Plan Review Details - Permit 18050698
Plan Review Stops For Permit 18050698
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-08-27 Cont ID  
Sent By dbattles Date 2018-08-27 Time 16:05 Rev Time 0.00
Received By dbattles Date 2018-08-27 Time 16:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-06-20 Cont ID  
Sent By skennedy Date 2018-06-20 Time 16:07 Rev Time 0.00
Received By skennedy Date 2018-06-20 Time 16:07 Sent To  
Notes
2018-06-20 16:08:55****CORRECTIONS****
 W.P.B. PERMIT: 18050698
  
 STEVEN KENNEDY
 ASSISTANT BUILDING OFFICIAL
 [email protected]
 561-805-6710
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1.[FBC 109]IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY
 IS REQUIRED. THE PLANS ARE TO BE STAMPED AND THE
 RECEIPT SHOWING THAT FEES DUE, IF APPLICABLE, PROVIDED.
 AFTER ALL OTHER REVIEWS HAVE PASSED, CHECK OUT ONE SET
 OF PLANS TO TAKE TO THE COUNTY.
 561-233-5025 FOR MORE INFORMATION
  
 2..[FBC 107.3.4.1] PRODUCT APPROVALS TO BE REVIEWED BY
 DESIGNER OF RECORD:
 A) PROVIDE ROOFING PRODUCT SUBMITTTAL.
 B) FOR DOOR PRODUCT FL 12509.3 PROVIDE THE DBPR COVER
 SHEET AND COPIES PRINTED AT THE CORRECT SIZE.
 C) PROVIDE AN INSTALLATION SCHEDULE OR OTHERWIZE
 SPECIFY THE CONNECTOR TO BE USED FOR THE SHUTTER
 PRODUCT NOA 17-0118.07.
  
 3.[FBC 109.3]PROVIDE COPY OF PROPOSAL WITH CONTRACTOR
 TO SHOW WORK VALUE EQUAL TO $45,000.00, OR ADJUST VALUE
 TO MATCH ACTUAL COST OF WORK. PLEASE ADJUST FEE AT
 FRONT DESK AND PAY ADJUSTED PERMIT REVIEW FEE AT TIME
 OF RE-SUBMITTAL.
  
 4.[FBC R301]PROVIDE SURVEY OF PROPERTY. SURVEY TO
 INCLUDE SLAB ELEVATION AND SHOW POSITIVE DRAINAGE FROM
 FOUNDATION.
 [FBC 110.7] PROVIDE PROFESSIONALLY PREPARED DRAINAGE
 PLAN.
  
 5.[FBC E505]SHEET A-2 REFERENCES LEVEL 2 ALTERATION.
 THIS WOULD BE LEVEL 3 ALTERATION DUE TO MORE THAN 50%
 OF EXISTING BUILDING AREA INCORPORATED INTO THE WORK
 PROPOSED.
  
 6.[FBC 107]PROVIDE DEMO PLAN TO SHOW EXISTING TO BE
 REMOVED.
  
 7.[FBC R310.2.1]SHEET A-1 WINDOW G DOESN'T MEET EGRESS
 REQUIREMENTS. IT APPEARS TO BE 36"X60" IN ELEVATION
 VIEW, BUT THE TABLE STATES IT IS 24"X48".
 ALTERNATIVELY, DEMONSTRATE COMPLIANCE WITH FBCEB 702.5.
  
 8.[FBC R608.8(2)]SHEET A-1 WINDOWS IN ELEVATION APPEAR
 TO GO ABOVE BOTTOM OF BEAM. CO-ORDINATE WINDOWS WITH
 BEAM AND ADD BEAM SCHEDULE TO SHOW WHAT IS PROVIDED
 ABOVE WINDOWS AND DOORS. PROVIDE LINTEL SCHEDULE IF
 APPLICABLE.
  
 9.[FBC R802.10.1]SHEET A-1 ADD ROOF PITCH TO ELEVATION
 AND ELEVATION CALL OUTS AS APPLICABLE FOR BEAM LOCATES
 AND WINDOW SILL HEIGHTS.
  
 10.[FBC R301.2(2)]SHEET A-1 PROVIDE CONNECTION DETAIL
 FOR DECORATIVE TRELLIS AT ENTRY FEATURE.
  
 11.[FBC 301.1]SHEET A-1 ADD DETAIL CALL OUTS AS
 APPLICABLE.
  
 12.[FBC R319]SHEET A-1 ADD NOTE FOR SITE ADDRESS.
  
 13.[FBC E907]SHEET A-2 NOTE 16 WHERE COLUMNS, SLAB AND
 BEAM MEETS EXISTING. SHOW DETAILS/NOTES OF HOW NEW WORK
 TIES INTO EXISTING STRUCTURE AT THE SLAB, COLUMN AND
 BEAM.
  
 14.[FBC 301.2.1]SHEET A-2 PRESSURES SHOWN IN ELEVATIONS
 DON'T MATCH THE PRESSURES IN THE TABLE. ALSO, THE TABLE
 SHOWS PRODUCT APPROVAL PRESSURES THAT DON'T MATCH THE
 PRODUST APPROVALS PROVIDED.
  
 15.[FBC 301.2.1]SHEET A-2 PROVIDE WINDOW LABELS IN PLAN
 VIEW TO MATCH WHAT IS SHOWN IN ELEVATION. ONE LABEL H
 IS SHOWN, BUT IT WOULD NOT BE THE CORRECT LOCATION FOR
 WINDOW BEING CALLED OUT.
  
 16.[FBC R305]SHEET A-2 PROVIDE CEILING HEIGHTS FOR ALL
 ROOMS.
  
 17.[FBC R807]SHEET A-2, S-2 SHOW LOCATION AND SIZE OF
 ATTIC ACCESS.
  
 18.[FBC R302.11]SHEET A-3 ADD FIREBLOCKING TO DETAIL ON
 TYPICAL WALL SECTION AS SHOWN IN FRONT PORCH SECTION.
  
 19.[FBC R301.1]SHEET A-3 DETAIL OF TYPICAL WALL SECTION
 SHOW 16" U-BLOCK, BUT THE NOTE CALLS OUT 8"X8" BEAM
 WITH TWO #5 BARS. SHOW ACTUAL CONDITION TO MATCH BEAM
 SCHEDULE AND SHOW REINFORCING BARS IN SECTION. ALSO,
 CALL OUT STANDARD HOOKS FOR REBAR GOING INTO FOOTERS
 AND BEAMS.
  
 20.[FBC R311.3.1]SHEET S-1 EGRESS LANDING SHALL NOT BE
 LESS THAN 1 1/2" LOWER THAN THE TOP OF THRESHOLD.
  
 21.[FBC R806]SHEET S-2 PROVIDE ROOF VENTILATION
 CALCULATION.
  
 22.[FBC E907]SHEET S-2 UPDATE NOTE #2 TO STATE 2017 FBC
 6TH EDITION.
 UPDATE STRUCTURAL NOTES CONCRETE STRENGHT TO MATCH WHAT
 IS CALLED OUT ONFOUNDATION PLANS. FIX NOTES BETWEEN
 SLUMP TEST AND REINFORCED MASONRY (OVERLAPPING TEXT).
  
 23.[FBC TABLE R301.7]SHEET S-2 ADD ALLOWABLE DEFLECTION
 L/240 FOR CEILINGS.
  
 24. ENERGY SUBMITTAL TO BE SIGNED AT OWNER/AGENT
 SIGNATURE LINE.
  
 25. [FBC 107.3.4.2] DEFERRED SUBMITTALS: IT IS PRESUMED
 THE ROOF TRUSS PACKAGE WILL BE DEFERRED. PLEASE
 ACKNOWLEGE.
  
 NOTE:
 ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF ADDITIONAL MATERIALS REQUESTED.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-08-09 Cont ID  
Sent By ppetty Date 2018-08-09 Time 09:03 Rev Time 0.00
Received By ppetty Date 2018-08-09 Time 09:03 Sent To  
Notes
2018-08-09 09:05:25CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: OK, SEE COMMENTS BELOW.
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER
 561-805-6742
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-06-15 Cont ID  
Sent By jpearson Date 2018-06-15 Time 12:52 Rev Time 0.00
Received By jpearson Date 2018-06-15 Time 11:16 Sent To  
Notes
2018-06-15 12:52:07CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. FBC
 109.3
 2. FEED TO INTERIOR PANEL IS REQUIRED TO HAVE AN
 EQUIPMENT GROUNDING CONDUCTOR, SIZED PER CODE. PROVIDE
 CORRECTION. NEC 250.122; FBC RE E3704.6, 3607.3.1
 3. NOTE 6 STATES THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT
 APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE
 CORRECTION. NEC 406.12; FBC RE E4002.14
 4. NOTE FOR ENERGY COMPLIANCE STATES THAT 50% OF
 LIGHTING SHALL BE HIGH EFFICIENCY. PROVIDE CORRECTION:
 A MINIMUM OF 75 PERCENT OF THE LAMPS IN PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY
 LAMPS OR A MINIMUM OF 75 PERCENT OF THE PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH
 EFFICACY LAMPS. A NOTE WILL SUFFICE. FBC EC C405.1,
 R404.1
 5. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 6. ALL RECEPTACLES IN KITCHEN REQUIRE GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.6
 7. DINING ROOM CIRCUIT MUST BE RATED FOR 20 AMPS AND
 CANNOT FEED RECEPTACLES IN OTHER AREAS. PROVIDE
 CORRECTION. NEC 210.52(B); FBC RE E3901.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-09-21 Cont ID  
Sent By shill Date 2018-09-21 Time 16:29 Rev Time 0.00
Received By shill Date 2018-07-23 Time 09:11 Sent To  
Notes
2018-07-25 09:11:38R42

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-25 Cont ID  
Sent By skennedy Date 2018-06-25 Time 10:23 Rev Time 0.00
Received By skennedy Date 2018-05-15 Time 14:08 Sent To  
Notes
2018-05-16 14:08:19R23

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2018-09-21 Cont ID  
Sent By shill Date 2018-09-21 Time 16:28 Rev Time 0.00
Received By shill Date 2018-09-21 Time 16:28 Sent To  
Notes
2018-09-21 16:29:19MU 2018 024707
 $1,101.25 PAID
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-06-20 Cont ID  
Sent By skennedy Date 2018-06-20 Time 16:09 Rev Time 0.00
Received By skennedy Date 2018-06-20 Time 16:09 Sent To  
Notes
2018-06-20 16:11:271ST REVIEW: FBC 2017 6TH ED. RESIDENTIAL
 1ST REVIEW FBC 2017 EXISTING BUILDING
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND
 TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED
 WITH A COPY OF RECEIPT AS APPLICABLE.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-09-21 Cont ID  
Sent By ccole Date 2018-09-21 Time 16:14 Rev Time 0.00
Received By ccole Date 2018-09-21 Time 16:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-06-11 Cont ID  
Sent By hmoser Date 2018-06-11 Time 15:10 Rev Time 0.00
Received By hmoser Date 2018-06-11 Time 11:20 Sent To I
Notes
2018-06-11 15:09:56PLAN DENIED
 1) PROVIDE BATH EXHAUST ON PLAN. PER SECTION
 M1507.4 2017 RESIDENTIAL CODE.
 2) ENERGY CALCULATIONS MUST BE SIGNED BY
 THE OWNER AGENT. SECTION R103.1.1.2 2017
 FLORIDA ENERGY CODE.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status N Date 2018-09-04 Cont ID  
Sent By shill Date 2018-09-04 Time 10:47 Rev Time 0.00
Received By shill Date 2018-09-04 Time 10:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-06-15 Cont ID  
Sent By gjohnson Date 2018-06-15 Time 10:23 Rev Time 0.00
Received By gjohnson Date 2018-06-15 Time 10:23 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2018-08-27 Cont ID  
Sent By dbattles Date 2018-08-27 Time 16:07 Rev Time 0.00
Received By dbattles Date 2018-08-27 Time 16:06 Sent To  
Notes
2018-08-27 16:08:24PRODUCT APPROVAL FOR SHINGLE ROOF APPROVED.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2018-06-25 Cont ID  
Sent By skennedy Date 2018-06-25 Time 10:30 Rev Time 0.00
Received By skennedy Date 2018-06-25 Time 10:29 Sent To  
Notes
2018-06-25 10:30:46SEE COMMENT # 2 IN BUILDING REVIEW.

Review Stop Z ZONING
Rev No 2 Status P Date 2018-07-30 Cont ID  
Sent By awooten Date 2018-07-30 Time 15:39 Rev Time 0.00
Received By awooten Date 2018-07-30 Time 15:38 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2018-06-05 Cont ID  
Sent By AW Date 2018-06-05 Time 14:56 Rev Time 0.00
Received By awooten Date 2018-06-05 Time 14:54 Sent To  
Notes
2018-06-05 14:56:32*******************************************ZONING
 REVIEW FAILED*********************************
  
 THE ZONING IS SF-7.
  
 PROVIDE A COPY OF THE SURVEY OF PROPERTY SHOWING THE
 EXISTING STRUCTURE.
  
 THE VALUE OF THE CONSTRUCTION ($45,000) EXCEEDS 50% OF
 THE STRUCTURE'S VALUE ($60,000) ACCORDING TO THE P.B.C.
 PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT TO
 SECTION 94-441(C)(2) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE
 IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN
 ARTICLE XIV OF THE ZLDR. IF THE SITE CONFORMS TO
 ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN
 DEMONSTRATING COMPLIANCE SHALL BE INCLUDED WITH THE
 PERMIT RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO
 ARTICLE XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS
 PERMIT A SEPARATE LANDSCAPE PERMIT AND IRRIGATION
 PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE
 SITE INTO CONFORMITY.
  
 * PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION
 PERMIT. SHOWING THE FOLLOWING:
 RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM
 BEACH
 SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS
  
 O GROSS LOT SQUARE FOOTAGE MINUS
 O BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS
 O OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA)
 O ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
 O ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
  
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 561-822-1449