Plan Review Details - Permit 18050683
Plan Review Stops For Permit 18050683
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-05-18 Cont ID  
Sent By pleduc Date 2018-05-18 Time   Rev Time 0.00
Received By pleduc Date 2018-05-18 Time 12:15 Sent To I
Notes
2018-05-18 13:14:23THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) WHAT IS THE PURPOSE OF THE PROPOSED 4 HEADS? WATER
 CURTAIN? INTENDED FIRE RATING?
  
 A WINDOW MAY BE PROTECTED WITH CLOSELY SPACED
 SPRINKLERS AND THE HEADS HAVE TO BE A SPECIFIC TYPE.
 (THE HEADS PROVIDED ARE REGULAR HEADS.)
  
 A MOVEABLE DOOR CAN NOT BE PROTECTED THE SAME WAY. ONCE
 THE DOOR IS OPENED, WHATEVER PROTECTION IS PROVIDED OR
 INTENDED IS LOST.
  
 PLEASE PROVIDE DETAILS, NARRATIVE, AND THE SPECIFIC
 FIRE CODE REFERENCE(S).
  
  
  
 2) WHY DOES THE GLASS DOOR NEED TO BE PROTECTED?
  
 IS IT REQUIRED TO BE RATED? IS THE WALL IT IS INSTALLED
 IN A RATED WALL?
  
 PLEASE PROVIDE SPECIFIC DETAILS.
  
  
  
 3) THERE IS NO ENGNEER STAMP OR REVIEW OF THIS DESIGN.
 THE ORIGINAL EOR MAY HAVE HAD A REASON TO RATE (?) THE
 WALL THIS GLASS DOOR WAS INSTALLED IN.
  
 WAS THE EOR CONSTULTED ON THIS CHANGE AND WAS
 THISDESIGN APPROVED?
  
 WAS LSM THE DESIGNER OF THE ORIGINAL FIRE SPRINKLER
 SYSTEM AND ARE THEY THE EOR?
  
  
 4) THERE ARE NO HYDRALIC CALCULATIONS INDICATING THAT
 THE EXISTING SYSTEM IS CAPABLE TO PROVIDE THE REQUIRED
 WATER SUPPLY OF THIS DESIGN.
  
 PLEASE PROVIDE A HYDRALIC REVIEW.
  
  
  
 5) WHAT AREA OF THE BUILDING IS THIS PROPOSED. THE
 REFERNECED PRIMARY PERMIT 16080044 INDICATED MULTIPLE
 FLOOR OF WORK BUT NO SPECIFIC GLASS DOOR WAS FOUND.
  
 PLEASE PROVIDE DETAILS.
  
  
  
  
 6) WAS THIS GLASS DOOR A REVISION PERMIT OF THE ABOVE
 PRIMARY PERMIT AND PROPERLY APPROVED?
  
 PLEAE PROVIDE DETAILS.
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-18 Cont ID  
Sent By cpuell Date 2018-05-18 Time 15:20 Rev Time 0.00
Received By cpuell Date 2018-05-15 Time 13:41 Sent To  
Notes
2018-05-16 13:42:07ROUTED TO FIRE INBOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved