Plan Review Details - Permit 18050651
Plan Review Stops For Permit 18050651
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-06-16 Cont ID  
Sent By shill Date 2018-06-16 Time 19:08 Rev Time 0.00
Received By shill Date 2018-06-16 Time 19:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-05-27 Cont ID  
Sent By shill Date 2018-05-27 Time 20:15 Rev Time 0.00
Received By shill Date 2018-05-27 Time 20:12 Sent To  
Notes
2018-05-27 20:15:32****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED
 SETS OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 2. VALUE IS TO INCLUDE LABOR AND MATERIALS, FBC 109.
  
 3. SHEET 1, OCCUPANCY CLASSIFICATION IS INCORRECT,
 REVISE (SHOULD BE R2), FBC B CHAPTER 3.
  
 4. SHEET 0, REVISE TO INCLUDE SQUARE FOOT AREA, FBC
 107.
  
 5. REVISE PLAN TO SHOW COMPLIANCE WITH FBC A FAIR
 HOUSING (MASTER BATH REMODEL).
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2018-06-18 Cont ID  
Sent By skennedy Date 2018-06-18 Time 12:00 Rev Time 0.00
Received By skennedy Date 2018-06-18 Time 12:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-05-20 Cont ID  
Sent By jpearson Date 2018-05-20 Time 09:57 Rev Time 0.00
Received By jpearson Date 2018-05-20 Time 09:57 Sent To  
Notes
2018-05-20 09:57:45CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN STATES THERE ARE NO CHANGES TO ELECRTICAL
 EXCEPT UPGRADING OF OUTLETS TO GFCI. HOWEVER, CONTRACT
 PROVIDED STATES THAT NEW LIGHTING IS BEING ADDED IN
 SEVERAL LOCATIONS. PROVIDE ELECTRICAL PLAN FOR REVIEW,
 SIGNED AND SEALED BY A LICENSED DESIGN PROFESSIONAL OR
 THE ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H);
 471.025; WPB FBC 107.2.1, 107.3.5
 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; WPB FBC
 107.3.5
 3. SHOW ALL EXISTING RECEPTACLE OUTLETS IN KITCHEN AND
 BATHROOMS, PROVIDE AFCI AND GFCI PROTECTION WHERE
 APPLICABLE PER CODE. NEC 210.8, 210.12; FBC 107.2.1
 4. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC 210.8(D)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-06-15 Cont ID  
Sent By pleduc Date 2018-06-15 Time   Rev Time 0.00
Received By pleduc Date 2018-06-15 Time 12:53 Sent To  
Notes
2018-06-15 12:54:19THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) A REVIEW OF THE FIRE SPRINKLER COVERAGE IS REQUIRED.
  
 ANY AND ALL WORK ON THE FIRE SPRINKLER SYSTEM SHALL BE
 DONE UNDER SEPARATE SHOP DRAWINGS AND BY CERTIFIED LIFE
 SAFETY CONTRACTORS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-05-18 Cont ID  
Sent By pleduc Date 2018-05-18 Time   Rev Time 0.00
Received By pleduc Date 2018-05-18 Time 14:58 Sent To  
Notes
2018-05-18 16:01:48THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ANY AND ALL WORK ON THE FIRE SPRINKLER SYSTEM SHALL
 BE DONE UNDER SEPARATE SHOP DRAWINGS AND BY CERTIFIED
 LIFE SAFETY CONTRACTORS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-06-18 Cont ID  
Sent By skennedy Date 2018-06-18 Time 12:01 Rev Time 0.00
Received By skennedy Date 2018-06-12 Time 13:49 Sent To  
Notes
2018-06-13 13:53:20B14

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-29 Cont ID  
Sent By tklarge Date 2018-05-29 Time 10:57 Rev Time 0.00
Received By tklarge Date 2018-05-15 Time 13:29 Sent To  
Notes
2018-05-16 13:29:46B04

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-06-18 Cont ID  
Sent By skennedy Date 2018-06-18 Time 12:01 Rev Time 0.00
Received By skennedy Date 2018-06-18 Time 12:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-05-29 Cont ID  
Sent By tklarge Date 2018-05-29 Time 10:57 Rev Time 0.00
Received By tklarge Date 2018-05-29 Time 09:50 Sent To I
Notes
2018-05-29 10:41:371) SHOW THE LENGTH AND WIDTH DIMENSIONS OF THE PROPOSED
 SHOWER. THE SHOWER SIZE AND DIMENSIONS SHALL COMPLY
 WITH 2017 FBC-PLUMBING SEC.417.4.
 2) THIS BUILDING WAS CONSTRUCTED IN 2006 AND THEREFORE
 WAS BUILT UNDER THE FAIR HOUSING ACT REQUIREMENTS. SHOW
 THE REQUIRED CLEAR FLOOR SPACE ADJACENT TO THE SHOWER
 AND PROVIDE THE LENGTH AND WIDTH DIMENSIONS AND THE
 LOCATION OF THE CLEAR FLOOR SPACEE AS REQUIRED BY THE
 FHA REQUIOREMENT #7.
 3) SHOW THE LOCATION OF THE SHOWER CONTROL VALVE FOR
 THE PROPOSED SHOWER.
 4) PROVIDE DETAILS FOR THE REQUIRED REINFORCEMENT FOR
 FUTURE GRAB BARS FOR THE PROPOSED SHOWER.SHOW THE TYPE
 OF REINFORCEMENT MATERIAL, THE WIDTH OF THE
 REINFORCEMENT AND THE MINIMUM AND MAXIMUM HEIGHT
 DIMENSIONS OF THE REINFORCEMENT FROM THE FINISH FLOOR.
 COMPLY WITH THE FAIR HOUSING ACT REQ. #6.
 5) SHT. 01 NOTES THE OCCUPANCY AS R-3. THIS IS
 INCORRECT. REVISE THE OCCUPANCY TO READ R-2.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
  
  
  