Plan Review Details - Permit 18050714
Plan Review Stops For Permit 18050714
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-07-30 Cont ID  
Sent By rmcdouga Date 2018-07-30 Time 19:14 Rev Time 0.00
Received By rmcdouga Date 2018-07-30 Time 18:58 Sent To G
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-05-22 Cont ID  
Sent By rmcdouga Date 2018-05-22 Time 08:59 Rev Time 0.00
Received By rmcdouga Date 2018-05-22 Time 08:59 Sent To E
Notes
2018-05-22 08:59:22PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEM NOTED BELOW:
  
 1) THE SIGNED AND SEALED GENERATOR PAD ENGINEERING
 REQUIRES THE GENERATOR TO HAVE A MINIMUM WEIGHT OF 526
 POUNDS. THE PROPOSED 22KW GENERAC GENERATOR WEIGHS 466
 POUNDS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-07-27 Cont ID  
Sent By jleahy Date 2018-07-27 Time 16:30 Rev Time 0.00
Received By jleahy Date 2018-07-27 Time 16:30 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-05-23 Cont ID  
Sent By jleahy Date 2018-05-23 Time 10:26 Rev Time 0.00
Received By jleahy Date 2018-05-23 Time 10:26 Sent To I
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2018-08-20 Cont ID  
Sent By lcrespo Date 2018-08-20 Time 17:35 Rev Time 0.00
Received By lcrespo Date 2018-08-20 Time 17:24 Sent To  
Notes
2018-08-20 17:36:1808/20/18 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-07-31 Cont ID  
Sent By tklarge Date 2018-07-31 Time 10:44 Rev Time 0.00
Received By tklarge Date 2018-07-31 Time 10:16 Sent To I
Notes
2018-07-31 10:21:551) THE EXISTING GAS PLAN ON FILE IN CITY RECORDS SHOWS
 AN EXISTING 1 1/2 INCH GALVANIZED LINE AT THE OUTLET OF
 THE GAS METER AND THE SUBMITTED GAS PLAN FROM RELIABLE
 POWER SYSTEMS SHOWS AN EXISTING 3/4 INCH LINE. CLARIFY.
 2) THE EXISTING GAS PLAN ON FILE IN CITY RECORDS SHOWS
 AN EXISTING 1 INCH LINE TO THE INTERIOR OF THE
 STRUCTURE AND THE SUBMITTED GAS PLAN FROM RELIABLE
 POWER SYSTEMS SHOWS A 3/4 INCH LINE. CLARIFY.
 3) THE EXISTING GAS PLAN ON FILE IN CITY RECORDS SHOWS
 A FUTURE BBQ GRILL AT 55,000 BTU'S. THIS APPLIANCE MUST
 BE ADDED TO THE EXISTING LOAD . 2017 FBC-FUEL GAS
 SEC.401.4.
 4) THE EXISTING GAS PLAN SHOWS AN 1 1/4 INCH PE LINE TO
 THE POOL HEATER AND BBQ AT A DISTANCE OF 83 FEET. THIS
 DISTANCE SHALL BE USED FOR THE SIZING OF THE 2 PSI
 SYSTEM. 2017 FBC-FUEL GAS SEC.402.4.1.
  
 NOTE: I HAVE PLACED A COPY OF THE EXISTING GAS PLAN IN
 YOUR APPLICATION THAT YOU CAN USE AS A REFERENCE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-05-19 Cont ID  
Sent By tklarge Date 2018-05-19 Time 08:25 Rev Time 0.00
Received By tklarge Date 2018-05-19 Time 08:08 Sent To  
Notes
2018-05-19 08:25:33 
 1) SHOW THE TYPE OF PIPE AND PIPE SIZE AT THE OUTLET OF
 THE 2 PSI METER . WPB AMEND. TO FBC SEC. 107.2.1.
 2) SHOW THE PIPE SIZE OF THE SECTION OF PIPE TO THE
 EXISTING GAS LOAD.WPB AMEND. TO FBC SEC. 107.2.1.
 3) SPECIFY ON THE GAS DRAWING HOW THE 3/4 INCH
 GALVANIZED PIPE IS GOING TO BE INSTALLED. ABOVE-GROUND
 PIPING OUTDOORS SHALL COMPLY WITH 2017 FBCR
 SEC.G2415.9, G2415.11.
 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FLEX
 CONNECTOR FOR THE GENERATOR. THE FLEX CONNECTOR SHALL
 BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE
 GENERATOR. 2017 FBCR SEC. G2422.1 (8).
 7) THE SEDIMENT TRAP AS DRAWN DOES NOT COMPLY WITH 2017
 FBCR SEC.G2419.4.
 8) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION SHEETS FOR THE REGULATOR. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION. 2017 FBCR
 SEC.G2421.1, FBC-FUEL GAS SEC. 410.1.
 9) LIST THE EXISTING GAS FIXTURES ON THE PLAN AND THE
 CORRESPONDING BTU LOAD FOR EACH APPLIANCE. WPB AMEND.
 TO FBC SEC .107.2.1, 2017 FBC-FUEL GAS SEC.402.1.
 10) THE EXISTING BTU LOAD LISTED ON THE GAS DRAWING
 DOES NOT CORRELATE WITH THE EXISTING GAS PLAN ON FILE
 WITH THE CITY. I HAVE PLACED A COPY OF THE GAS DRAWING
 FROM THE ORIGINAL PERMIT #01090269.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-08-20 Cont ID  
Sent By lcrespo Date 2018-08-20 Time 17:36 Rev Time 0.00
Received By lcrespo Date 2018-08-16 Time 13:32 Sent To  
Notes
2018-08-17 13:32:22RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-31 Cont ID  
Sent By tklarge Date 2018-07-31 Time 10:45 Rev Time 0.00
Received By tklarge Date 2018-07-16 Time 14:42 Sent To  
Notes
2018-07-17 14:42:48RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-23 Cont ID  
Sent By jleahy Date 2018-05-23 Time 10:26 Rev Time 0.00
Received By jleahy Date 2018-05-15 Time 11:11 Sent To  
Notes
2018-05-16 11:11:43ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 2 Status P Date 2018-07-23 Cont ID  
Sent By mcruz Date 2018-07-23 Time 13:43 Rev Time 0.00
Received By mcruz Date 2018-07-23 Time 13:37 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-07-23 Cont ID  
Sent By mcruz Date 2018-05-17 Time   Rev Time  
Received By mcruz Date 2018-05-17 Time   Sent To  
Notes
2018-05-17 15:58:56NOTE - GENERATOR SHALL BE AT LEAST 3.5 FEET FROM SIDE
 PROPERTY LINE.
  
 M. CRUZ
 ASSOCIATE PLANNER
 561-822-1442
 [email protected]