Plan Review Details - Permit 18050588
Plan Review Stops For Permit 18050588
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-08-15 Cont ID  
Sent By cthroop Date 2018-08-15 Time 16:43 Rev Time 0.00
Received By cthroop Date 2018-08-15 Time 16:26 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-07-14 Cont ID  
Sent By shill Date 2018-07-14 Time 12:18 Rev Time 0.00
Received By shill Date 2018-07-14 Time 12:18 Sent To  
Notes
2018-07-14 12:19:30****CORRECTIONS****
 W.P.B. PERMIT: 18050588 (2ND REVIEW)
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. OK
  
 2. OK
  
 3. COMMENT NOT ADDRESSED.
 PROVIDE SOILS REPORT.
 FBC 1803.1 GENERAL.GEOTECHNICAL INVESTIGATIONS SHALL BE
 CONDUCTED IN ACCORDANCE WITH SECTION 1803.2 AND
 REPORTED IN ACCORDANCE WITH SECTION 1803.6. WHERE
 REQUIRED BY THE BUILDING OFFICIAL OR WHERE GEOTECHNICAL
 INVESTIGATIONS INVOLVE IN-SITU TESTING, LABORATORY
 TESTING OR ENGINEERING CALCULATIONS, SUCH
 INVESTIGATIONS SHALL BE CONDUCTED BY A REGISTERED
 DESIGN PROFESSIONAL.
  
 4. OK
  
 5. OK
  
 6. NEW COMMENT DUE TO ADJUSTED ELEVATION NAV88.
 [FBC R322.2.2]ENCLOSED AREA BELOW DESIGN FLOOD
 ELEVATION (GARAGE). FOLLOW R322.2.2.1 FOR INSTALLATION
 HEIGHTS OF FLOOD VENTS.
  
 NOTE:IF OPEN WEB TYPE FLOOR JOISTS ARE BEING USED THEN
 SMOKE COMPARTMENTS WILL BE NEEDED [FBC R302.12].
  
 THIS PERMIT WILL BE ISSUED WITH PROVISO:
 BUILDING UNDER CONSTRUCTION ELEVATION CERTIFICATE IS
 REQUIRED PRIOR TO CONCRETE POUR
 FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS REQUIRED
 PRIOR TO CO

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-06-15 Cont ID  
Sent By cthroop Date 2018-06-15 Time 11:24 Rev Time 0.00
Received By cthroop Date 2018-06-13 Time 17:27 Sent To  
Notes
2018-06-15 11:38:24BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. STRUCTURE APPEARS TO BE PARTIALLY IN FLOOD ZONE AE.
 PROVIDE CURRENT SURVEY. SURVEYOR TO IDENTIFY BOUNDARIES
 OF FLOOD ZONE.
  
 R322.1 GENERAL.
 BUILDINGS AND STRUCTURES CONSTRUCTED IN WHOLE OR IN
 PART IN FLOOD HAZARD AREAS (INCLUDING A OR V ZONES) AS
 ESTABLISHED IN TABLE R301.2(1) SHALL BE DESIGNED AND
 CONSTRUCTED IN ACCORDANCE WITH THE PROVISIONS CONTAINED
 IN THIS SECTION. BUILDINGS AND STRUCTURES LOCATED IN
 WHOLE OR IN PART IN IDENTIFIED FLOODWAYS SHALL BE
 DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ASCE 24.
  
 1A. AS OF OCTOBER 5, 2017, THE FEDERAL EMERGENCY
 MANAGEMENT AGENCY (FEMA) ESTABLISHED A NEW FLOOD
 INSURANCE RATE MAP (FIRM) UTILIZING THE RECENTLY
 COMPLETED FLOOD HAZARD DETERMINATION (FHD) FOR THE CITY
 OF WEST PALM BEACH, FL.
 1B. ALL NEW BASE FLOOD ELEVATIONS (BFE) SHALL BE BASED
 ON NAVD88 DATUM. ON AUGUST 23, 2017, THE CITY OF WEST
 PALM BEACH, BY ORDINANCE, ESTABLISHED A TWO FOOT
 FREEBOARD ABOVE THE (BFE).
 1C. YOU MAY SUBMIT A NEW SURVEY SHOWING ALL EXISTING
 AND PROPOSED ELEVATIONS BASED ON NAVD88 DATUM PLUS TWO
 FEET OF FREEBOARD OR THE ENGINEER OF RECORD (EOR) MAY
 ADD A STATEMENT TO THE STRUCTURAL PLAN THAT THE DESIGN
 FLOOD ELEVATION (DFE) WILL BE 8.00 FEET NAVD88 BASED ON
 THE (BFE) OF 6.00 FEET FOR FLOOD ZONE AE PLUS TWO FEET
 OF FREEBOARD.
  
 2. OWNER/AGENT TO SIGN ENERGY SUBMITTAL.
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 3. PROVIDE SOILS REPORT.
 FBC 1803.1 GENERAL.GEOTECHNICAL INVESTIGATIONS SHALL BE
 CONDUCTED IN ACCORDANCE WITH SECTION 1803.2 AND
 REPORTED IN ACCORDANCE WITH SECTION 1803.6. WHERE
 REQUIRED BY THE BUILDING OFFICIAL OR WHERE GEOTECHNICAL
 INVESTIGATIONS INVOLVE IN-SITU TESTING, LABORATORY
 TESTING OR ENGINEERING CALCULATIONS, SUCH
 INVESTIGATIONS SHALL BE CONDUCTED BY A REGISTERED
 DESIGN PROFESSIONAL.
  
 4. BASED ON THE CURRENT BUILDING VALUATION DATA
 PUBLISHED BY THE INTERNATIONAL CODE COUNCIL, THE VALUE
 HAS BEEN CHANGED FRO $500,00 TO $522,876.
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 5. CHANGE THE APPLICABLE CODES FROM FBC EXISTING
 BUILDING CODE 2017 6TH EDITION TO FBC RESIDENTIAL
 BUILDING CODE 2017 6TH EDITION.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-06-04 Cont ID  
Sent By jleahy Date 2018-06-04 Time 17:19 Rev Time 0.00
Received By jleahy Date 2018-06-04 Time 17:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-08-15 Cont ID  
Sent By cthroop Date 2018-08-15 Time 16:43 Rev Time 0.00
Received By cthroop Date 2018-08-09 Time 13:47 Sent To  
Notes
2018-08-10 13:47:23RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-30 Cont ID  
Sent By thunt Date 2018-07-30 Time 09:20 Rev Time 0.00
Received By thunt Date 2018-06-21 Time 15:19 Sent To I
Notes
2018-06-22 15:19:54R20

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-15 Cont ID  
Sent By cthroop Date 2018-06-15 Time 13:04 Rev Time 0.00
Received By cthroop Date 2018-05-14 Time 16:40 Sent To I
Notes
2018-05-15 16:41:03R20

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2018-08-15 Cont ID  
Sent By cthroop Date 2018-08-15 Time 16:42 Rev Time 0.00
Received By cthroop Date 2018-08-15 Time 16:26 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-07-14 Cont ID  
Sent By shill Date 2018-07-14 Time 12:17 Rev Time 0.00
Received By shill Date 2018-07-14 Time 12:17 Sent To  
Notes
2018-07-14 12:18:25PROVIDE THE IMPACT FEE RECEIPT SHOWING THAT FEES DUE
 WERE PAID
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-06-15 Cont ID  
Sent By cthroop Date 2018-06-15 Time 11:23 Rev Time 0.00
Received By cthroop Date 2018-06-13 Time 17:27 Sent To  
Notes
2018-06-15 11:24:29BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-06-01 Cont ID  
Sent By hmoser Date 2018-06-01 Time 13:36 Rev Time 0.00
Received By hmoser Date 2018-05-31 Time 14:13 Sent To  
Notes
2018-06-01 13:38:51ENERGY CALCULATIONS MUST BE SIGNED BY OWNER / AGENT

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status P Date 2018-08-15 Cont ID  
Sent By cthroop Date 2018-08-15 Time 16:42 Rev Time 0.00
Received By cthroop Date 2018-08-15 Time 16:42 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2018-06-15 Cont ID  
Sent By cthroop Date 2018-06-15 Time 12:24 Rev Time 0.00
Received By cthroop Date 2018-06-15 Time 11:38 Sent To  
Notes
2018-06-15 12:26:06BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. STRUCTURE APPEARS TO BE PARTIALLY IN FLOOD ZONE AE
 WITH A BASE FLOOD ELEVATION OF 6.0 FEET NAVD. PROVIDE
 CURRENT SURVEY. SURVEYOR TO IDENTIFY BOUNDARIES OF
 FLOOD ZONE.
  
 R322.1 GENERAL.
 BUILDINGS AND STRUCTURES CONSTRUCTED IN WHOLE OR IN
 PART IN FLOOD HAZARD AREAS (INCLUDING A OR V ZONES) AS
 ESTABLISHED IN TABLE R301.2(1) SHALL BE DESIGNED AND
 CONSTRUCTED IN ACCORDANCE WITH THE PROVISIONS CONTAINED
 IN THIS SECTION. BUILDINGS AND STRUCTURES LOCATED IN
 WHOLE OR IN PART IN IDENTIFIED FLOODWAYS SHALL BE
 DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ASCE 24.
  
 1A. AS OF OCTOBER 5, 2017, THE FEDERAL EMERGENCY
 MANAGEMENT AGENCY (FEMA) ESTABLISHED A NEW FLOOD
 INSURANCE RATE MAP (FIRM) UTILIZING THE RECENTLY
 COMPLETED FLOOD HAZARD DETERMINATION (FHD) FOR THE CITY
 OF WEST PALM BEACH, FL.
 1B. ALL NEW BASE FLOOD ELEVATIONS (BFE) SHALL BE BASED
 ON NAVD88 DATUM. ON AUGUST 23, 2017, THE CITY OF WEST
 PALM BEACH, BY ORDINANCE, ESTABLISHED A TWO FOOT
 FREEBOARD ABOVE THE (BFE).
 1C. YOU MAY SUBMIT A NEW SURVEY SHOWING ALL EXISTING
 AND PROPOSED ELEVATIONS BASED ON NAVD88 DATUM PLUS TWO
 FEET OF FREEBOARD OR THE ENGINEER OF RECORD (EOR) MAY
 ADD A STATEMENT TO THE STRUCTURAL PLAN THAT THE DESIGN
 FLOOD ELEVATION (DFE) WILL BE 8.00 FEET NAVD88 BASED ON
 THE (BFE) OF 6.00 FEET FOR FLOOD ZONE AE PLUS TWO FEET
 OF FREEBOARD.
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-07-30 Cont ID  
Sent By thunt Date 2018-07-30 Time 09:18 Rev Time 0.00
Received By thunt Date 2018-07-30 Time 08:42 Sent To  
Notes
2018-07-30 09:20:02PASS WITH PROVISO.
  
 BATH #2 ON 2ND FLOOR ISOMETRIC IS SHOWING 2 WET VENTED
 FIXTURES BEYOND THE WET VENT. SUPPLY A CORRECTED
 ISOMETRIC BY 1ST INSPECTION. FBC R P3108.2.1

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-06-07 Cont ID  
Sent By lcrespo Date 2018-06-07 Time 15:57 Rev Time 0.00
Received By lcrespo Date 2018-06-07 Time 07:16 Sent To  
Notes
2018-06-07 15:57:4506/07/2018 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A SEPARATE PERMIT SHALL BE REQUIRED FOR IRRIGATION
 SYSTEM AND A BACKFLOW DEVICE, THE POTABLE WATER SUPPLY
 TO LAWN IRRIGATION SYSTEMS SHALL BE PROTECTED AGAINST
 BACKFLOW BY AN ATMOSPHERIC VACUUM BREAKER, A PRESSURE
 VACUUM BREAKER ASSEMBLY OR A REDUCED PRESSURE PRINCIPLE
 BACKFLOW PREVENTION ASSEMBLY. VALVES SHALL NOT BE
 INSTALLED DOWNSTREAM FROM AN ATMOSPHERIC VACUUM
 BREAKER. WHERE CHEMICALS ARE INTRODUCED INTO THE
 SYSTEM, THE POTABLE WATER SUPPLY SHALL BE PROTECTED
 AGAINST BACKFLOW BY A REDUCED PRESSURE PRINCIPLE
 BACKFLOW PREVENTION ASSEMBLY. 2017 FBC R2902.5.3 LAWN
 IRRIGATION SYSTEMS.
  
 2. POWER BATH WATER CLOSET NEEDS TO BE VENTED BY LAB
 WHICH IS ON TRUNK LINE. 2017 FBC R3101.2.1 VENTING
 REQUIRED.
  
 3. THE 4? PVC GOING TO SECOND FLOOR IS NOT REQUIRED PER
 CODE AND MAY BE TOO LARGE TO RUN IN TRUSSES. THE CODE
 WILL ALLOW A 3? PIPE BE USED PLEASE REFER TO P3004.1
 DWV SYSTEM LOAD.
  
 4. WATER HEATER PAN TERMINATION ON DRAIN PAN SHALL
 TERMINATE OUTSIDE BUILDING AND RELIEF SHALL TERMINATE
 IN PAN ON PAGE P001, 2017 FBC R 2801.6.2
  
 5. BACKFLOW PREVENTER DEVICE SHALL BE MIN 5? FROM METER
 PER UTILITIES DEPARTMENT AND PLEASE VISIT CITY OF WEST
 PALM BEACH UTILITY DEPARTMENT. YOU CAN REFER TO THEIR
 CROSS CONNECTION MANUAL IN THE CITY WEB SITE HTTP://WPB
 .ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLICATIONS/BA
 CKFLOW-CROSS-CONNECTION-CONTROL-MANUAL FOR MORE
 INFORMATION.
  
 6. ROMAN TUB STANDALONE REQUIRED A CONTROL VALVE BY A
 WATER TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3, EXCEPT WHERE SUCH PROTECTION IS
 OTHERWISE PROVIDED BY A COMBINATION TUB/SHOWER VALVE IN
 ACCORDANCE WITH SECTION P2708.4. FBC R 2713.3 BATHTUB
 AND WHIRLPOOL BATHTUB VALVES. THIS VALVE IF REQUIRED
 HAS TO BE ACCESSIBLE LOCATION LIKE UNDER A CABINET OR A
 WALL PANEL.
  
 7. WATER HEATER EF 0.92 ON A 50 GALLON OF FORM
 R405-2017 IS NOT CORRECT ACCORDING TO NEACA HOT WATER
 REGULATION 2015 AND IT SHOULD BE AT EF 0.95, PLEASE
 VISIT HTTP://WWW.CASHACME.COM/RESOURCES/NAECA-2015-REGU
 LATIONS/ FOR FURTHER DETAILS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2018-06-15 Cont ID  
Sent By cthroop Date 2018-06-15 Time 11:24 Rev Time 0.00
Received By cthroop Date 2018-06-14 Time 16:34 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2018-08-17 Cont ID  
Sent By awooten Date 2018-08-17 Time 15:56 Rev Time 0.00
Received By awooten Date 2018-08-17 Time 15:56 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2018-08-13 Cont ID  
Sent By awooten Date 2018-08-13 Time 16:01 Rev Time 0.00
Received By awooten Date 2018-08-13 Time 15:47 Sent To B
Notes
2018-08-13 16:01:29*********************************ZONING REVIEW
 FAILED**************************
  
 A SEPARATE LANDSCAPE AND IRRIGATION PERMIT IS REQUIRED.
 ONE OF THE LANDSCAPE PLANS SUBMITTED IN THIS PERMIT IS
 FOR 226 PURITAN. SPOKE TO D. BOWDEN AND WAS ADVISED
 THAT HE WILL COME AND SUBMIT SEPARATE LANDSCAPE PERMIT
 TOMORROW FOR 140 EDMORE.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2018-06-28 Cont ID  
Sent By awooten Date 2018-06-28 Time 15:13 Rev Time 0.00
Received By awooten Date 2018-06-28 Time   Sent To  
Notes
2018-06-28 15:13:14******************ZONING REVIEW
 FAILED******************************
  
 A SEPARATE LANDSCAPE AND IRRIGATION PLAN MUST BE
 SUBMITTED PRIOR TO THIS PERMIT BEING APPROVED OR A
 CONDITIONAL LANDSCAPE APPROVAL APPLICATION MUST BE
 SUBMITTED. PLEASE CONTACT ME FOR MORE INFORMATION.
  
 LANDSCAPING:
 PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION
 PERMIT APPLICATION. SHOWING THE FOLLOWING:
 RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM
 BEACH
 SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS
  
 O GROSS LOT SQUARE FOOTAGE MINUS
 O BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS
 O OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA)
 O ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
 O ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
  
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By AW Date 2018-05-23 Time   Rev Time 0.00
Received By awooten Date 2018-05-23 Time 14:56 Sent To  
Notes
2018-05-23 15:10:10************************************ZONING REVIEW
 FAILED**********************************
  
 ZONING CLASSIFICATION IS INCORRECT ON PLANS. THIS
 PROPERTY IS ZONED SF-7.
  
 PROVIDE A SURVEY.
  
 LANDSCAPING:
 PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION
 PERMIT APPLICATION. SHOWING THE FOLLOWING:
 RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM
 BEACH
 SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS
  
 O GROSS LOT SQUARE FOOTAGE MINUS
 O BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS
 O OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA)
 O ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
 O ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
  
 THE PROPOSED DRIVEWAY, POOL, AND FENCE REQUIRE A
 SEPARATE PERMIT.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy