| Plan Review Stops For Permit 18050651 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2018-06-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-06-16 |
Time |
19:08 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-06-16 |
Time |
19:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-05-27 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-05-27 |
Time |
20:15 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-05-27 |
Time |
20:12 |
Sent To |
|
|
| Notes |
| 2018-05-27 20:15:32 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED | | | SETS OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) | | | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT | | | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER | | | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" | | | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS | | | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE | | | NEED "VOID", RENDERING THEM NOT USABLE. | | | | | | 2. VALUE IS TO INCLUDE LABOR AND MATERIALS, FBC 109. | | | | | | 3. SHEET 1, OCCUPANCY CLASSIFICATION IS INCORRECT, | | | REVISE (SHOULD BE R2), FBC B CHAPTER 3. | | | | | | 4. SHEET 0, REVISE TO INCLUDE SQUARE FOOT AREA, FBC | | | 107. | | | | | | 5. REVISE PLAN TO SHOW COMPLIANCE WITH FBC A FAIR | | | HOUSING (MASTER BATH REMODEL). | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
N |
Date |
2018-06-18 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-06-18 |
Time |
12:00 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-06-18 |
Time |
12:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-05-20 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-05-20 |
Time |
09:57 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-05-20 |
Time |
09:57 |
Sent To |
|
|
| Notes |
| 2018-05-20 09:57:45 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PLAN STATES THERE ARE NO CHANGES TO ELECRTICAL | | | EXCEPT UPGRADING OF OUTLETS TO GFCI. HOWEVER, CONTRACT | | | PROVIDED STATES THAT NEW LIGHTING IS BEING ADDED IN | | | SEVERAL LOCATIONS. PROVIDE ELECTRICAL PLAN FOR REVIEW, | | | SIGNED AND SEALED BY A LICENSED DESIGN PROFESSIONAL OR | | | THE ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H); | | | 471.025; WPB FBC 107.2.1, 107.3.5 | | | 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED | | | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, | | | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY | | | WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; WPB FBC | | | 107.3.5 | | | 3. SHOW ALL EXISTING RECEPTACLE OUTLETS IN KITCHEN AND | | | BATHROOMS, PROVIDE AFCI AND GFCI PROTECTION WHERE | | | APPLICABLE PER CODE. NEC 210.8, 210.12; FBC 107.2.1 | | | 4. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC 210.8(D) | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2018-06-15 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-06-15 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-06-15 |
Time |
12:53 |
Sent To |
|
|
| Notes |
| 2018-06-15 12:54:19 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) A REVIEW OF THE FIRE SPRINKLER COVERAGE IS REQUIRED. | | | | | | ANY AND ALL WORK ON THE FIRE SPRINKLER SYSTEM SHALL BE | | | DONE UNDER SEPARATE SHOP DRAWINGS AND BY CERTIFIED LIFE | | | SAFETY CONTRACTORS. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | 561-804-4709 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2018-05-18 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-05-18 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-05-18 |
Time |
14:58 |
Sent To |
|
|
| Notes |
| 2018-05-18 16:01:48 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) ANY AND ALL WORK ON THE FIRE SPRINKLER SYSTEM SHALL | | | BE DONE UNDER SEPARATE SHOP DRAWINGS AND BY CERTIFIED | | | LIFE SAFETY CONTRACTORS. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-06-18 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-06-18 |
Time |
12:01 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-06-12 |
Time |
13:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-05-29 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-05-29 |
Time |
10:57 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-05-15 |
Time |
13:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2018-06-18 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-06-18 |
Time |
12:01 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-06-18 |
Time |
12:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2018-05-29 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-05-29 |
Time |
10:57 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-05-29 |
Time |
09:50 |
Sent To |
I |
|
| Notes |
| 2018-05-29 10:41:37 | 1) SHOW THE LENGTH AND WIDTH DIMENSIONS OF THE PROPOSED | | | SHOWER. THE SHOWER SIZE AND DIMENSIONS SHALL COMPLY | | | WITH 2017 FBC-PLUMBING SEC.417.4. | | | 2) THIS BUILDING WAS CONSTRUCTED IN 2006 AND THEREFORE | | | WAS BUILT UNDER THE FAIR HOUSING ACT REQUIREMENTS. SHOW | | | THE REQUIRED CLEAR FLOOR SPACE ADJACENT TO THE SHOWER | | | AND PROVIDE THE LENGTH AND WIDTH DIMENSIONS AND THE | | | LOCATION OF THE CLEAR FLOOR SPACEE AS REQUIRED BY THE | | | FHA REQUIOREMENT #7. | | | 3) SHOW THE LOCATION OF THE SHOWER CONTROL VALVE FOR | | | THE PROPOSED SHOWER. | | | 4) PROVIDE DETAILS FOR THE REQUIRED REINFORCEMENT FOR | | | FUTURE GRAB BARS FOR THE PROPOSED SHOWER.SHOW THE TYPE | | | OF REINFORCEMENT MATERIAL, THE WIDTH OF THE | | | REINFORCEMENT AND THE MINIMUM AND MAXIMUM HEIGHT | | | DIMENSIONS OF THE REINFORCEMENT FROM THE FINISH FLOOR. | | | COMPLY WITH THE FAIR HOUSING ACT REQ. #6. | | | 5) SHT. 01 NOTES THE OCCUPANCY AS R-3. THIS IS | | | INCORRECT. REVISE THE OCCUPANCY TO READ R-2. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | | | | | | | |
|
|