| 2018-05-18 13:14:23 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) WHAT IS THE PURPOSE OF THE PROPOSED 4 HEADS? WATER |
| | CURTAIN? INTENDED FIRE RATING? |
| | |
| | A WINDOW MAY BE PROTECTED WITH CLOSELY SPACED |
| | SPRINKLERS AND THE HEADS HAVE TO BE A SPECIFIC TYPE. |
| | (THE HEADS PROVIDED ARE REGULAR HEADS.) |
| | |
| | A MOVEABLE DOOR CAN NOT BE PROTECTED THE SAME WAY. ONCE |
| | THE DOOR IS OPENED, WHATEVER PROTECTION IS PROVIDED OR |
| | INTENDED IS LOST. |
| | |
| | PLEASE PROVIDE DETAILS, NARRATIVE, AND THE SPECIFIC |
| | FIRE CODE REFERENCE(S). |
| | |
| | |
| | |
| | 2) WHY DOES THE GLASS DOOR NEED TO BE PROTECTED? |
| | |
| | IS IT REQUIRED TO BE RATED? IS THE WALL IT IS INSTALLED |
| | IN A RATED WALL? |
| | |
| | PLEASE PROVIDE SPECIFIC DETAILS. |
| | |
| | |
| | |
| | 3) THERE IS NO ENGNEER STAMP OR REVIEW OF THIS DESIGN. |
| | THE ORIGINAL EOR MAY HAVE HAD A REASON TO RATE (?) THE |
| | WALL THIS GLASS DOOR WAS INSTALLED IN. |
| | |
| | WAS THE EOR CONSTULTED ON THIS CHANGE AND WAS |
| | THISDESIGN APPROVED? |
| | |
| | WAS LSM THE DESIGNER OF THE ORIGINAL FIRE SPRINKLER |
| | SYSTEM AND ARE THEY THE EOR? |
| | |
| | |
| | 4) THERE ARE NO HYDRALIC CALCULATIONS INDICATING THAT |
| | THE EXISTING SYSTEM IS CAPABLE TO PROVIDE THE REQUIRED |
| | WATER SUPPLY OF THIS DESIGN. |
| | |
| | PLEASE PROVIDE A HYDRALIC REVIEW. |
| | |
| | |
| | |
| | 5) WHAT AREA OF THE BUILDING IS THIS PROPOSED. THE |
| | REFERNECED PRIMARY PERMIT 16080044 INDICATED MULTIPLE |
| | FLOOR OF WORK BUT NO SPECIFIC GLASS DOOR WAS FOUND. |
| | |
| | PLEASE PROVIDE DETAILS. |
| | |
| | |
| | |
| | |
| | 6) WAS THIS GLASS DOOR A REVISION PERMIT OF THE ABOVE |
| | PRIMARY PERMIT AND PROPERLY APPROVED? |
| | |
| | PLEAE PROVIDE DETAILS. |
| | |
| | |
| | |
| | 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |