Plan Review Details - Permit 18050617
Plan Review Stops For Permit 18050617
Review Stop AD ADDRESSING
Rev No 2 Status N Date 2018-12-12 Cont ID  
Sent By shill Date 2018-12-12 Time 12:06 Rev Time 0.00
Received By shill Date 2018-12-12 Time 12:06 Sent To  
Notes
2018-12-12 12:07:07PROVISO - PRIOR TO CO

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2018-08-27 Cont ID  
Sent By shill Date 2018-08-27 Time 18:06 Rev Time 0.00
Received By shill Date 2018-08-27 Time 18:06 Sent To  
Notes
2018-08-27 18:07:03FOR ADDRESSING, PLEASE CONTACT (PREFERABLY VIA EMAIL):
  
 MICHAEL ORIO
 GIS SUPPORT SPECIALIST
 [email protected]
 CITY OF WEST PALM BEACH
 INFORMATION TECHNOLOGY DEPARTMENT
 401 CLEMATIS STREET, WEST PALM BEACH, FLORIDA 33401
 P: 561.494.1080
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2018-12-12 Cont ID  
Sent By shill Date 2018-12-12 Time 12:06 Rev Time 0.00
Received By shill Date 2018-12-12 Time 12:06 Sent To  
Notes
2018-12-12 12:08:03PROVISO: PROVIDE PRIOR TO CO PER CONVERSATION WITH
 SHERYL, ELEVATED EXPEDITING
 561 601 7721
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-12-08 Cont ID  
Sent By shill Date 2018-12-08 Time 16:47 Rev Time 0.00
Received By shill Date 2018-12-08 Time 16:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-10-06 Cont ID  
Sent By shill Date 2018-10-06 Time 15:25 Rev Time 0.00
Received By shill Date 2018-10-06 Time 15:25 Sent To  
Notes
2018-10-06 15:25:27****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. SHEET S1.1 IS NOTED AS PRELIMINARY UNLESS SIGNED &
 SEALED, FS471, PROVIDE A DOCUMENT SIGNED AND SEALED.
  
 2ND REVIEW, DOCUMENT IS NOT DIGITALLY SIGNED. A PAPER
 ORIGINAL IS REQUIRED IF ENGINEER DOES NOT HAVE A
 DIGITAL SIGNATURE.
  
 2. PLEASE ADVISE AS TO RESOLUTION OF CONTACT WITH
 ADDRESSING; SEE ADDRESS REVIEW. THIS WAS NOT INCLUDED
 IN THE RESPONSE LETTER.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-08-27 Cont ID  
Sent By shill Date 2018-08-27 Time 18:01 Rev Time 0.00
Received By shill Date 2018-08-27 Time 18:01 Sent To  
Notes
2018-08-27 18:05:43****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. SHEET S1.1 IS NOTED AS PRELIMINARY UNLESS SIGNED &
 SEALED, FS471, PROVIDE A DOCUMENT SIGNED AND SEALED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-06-16 Cont ID  
Sent By shill Date 2018-06-16 Time 19:48 Rev Time 0.00
Received By shill Date 2018-06-16 Time 19:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2018-10-30 Cont ID  
Sent By jpearson Date 2018-10-30 Time 14:12 Rev Time 0.00
Received By jpearson Date 2018-10-30 Time 14:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-10-01 Cont ID  
Sent By jpearson Date 2018-09-28 Time 07:56 Rev Time 0.00
Received By jpearson Date 2018-09-28 Time 07:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-08-23 Cont ID  
Sent By jpearson Date 2018-08-20 Time 08:41 Rev Time 0.00
Received By jpearson Date 2018-08-20 Time 08:41 Sent To  
Notes
2018-08-23 14:59:25LAURA RECEIVED NEW APPLICATION WITH UPDATED VALUE BASED
 ON CONTRACT FOR WORK. CHANGED STATUS TO PASS.
  
  
2018-08-20 08:41:14CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. FBC
 109.3
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED.
 7. CORRECTED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-06-26 Cont ID  
Sent By jpearson Date 2018-06-26 Time 19:10 Rev Time 0.00
Received By jpearson Date 2018-06-26 Time 19:10 Sent To  
Notes
2018-06-26 19:10:49CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. FBC
 109.3
 2. ALL RECEPTACLES IN KITCHEN/PREP AREAS REQUIRE GFCI
 PROTECTION. PROVIDE CORRECTION. NEC 210.8
 3. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC
 105.1, 107.2.1
 4. PROVIDE LIGHTING PLAN. WPB FBC 107.2.1
 5. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2
 6. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. FBC EC C405.2
 7. EMERGENCY AND EXIT LIGHTS ARE REQUIRED TO BE FED
 FROM THE GENERAL LIGHTING CIRCUIT IN THE AREA. PROVIDE
 CORRECTION. NEC 700.12(F)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2018-10-30 Cont ID  
Sent By jpearson Date 2018-10-30 Time 15:16 Rev Time 0.00
Received By jpearson Date 2018-10-30 Time 15:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2018-10-24 Cont ID  
Sent By scaldero Date 2018-10-24 Time 11:32 Rev Time 0.00
Received By scaldero Date 2018-10-24 Time 11:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-09-17 Cont ID  
Sent By scaldero Date 2018-09-17 Time 13:40 Rev Time 0.00
Received By scaldero Date 2018-09-17 Time 13:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-08-01 Cont ID  
Sent By scaldero Date 2018-08-01 Time 14:09 Rev Time 0.00
Received By scaldero Date 2018-08-01 Time 14:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-06-07 Cont ID  
Sent By scaldero Date 2018-06-07 Time 13:42 Rev Time 0.00
Received By scaldero Date 2018-06-07 Time 11:18 Sent To  
Notes
2018-06-07 13:42:59PERMIT # 18050617
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 GENERAL COMMENTS:
  
 1) UPDATE THE CODE LIST TO REFERENCE THE 6TH EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2015 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 2) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2018-12-12 Cont ID  
Sent By gjohnson Date 2018-12-12 Time 11:42 Rev Time 0.00
Received By gjohnson Date 2018-12-12 Time 11:42 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2018-10-11 Cont ID  
Sent By gjohnson Date 2018-10-11 Time 09:01 Rev Time 0.00
Received By gjohnson Date 2018-10-11 Time 06:36 Sent To  
Notes
2018-10-11 09:01:243RD REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 GAS COMMENTS:
  
 3RD REQUEST PREVIOUS COMMENT NOT COMPLIED 2. TYPE OF
 GAS (LP OR NATURAL).WPB AMEND. TO FBC SEC. 107.2.1. THE
 RESPONSE LETTER LIST THE TYPE OF GAS AS LP THE NOTE ON
 THE PLAN DOES NOT LIST A TYPE OF GAS IT DOES HAVE A
 SIZING TABLE FOR NATURAL GAS AND SHOWS A METER PLEASE
 PLACE NOTE ON THE GAS RISER TO CLARIFY.
  
 2ND REQUEST NOT COMPLIED 3. PROVIDE ROOF PLAN SHOWING
 GAS PIPING . WPB AMEND. TO FBC SEC. 107.2.1 RESPONSE
 LETTER LIST A ROOF PLAN ON M-1 THERE IS NO ROOF PLAN
 SHOWN ON M-1 PROVIDE ROOF PLAN TO SHOW GAS PIPING,
 INLET OF COMBUSTION AIR DUCT AND EXHAUST PIPING AND
 MAKE UP AIR INTAKES WITH THE DIMENSIONS BETWEEN THEM.
  
 NEW COMMENTS:
  
 1. PROVIDE DETAIL SHOWING DISTANCE BETWEEN INTAKE FOR
 COMBUSTION AIR DUCT EXHAUST VENT AND ANY OTHER INTAKES
 ON THE ROOF. PER WPB AMEND TO FBC 107.2.1
  
 2. THE SIZING TABLE IS FOR LESS THAN 2PSI BUT UNDER ONE
 OF THE NOTES FOR GAS IT LIST 2PSI PLEASE CLARIFY LIST
 PRESSURE ON RISER. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-08-28 Cont ID  
Sent By gjohnson Date 2018-08-28 Time 09:58 Rev Time 0.00
Received By gjohnson Date 2018-08-28 Time 09:58 Sent To  
Notes
2018-08-28 10:07:062ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 GAS COMMENTS:
  
  
  
 PREVIOUS COMMENT NOT COMPLIED 2. TYPE OF GAS (LP OR
 NATURAL).WPB AMEND. TO FBC SEC. 107.2.1. THE RESPONSE
 LETTER LIST THE TYPE OF GAS AS LP THE NOTE ON THE PLAN
 DOES NOT LIST A TYPE OF GAS IT PLEASE CLARIFY
  
 PREVIOUS COMMENT NOT COMPLIED 3. SUBMIT CALCULATIONS
 FOR COMBUSTION AIR PER THE 2017 FBC-FUEL GAS CODE
 SEC.304.1, 614.6 (CLOTHES DRYERS) OR 2017 FBC-RES. SEC.
 G 2407.1 AND G2439.4 (CLOTHES DRYERS). NOT SHOWN ON P-3
 AS INDICATED IN RESPONSE LETTER.
  
 PREVIOUS COMMENT PARTIALLY COMPLIED5. SUBMIT A DETAIL
 SHOWING THE TYPE OF VENT, LOCATION, SIZE, TERMINATION
 POINT, HEIGHT ABOVE THE ROOF AND ANCHORING DETAILS OF
 THE GAS VENT(S) PER 2017 FBC-FUEL GAS SECS. 502 THRU
 505 OR 2017 FBC-RES. SEC.G2426 THROUGH G2439. PLEASE
 PROVIDE THE FOLLOWING THE SIZE OF VENT PIPING, THE
 LENGTH FROM GAS APPLIANCE TO TERMINATION POINT.
  
 PREVIOUS COMMENT NOT COMPLIED 7. PROVIDE AN ENGINEERED
 DETAIL DRAWING FOR THE WATER HEATER STAND SHALL BE
 RATED TO A MIN OF 1000LB. PER WPB AMEND TO FBC 107.2.1
 . I COULD NOT LOCATE SHT. S-1 LISTED IN RESPONSE LETTER
  
 NEW COMMENT:
  
 1. PROVIDE SIZING TABLE USED TO SIZE SYSTEM SHOW ON
 PLAN. WPB AMEND. TO FBC SEC. 107.2.1 AND FBC FG 402.4
  
 2. SHOW REGULATORS. DRIP LEG AND SHUT OFFVALVE ON RISER
 REQUIRED FOR 2LB SYSTEM. PER FBC FG 410.1 AND 410.2
  
 3. PROVIDE ROOF PLAN SHOWING GAS PIPING . WPB AMEND. TO
 FBC SEC. 107.2.1
  
 4. SHOW GAS PIPING TO THE METER ON THE RISER AND ALL
 CUT SECTIONS OF PIPING TO METER. WPB AMEND. TO FBC SEC.
 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-06-28 Cont ID  
Sent By gjohnson Date 2018-06-28 Time 12:27 Rev Time 0.00
Received By gjohnson Date 2018-06-28 Time 12:27 Sent To  
Notes
2018-06-28 14:34:391ST REVIEW: FBC 2017 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
  
 GAS COMMENTS:
  
 1. THE GAS WATER HEATER SCHEDULE LIST THE WH AT
 75,000BTU THE GAS RISER SHOWS IT AT 60,00BTU PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 2. TYPE OF GAS (LP OR NATURAL).WPB AMEND. TO FBC SEC.
 107.2.1.
  
 3. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC-FUEL GAS CODE SEC.304.1, 614.6 (CLOTHES DRYERS) OR
 2017 FBC-RES. SEC. G 2407.1 AND G2439.4 (CLOTHES
 DRYERS).
  
 4. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3
 THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3.
  
 5. SUBMIT A DETAIL SHOWING THE TYPE OF VENT, LOCATION,
 SIZE, TERMINATION POINT, HEIGHT ABOVE THE ROOF AND
 ANCHORING DETAILS OF THE GAS VENT(S) PER 2017 FBC-FUEL
 GAS SECS. 502 THRU 505 OR 2017 FBC-RES. SEC.G2426
 THROUGH G2439.
  
 6. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 7. PROVIDE AN ENGINEERED DETAIL DRAWING FOR THE WATER
 HEATER STAND SHALL BE RATED TO A MIN OF 1000LB. PER WPB
 AMEND TO FBC 107.2.1
  
 8. USING THE SIZING TABLE LISTED ON THE PLAN 200
 DEVELOPED LENGTH 132,00 BTU THE THE SYSTEM IS
 UNDERSIZED IT SHALL BE 11/4" UP TO THE FIRST TEE FOR
 THE RTU THEN 1" TO THE WATER HEATER. PER FBC FG TABLE
 402.4(1)
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-12-12 Cont ID  
Sent By gjohnson Date 2018-12-12 Time 11:42 Rev Time 0.00
Received By gjohnson Date 2018-10-19 Time 10:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-10-11 Cont ID  
Sent By gjohnson Date 2018-10-11 Time 09:43 Rev Time 0.00
Received By gjohnson Date 2018-09-13 Time 13:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-28 Cont ID  
Sent By gjohnson Date 2018-08-28 Time 10:46 Rev Time 0.00
Received By gjohnson Date 2018-07-31 Time 13:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-28 Cont ID  
Sent By gjohnson Date 2018-06-28 Time 14:34 Rev Time 0.00
Received By gjohnson Date 2018-06-04 Time 09:09 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2018-06-16 Cont ID  
Sent By shill Date 2018-06-16 Time 19:48 Rev Time 0.00
Received By shill Date 2018-06-16 Time 19:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2018-11-08 Cont ID  
Sent By ccole Date 2018-11-08 Time 16:21 Rev Time 0.00
Received By ccole Date 2018-11-08 Time 15:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2018-10-04 Cont ID  
Sent By ccole Date 2018-10-04 Time 11:17 Rev Time 0.00
Received By ccole Date 2018-10-04 Time 11:17 Sent To  
Notes
2018-10-04 11:32:373RD REVIEW FBC-2017 MECHANICAL
 PERMIT #18050617
 10/4/18
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REVISED SHEET P-1: ACCORDING TO THE MANUFACTURER'S
 SPECIFICATIONS THE AO. SMITH BT-80 GAS-FIRED WATER
 HEATER REQUIRES A NATURAL DRAFT CATEGORY I B-VENT NOT A
 CATAGORY III POSITIVE PRESSURE VENT AS THE DRAWING
 INDICATES. PLEASE CORRECT SND SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE WATER HEATER AND VENT ASSEMBLY.
  
 2) REVISED P-2: THE COMBUSTION AIR CALCULATIONS ARE
 INCORRECT- 24"X24"X7'-0" = 28 CUBIT FT. IF USING THE
 STANDARD METHOD UNDER SECTION 304.5.1 FBC FG THE
 REQUIRED VOLUME SHALL BE 50 CUBIT FT. PER 1,000 BTUH.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-08-22 Cont ID  
Sent By ccole Date 2018-08-22 Time 13:53 Rev Time 0.00
Received By ccole Date 2018-08-22 Time 13:53 Sent To  
Notes
2018-08-22 13:54:39MECHANICAL PROVISOS;
  
 1) SEPARATE PERMIT REQUIRED FOR THE WALK-IN COOLER AND
 FREEZER,
  
 2) EF-3 OVER OVEN SHALL OPERATE WHENEVER THE APPLIANCE
 IS OPERATING.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-06-20 Cont ID  
Sent By ccole Date 2018-06-20 Time 09:21 Rev Time 0.00
Received By ccole Date 2018-06-20 Time 09:21 Sent To  
Notes
2018-06-20 09:50:261ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18050617
 6/20/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1: A DUCT SMOKE DETECTOR IS REQUIRED IN THE
 SUPPLY AIR SYSTEM OF THE RTU- SECTION 606.2.1 FBC M,
  
 2) M-1 & M-2: THE OUTSIDE AIR CALCULATIONS ARE
 INDICATING 0.7 CFMS OF O/A FOR THE KITCHEN, HOWEVER
 TABLE 403.3.1.1 REQUIRES AN EXHAUST SYSTEM FOR THE
 KITCHEN AT A RATE OF 0.70 CFMS PER SQ. FT. THERE IS NO
 EXHAUST SYSTEM SHOWN ON THE PLAN FOR THE KITCHEN.
  
 3) A-4, M-1, & M-2: SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE OVEN/PROOFER AND REFER TO
 SECTION 507.3. A TYPE II HOOD IS REQUIRED FOR THE OVEN,
 OR IF A HOOD IS NOT REQUIRED PER THE MANUFACTURER, THEN
 AN EXHAUST SYSTEM SIZED AT 0.70 CFMS FOR 100 SQ. FT. OF
 THE OCCUPYING SPACE OF THE OVEN IS REQUIRED
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2018-12-12 Cont ID  
Sent By gjohnson Date 2018-12-12 Time 11:41 Rev Time 0.00
Received By gjohnson Date 2018-12-12 Time 11:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-10-11 Cont ID  
Sent By gjohnson Date 2018-10-11 Time 09:43 Rev Time 0.00
Received By gjohnson Date 2018-10-11 Time 09:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-08-28 Cont ID  
Sent By gjohnson Date 2018-08-26 Time   Rev Time 0.00
Received By gjohnson Date 2018-08-26 Time   Sent To  
Notes
2018-08-28 09:55:37APPROVED NO COMMENTS PER GEORGE JOHNSON 8/28/18
2018-08-27 09:46:20REVIEW BY GJOHNSON. COMMENTS TO BE ADDED ON 8/28/18.

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-06-28 Cont ID  
Sent By gjohnson Date 2018-06-28 Time 12:27 Rev Time 0.00
Received By gjohnson Date 2018-06-27 Time 08:41 Sent To  
Notes
2018-06-28 12:26:491ST REVIEW: FBC 2017 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. T-1 THE DESIGN CODES SHALLLL BE
 2017 FLORIDA BUILDING CODE - BUILDING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE -PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - MECHANICAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 2. SHOW COMPLIANCE WITH FBC ACC 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER.
  
 3. SHOW COMPLIANCE WITH FBC ACC 604.4 SEATS. THE SEAT
 HEIGHT OF A WATER CLOSET ABOVE THE FINISH FLOOR SHALL
 BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM)
 MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS SHALL
 NOT BE SPRUNG TO RETURN TO A LIFTED POSITION.
  
 4. SHT. P-2/ 018 DETAIL #2THE VENT SHALL RISE VERTICAL
 TO A POINT ABOVE FLOOD LEVEL RIM OF THE FLOOR DRAIN
 BEFORE IT CAN TURN AND RUN HORIZONTAL AND SHAL COMPLY
 WITH FBC PL 905.3, 905.4
  
 5. A BACKFLOW IS REQUIRED FOR THE ICE MACHINE, WATER
 FILTER, TEA BREWER AND CARBONATOR SHALL COMPLY WITH FBC
 PL 608.3, 608.16.10, 608.16.1
  
 6. SHT. P-3/019 THE VENT FOR THE FLOOR DRAIN AT THE
 DRINK MACHINE AND THE GREASE INTERCEPTOR SHALL RISE
 VERTICAL TO A POINT ABOVE FLOOD LEVEL RIM OF THE FLOOR
 DRAIN BEFORE IT CAN TURN AND RUN HORIZONTAL AND SHAL
 COMPLY WITH FBC PL 905.3, 905.4
  
 7. PROVIDE MANUFACTURE SPECIFICATION SHOWING A PIPING
 DETAIL OR A PIPING DETAIL ON THE PLAN FOR THE GREASE
 INTERCEPTOR. PER WPB AMEND TO FBC 107.2.1
  
 8. SHT. P-2 / 018 NOTE #2 THE MIXING VALVE SHALL
 CONFORM TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 1 Status P Date 2018-08-28 Cont ID  
Sent By gjohnson Date 2018-08-28 Time 09:56 Rev Time 0.00
Received By gjohnson Date 2018-08-28 Time 09:56 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status P Date 2018-12-12 Cont ID  
Sent By shill Date 2018-12-12 Time 12:09 Rev Time 0.00
Received By shill Date 2018-12-12 Time 12:09 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status F Date 2018-12-08 Cont ID  
Sent By shill Date 2018-12-08 Time 16:44 Rev Time 0.00
Received By shill Date 2018-12-08 Time 16:44 Sent To  
Notes
2018-12-08 16:45:29SHEET S1.1 IS NOT DIGITALLY SIGNED.
 PLEASE CALL ME - 561-805-6724 TO DISCUSS RESOLUTION.
 I'LL WALK YOU THROUGH HOW TO DETERMINE THAT IT IS
 SIGNED AND DOES NOT JUST APPEAR TO BE SIGNED (AS IN
 THIS CASE), AND I'LL ACCEPT THE PAGE VIA EMAIL
 ([email protected]).
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2018-10-30 Cont ID  
Sent By jpearson Date 2018-10-30 Time 14:02 Rev Time 0.00
Received By jpearson Date 2018-10-30 Time 14:02 Sent To  
Notes
2018-10-30 14:01:59SHEET S1.1 IS NOT DIGITALLY SIGNED/SEALED. PROVIDE
 CORRECTION. FS 471/481; WPB FBC 107.1
  
 ALL OTHER SHEETS OK.
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2018-09-28 Cont ID  
Sent By jpearson Date 2018-09-28 Time 11:40 Rev Time 0.00
Received By jpearson Date 2018-09-28 Time 11:40 Sent To  
Notes
2018-09-28 11:40:40SHEET S1.1 IS NOT DIGITALLY SIGNED/SEALED. FS 471/481;
 WPB FBC 107.1
  
 ALL OTHER SHEETS OK.
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2018-08-27 Cont ID  
Sent By shill Date 2018-08-27 Time 17:58 Rev Time 0.00
Received By shill Date 2018-08-27 Time 17:58 Sent To  
Notes
2018-08-27 17:59:34SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 A, M, E, P SHEETS ARE OK
 S 1.1 IS PRELIMINARY AND NOT SIGNED & SEALED
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-06-16 Cont ID  
Sent By shill Date 2018-06-16 Time 19:42 Rev Time 0.00
Received By shill Date 2018-06-16 Time 19:42 Sent To  
Notes
2018-06-16 19:42:32SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. DIGITAL SIGNATURES/SEALS ARE IN ACCORDANCE WITH FS
 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE NEXT
 REVIEW CYCLE REQUIRE REVIEW.