:59:22 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEM NOTED BELOW: | | | | | | 1) THE SIGNED AND SEALED GENERATOR PAD ENGINEERING | | | REQUIRES THE GENERATOR TO HAVE A MINIMUM WEIGHT OF 526 | | | POUNDS. THE PROPOSED 22KW GENERAC GENERATOR WEIGHS 466 | | | POUNDS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2018-07-27 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-07-27 |
Time |
16:30 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-07-27 |
Time |
16:30 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2018-05-23 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-05-23 |
Time |
10:26 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-05-23 |
Time |
10:26 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2018-08-20 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2018-08-20 |
Time |
17:35 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2018-08-20 |
Time |
17:24 |
Sent To |
|
|
| Notes |
| 2018-08-20 17:36:18 | 08/20/18 REVIEWED FOR CODE COMPLIANCE (GAS) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM | | | THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND | | | NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF | | | PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY | | | ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2018-07-31 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-07-31 |
Time |
10:44 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-07-31 |
Time |
10:16 |
Sent To |
I |
|
| Notes |
| 2018-07-31 10:21:55 | 1) THE EXISTING GAS PLAN ON FILE IN CITY RECORDS SHOWS | | | AN EXISTING 1 1/2 INCH GALVANIZED LINE AT THE OUTLET OF | | | THE GAS METER AND THE SUBMITTED GAS PLAN FROM RELIABLE | | | POWER SYSTEMS SHOWS AN EXISTING 3/4 INCH LINE. CLARIFY. | | | 2) THE EXISTING GAS PLAN ON FILE IN CITY RECORDS SHOWS | | | AN EXISTING 1 INCH LINE TO THE INTERIOR OF THE | | | STRUCTURE AND THE SUBMITTED GAS PLAN FROM RELIABLE | | | POWER SYSTEMS SHOWS A 3/4 INCH LINE. CLARIFY. | | | 3) THE EXISTING GAS PLAN ON FILE IN CITY RECORDS SHOWS | | | A FUTURE BBQ GRILL AT 55,000 BTU'S. THIS APPLIANCE MUST | | | BE ADDED TO THE EXISTING LOAD . 2017 FBC-FUEL GAS | | | SEC.401.4. | | | 4) THE EXISTING GAS PLAN SHOWS AN 1 1/4 INCH PE LINE TO | | | THE POOL HEATER AND BBQ AT A DISTANCE OF 83 FEET. THIS | | | DISTANCE SHALL BE USED FOR THE SIZING OF THE 2 PSI | | | SYSTEM. 2017 FBC-FUEL GAS SEC.402.4.1. | | | | | | NOTE: I HAVE PLACED A COPY OF THE EXISTING GAS PLAN IN | | | YOUR APPLICATION THAT YOU CAN USE AS A REFERENCE. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2018-05-19 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-05-19 |
Time |
08:25 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-05-19 |
Time |
08:08 |
Sent To |
|
|
| Notes |
| 2018-05-19 08:25:33 | | | | 1) SHOW THE TYPE OF PIPE AND PIPE SIZE AT THE OUTLET OF | | | THE 2 PSI METER . WPB AMEND. TO FBC SEC. 107.2.1. | | | 2) SHOW THE PIPE SIZE OF THE SECTION OF PIPE TO THE | | | EXISTING GAS LOAD.WPB AMEND. TO FBC SEC. 107.2.1. | | | 3) SPECIFY ON THE GAS DRAWING HOW THE 3/4 INCH | | | GALVANIZED PIPE IS GOING TO BE INSTALLED. ABOVE-GROUND | | | PIPING OUTDOORS SHALL COMPLY WITH 2017 FBCR | | | SEC.G2415.9, G2415.11. | | | 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FLEX | | | CONNECTOR FOR THE GENERATOR. THE FLEX CONNECTOR SHALL | | | BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE | | | GENERATOR. 2017 FBCR SEC. G2422.1 (8). | | | 7) THE SEDIMENT TRAP AS DRAWN DOES NOT COMPLY WITH 2017 | | | FBCR SEC.G2419.4. | | | 8) SUBMIT MANUFACTURER'S SPECIFICATIONS AND | | | INSTALLATION SHEETS FOR THE REGULATOR. REGULATORS | | | INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE | | | APPROVED FOR OUTDOOR INSTALLATION. 2017 FBCR | | | SEC.G2421.1, FBC-FUEL GAS SEC. 410.1. | | | 9) LIST THE EXISTING GAS FIXTURES ON THE PLAN AND THE | | | CORRESPONDING BTU LOAD FOR EACH APPLIANCE. WPB AMEND. | | | TO FBC SEC .107.2.1, 2017 FBC-FUEL GAS SEC.402.1. | | | 10) THE EXISTING BTU LOAD LISTED ON THE GAS DRAWING | | | DOES NOT CORRELATE WITH THE EXISTING GAS PLAN ON FILE | | | WITH THE CITY. I HAVE PLACED A COPY OF THE GAS DRAWING | | | FROM THE ORIGINAL PERMIT #01090269. | | | | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-08-20 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2018-08-20 |
Time |
17:36 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2018-08-16 |
Time |
13:32 |
Sent To |
|
|
| Notes |
| 2018-08-17 13:32:22 | RESUB ROUTED TO TKLARGE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-07-31 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-07-31 |
Time |
10:45 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-07-16 |
Time |
14:42 |
Sent To |
|
|
| Notes |
| 2018-07-17 14:42:48 | RESUB ROUTED TO ZONING INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-05-23 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-05-23 |
Time |
10:26 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-05-15 |
Time |
11:11 |
Sent To |
|
|
| Notes |
| 2018-05-16 11:11:43 | ROUTED TO ZONING INBOX |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2018-07-23 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2018-07-23 |
Time |
13:43 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2018-07-23 |
Time |
13:37 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2018-07-23 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2018-05-17 |
Time |
|
Rev Time |
|
| Received By |
mcruz |
Date |
2018-05-17 |
Time |
|
Sent To |
|
|
| Notes |
| 2018-05-17 15:58:56 | NOTE - GENERATOR SHALL BE AT LEAST 3.5 FEET FROM SIDE | | | PROPERTY LINE. | | | | | | M. CRUZ | | | ASSOCIATE PLANNER | | | 561-822-1442 | | | [email protected] |
|
|