Plan Review Details - Permit 18050712
Plan Review Stops For Permit 18050712
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-07-26 Cont ID  
Sent By tklarge Date 2018-07-26 Time 11:45 Rev Time 0.00
Received By tklarge Date 2018-07-26 Time 11:45 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-05-19 Cont ID  
Sent By tklarge Date 2018-05-19 Time 08:01 Rev Time 0.00
Received By tklarge Date 2018-05-19 Time 08:01 Sent To  
Notes
2018-05-19 08:01:29 
 1) SHOW THE TYPE OF PIPE AND PIPE SIZE AT THE OUTLET OF
 THE 2 PSI METER . WPB AMEND. TO FBC SEC. 107.2.1.
 2) SHOW THE PIPE SIZE OF THE SECTION OF PIPE SERVING
 THE EXISTING GAS LOAD.WPB AMEND. TO FBC SEC. 107.2.1.
 3) THE BTU LOAD OF THE RANGE DOES NOT CORRELATE WITH
 THE BTU LOAD SHOWN UNDER PERMIT # 17111114. I HAVE
 INCLUDED A COPY IN YOUR APPLICATION FILE TO BE USED AS
 REFERENCE.
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FLEX
 CONNECTOR FOR THE GENERATOR. THE FLEX CONNECTOR SHALL
 BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE
 GENERATOR. 2017 FBCR SEC. G2422.1 (8).
 5) THE SEDIMENT TRAP AS DRAWN DOES NOT COMPLY WITH 2017
 FBCR SEC.G2419.4.
 6) THE LONGEST RUN THAT IS LISTED ON THE GAS DRAWING
 DOES NOT CORRELATE WITH THE ORIGINAL GAS PERMIT.SEE THE
 COPY OF THE ORIGINAL GAS PERRMIT IN THE APPLICATION
 FOLDER. GA
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-26 Cont ID  
Sent By tklarge Date 2018-07-26 Time 11:45 Rev Time 0.00
Received By tklarge Date 2018-07-26 Time 11:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-19 Cont ID  
Sent By tklarge Date 2018-05-19 Time 08:01 Rev Time 0.00
Received By tklarge Date 2018-05-19 Time 08:00 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved