Plan Review Details - Permit 18050711
Plan Review Stops For Permit 18050711
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-07-26 Cont ID  
Sent By rmcdouga Date 2018-07-26 Time 08:22 Rev Time 0.00
Received By rmcdouga Date 2018-07-26 Time 08:15 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-05-22 Cont ID  
Sent By rmcdouga Date 2018-05-22 Time 08:56 Rev Time 0.00
Received By rmcdouga Date 2018-05-22 Time 07:49 Sent To E
Notes
2018-05-22 08:56:02PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEM NOTED BELOW:
  
 1) THE SIGNED AND SEALED GENERATOR PAD ENGINEERING
 REQUIRES THE GENERATOR TO HAVE A MINIMUM WEIGHT OF 526
 POUNDS. THE PROPOSED 22KW GENERAC GENERATOR WEIGHS 466
 POUNDS.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-05-23 Cont ID  
Sent By jleahy Date 2018-05-22 Time 13:03 Rev Time 0.00
Received By jleahy Date 2018-05-22 Time 13:03 Sent To I
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-07-25 Cont ID  
Sent By tklarge Date 2018-07-25 Time 12:25 Rev Time 0.00
Received By tklarge Date 2018-07-25 Time 10:58 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-05-19 Cont ID  
Sent By tklarge Date 2018-05-19 Time 07:59 Rev Time 0.00
Received By tklarge Date 2018-05-19 Time 07:42 Sent To  
Notes
2018-05-19 07:57:32 
 1) SHOW THE TYPE OF PIPE AND PIPE SIZE AT THE OUTLET OF
 THE 2 PSI METER . WPB AMEND. TO FBC SEC. 107.2.1.
 2) SHOW THE PIPE SIZE OF THE SECTION OF PIPE SERVING
 THE EXISTING GAS LOAD.WPB AMEND. TO FBC SEC. 107.2.1.
 3) THE BTU LOAD OF THE RANGE DOES NOT CORRELATE WITH
 THE BTU LOAD SHOWN UNDER PERMIT # 17111114. I HAVE
 INCLUDED A COPY IN YOUR APPLICATION FILE TO BE USED AS
 REFERENCE.
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FLEX
 CONNECTOR FOR THE GENERATOR. THE FLEX CONNECTOR SHALL
 BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE
 GENERATOR. 2017 FBCR SEC. G2422.1 (8).
 5) THE SEDIMENT TRAP AS DRAWN DOES NOT COMPLY WITH 2017
 FBCR SEC.G2419.4.
 6) THE LONGEST RUN THAT IS LISTED ON THE GAS DRAWING
 DOES NOT CORRELATE WITH THE ORIGINAL GAS PERMIT.SEE THE
 COPY OF THE ORIGINAL GAS PERRMIT IN THE APPLICATION
 FOLDER. GA
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-26 Cont ID  
Sent By rmcdouga Date 2018-07-26 Time 08:23 Rev Time 0.00
Received By rmcdouga Date 2018-07-16 Time 13:54 Sent To  
Notes
2018-07-17 13:55:09RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-23 Cont ID  
Sent By jleahy Date 2018-05-23 Time 07:03 Rev Time 0.00
Received By jleahy Date 2018-05-15 Time 11:12 Sent To  
Notes
2018-05-16 11:12:56ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 2 Status P Date 2018-07-19 Cont ID  
Sent By mcruz Date 2018-07-19 Time 14:11 Rev Time 0.00
Received By mcruz Date 2018-07-19 Time 14:11 Sent To G
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By mcruz Date 2018-05-17 Time   Rev Time  
Received By   Date 2018-05-17 Time   Sent To PC
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved