| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1.[FBC 109]IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY |
| | IS REQUIRED. THE PLANS ARE TO BE STAMPED AND THE |
| | RECEIPT SHOWING THAT FEES DUE, IF APPLICABLE, PROVIDED. |
| | AFTER ALL OTHER REVIEWS HAVE PASSED, CHECK OUT ONE SET |
| | OF PLANS TO TAKE TO THE COUNTY. |
| | 561-233-5025 FOR MORE INFORMATION |
| | |
| | 2..[FBC 107.3.4.1] PRODUCT APPROVALS TO BE REVIEWED BY |
| | DESIGNER OF RECORD: |
| | A) PROVIDE ROOFING PRODUCT SUBMITTTAL. |
| | B) FOR DOOR PRODUCT FL 12509.3 PROVIDE THE DBPR COVER |
| | SHEET AND COPIES PRINTED AT THE CORRECT SIZE. |
| | C) PROVIDE AN INSTALLATION SCHEDULE OR OTHERWIZE |
| | SPECIFY THE CONNECTOR TO BE USED FOR THE SHUTTER |
| | PRODUCT NOA 17-0118.07. |
| | |
| | 3.[FBC 109.3]PROVIDE COPY OF PROPOSAL WITH CONTRACTOR |
| | TO SHOW WORK VALUE EQUAL TO $45,000.00, OR ADJUST VALUE |
| | TO MATCH ACTUAL COST OF WORK. PLEASE ADJUST FEE AT |
| | FRONT DESK AND PAY ADJUSTED PERMIT REVIEW FEE AT TIME |
| | OF RE-SUBMITTAL. |
| | |
| | 4.[FBC R301]PROVIDE SURVEY OF PROPERTY. SURVEY TO |
| | INCLUDE SLAB ELEVATION AND SHOW POSITIVE DRAINAGE FROM |
| | FOUNDATION. |
| | [FBC 110.7] PROVIDE PROFESSIONALLY PREPARED DRAINAGE |
| | PLAN. |
| | |
| | 5.[FBC E505]SHEET A-2 REFERENCES LEVEL 2 ALTERATION. |
| | THIS WOULD BE LEVEL 3 ALTERATION DUE TO MORE THAN 50% |
| | OF EXISTING BUILDING AREA INCORPORATED INTO THE WORK |
| | PROPOSED. |
| | |
| | 6.[FBC 107]PROVIDE DEMO PLAN TO SHOW EXISTING TO BE |
| | REMOVED. |
| | |
| | 7.[FBC R310.2.1]SHEET A-1 WINDOW G DOESN'T MEET EGRESS |
| | REQUIREMENTS. IT APPEARS TO BE 36"X60" IN ELEVATION |
| | VIEW, BUT THE TABLE STATES IT IS 24"X48". |
| | ALTERNATIVELY, DEMONSTRATE COMPLIANCE WITH FBCEB 702.5. |
| | |
| | 8.[FBC R608.8(2)]SHEET A-1 WINDOWS IN ELEVATION APPEAR |
| | TO GO ABOVE BOTTOM OF BEAM. CO-ORDINATE WINDOWS WITH |
| | BEAM AND ADD BEAM SCHEDULE TO SHOW WHAT IS PROVIDED |
| | ABOVE WINDOWS AND DOORS. PROVIDE LINTEL SCHEDULE IF |
| | APPLICABLE. |
| | |
| | 9.[FBC R802.10.1]SHEET A-1 ADD ROOF PITCH TO ELEVATION |
| | AND ELEVATION CALL OUTS AS APPLICABLE FOR BEAM LOCATES |
| | AND WINDOW SILL HEIGHTS. |
| | |
| | 10.[FBC R301.2(2)]SHEET A-1 PROVIDE CONNECTION DETAIL |
| | FOR DECORATIVE TRELLIS AT ENTRY FEATURE. |
| | |
