Plan Review Details - Permit 18050682
Plan Review Stops For Permit 18050682
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-05-23 Cont ID  
Sent By tklarge Date 2018-05-23 Time 09:09 Rev Time 0.00
Received By tklarge Date 2018-05-23 Time 09:06 Sent To I
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-05-18 Cont ID  
Sent By tklarge Date 2018-05-18 Time 09:11 Rev Time 0.00
Received By tklarge Date 2018-05-18 Time 08:23 Sent To I
Notes
2018-05-18 09:11:171) SHOW THE CORRESPONDING EHD FOR EACH SECTION OF CSST
 ON THE GAS DRAWING.
 2) THE SSIZE OF THE GALVANIZED LINE FROM THE GAS METER
 IS UNDERSIZED TO THE IS UNDERSIZED PER TABLE 402.4 (2).
 THE MAXIMUM BTU LOAD OF A 1 INCH GALVANIZED LINE AT 110
 FEET IS 173,000 BTU'S. THIS ONE INCH LINE MUST BE SIZED
 FOR THE BTU LOAD OF THE TANKLESS WATER HEATER,THE
 COOKTOP, THE GRILL AND THE DRYER.THIS LINE SHALL BE A
 MINIMUM OF 1 1/4 INCHES.
 3) THE PLANS NOTE THE INTERIOR LOAD AS 317,000 BUT I
 CALCULATE THE LOAD AS 68,000. THE EXTERIOR LOAD IS
 LISTED AS 520,000 BUT I CALCULATE THE LOAD AS 649,000.
 CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-05-23 Cont ID  
Sent By tklarge Date 2018-05-23 Time 09:09 Rev Time 0.00
Received By tklarge Date 2018-05-21 Time 13:16 Sent To  
Notes
2018-05-22 13:16:31RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-18 Cont ID  
Sent By tklarge Date 2018-05-18 Time 09:11 Rev Time 0.00
Received By tklarge Date 2018-05-15 Time 13:26 Sent To  
Notes
2018-05-16 13:26:40REVISION ROUTED TO TKLARGE