| | 11.[FBC 301.1]SHEET A-1 ADD DETAIL CALL OUTS AS |
| | APPLICABLE. |
| | |
| | 12.[FBC R319]SHEET A-1 ADD NOTE FOR SITE ADDRESS. |
| | |
| | 13.[FBC E907]SHEET A-2 NOTE 16 WHERE COLUMNS, SLAB AND |
| | BEAM MEETS EXISTING. SHOW DETAILS/NOTES OF HOW NEW WORK |
| | TIES INTO EXISTING STRUCTURE AT THE SLAB, COLUMN AND |
| | BEAM. |
| | |
| | 14.[FBC 301.2.1]SHEET A-2 PRESSURES SHOWN IN ELEVATIONS |
| | DON'T MATCH THE PRESSURES IN THE TABLE. ALSO, THE TABLE |
| | SHOWS PRODUCT APPROVAL PRESSURES THAT DON'T MATCH THE |
| | PRODUST APPROVALS PROVIDED. |
| | |
| | 15.[FBC 301.2.1]SHEET A-2 PROVIDE WINDOW LABELS IN PLAN |
| | VIEW TO MATCH WHAT IS SHOWN IN ELEVATION. ONE LABEL H |
| | IS SHOWN, BUT IT WOULD NOT BE THE CORRECT LOCATION FOR |
| | WINDOW BEING CALLED OUT. |
| | |
| | 16.[FBC R305]SHEET A-2 PROVIDE CEILING HEIGHTS FOR ALL |
| | ROOMS. |
| | |
| | 17.[FBC R807]SHEET A-2, S-2 SHOW LOCATION AND SIZE OF |
| | ATTIC ACCESS. |
| | |
| | 18.[FBC R302.11]SHEET A-3 ADD FIREBLOCKING TO DETAIL ON |
| | TYPICAL WALL SECTION AS SHOWN IN FRONT PORCH SECTION. |
| | |
| | 19.[FBC R301.1]SHEET A-3 DETAIL OF TYPICAL WALL SECTION |
| | SHOW 16" U-BLOCK, BUT THE NOTE CALLS OUT 8"X8" BEAM |
| | WITH TWO #5 BARS. SHOW ACTUAL CONDITION TO MATCH BEAM |
| | SCHEDULE AND SHOW REINFORCING BARS IN SECTION. ALSO, |
| | CALL OUT STANDARD HOOKS FOR REBAR GOING INTO FOOTERS |
| | AND BEAMS. |
| | |
| | 20.[FBC R311.3.1]SHEET S-1 EGRESS LANDING SHALL NOT BE |
| | LESS THAN 1 1/2" LOWER THAN THE TOP OF THRESHOLD. |
| | |
| | 21.[FBC R806]SHEET S-2 PROVIDE ROOF VENTILATION |
| | CALCULATION. |
| | |
| | 22.[FBC E907]SHEET S-2 UPDATE NOTE #2 TO STATE 2017 FBC |
| | 6TH EDITION. |
| | UPDATE STRUCTURAL NOTES CONCRETE STRENGHT TO MATCH WHAT |
| | IS CALLED OUT ONFOUNDATION PLANS. FIX NOTES BETWEEN |
| | SLUMP TEST AND REINFORCED MASONRY (OVERLAPPING TEXT). |
| | |
| | 23.[FBC TABLE R301.7]SHEET S-2 ADD ALLOWABLE DEFLECTION |
| | L/240 FOR CEILINGS. |
| | |
| | 24. ENERGY SUBMITTAL TO BE SIGNED AT OWNER/AGENT |
| | SIGNATURE LINE. |
| | |
| | 25. [FBC 107.3.4.2] DEFERRED SUBMITTALS: IT IS PRESUMED |
| | THE ROOF TRUSS PACKAGE WILL BE DEFERRED. PLEASE |
| | ACKNOWLEGE. |
| | |
| | NOTE: |
| | ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF ADDITIONAL MATERIALS REQUESTED. |
| | |
| | |
| | |
| | |