Plan Review Details - Permit 18050549
Plan Review Stops For Permit 18050549
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-08-02 Cont ID  
Sent By skennedy Date 2018-08-02 Time 14:53 Rev Time 0.00
Received By skennedy Date 2018-08-02 Time 14:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-06-20 Cont ID  
Sent By rmcdouga Date 2018-06-20 Time 17:36 Rev Time 0.00
Received By rmcdouga Date 2018-06-20 Time 13:08 Sent To I
Notes
2018-06-20 17:36:47PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 REVISED TRUSS DRAWINGS DENIED BY BUILDING
  
 1) TRUSS TO TRUSS CONNECTIONS ARE NOT SPECIFIED ON THE
 STRUCTURAL PLANS BY THE DESIGNER OF RECORD FOR THE
 STRUCTURE. THE NOTE ON THE STRUCTURAL PLANS STATES
 "CONNECTION BY TRUSS COMPANY" FOR THESE CONNECTIONS.
 THE CONNECTORS THAT ARE TO BE USED FOR THE TRUSS TO
 TRUSS CONNECTIONS NEED TO BE SPECIFIED. FBC107.1
 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF CONSTRUCTION
 DOCUMENTS, STATEMENT OF SPECIAL INSPECTIONS,
 GEOTECHNICAL REPORT AND OTHER DATA SHALL BE SUBMITTED
 IN TWO OR MORE SETS WITH EACH PERMIT APPLICATION. THE
 CONSTRUCTION DOCUMENTS SHALL BE PREPARED BY A
 REGISTERED DESIGN PROFESSIONAL WHERE REQUIRED BY
 CHAPTER 471, FLORIDA STATUTES & 61G15 FLORIDA
 ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA STATUTES &
 61G1 FLORIDA ADMINISTRATIVE CODE. WHERE SPECIAL
 CONDITIONS EXIST, THE BUILDING OFFICIAL IS AUTHORIZED
 TO REQUIRE ADDITIONAL CONSTRUCTION DOCUMENTS TO BE
 PREPARED BY A REGISTERED DESIGN PROFESSIONAL.
  
 2) THE TRUSS DRAWING COVER PAGE SPECIFIES THE 2017 FBC
 AND THIS PROJECT IS PERMITTED UNDER THE 2014 FBC.
 PLEASE CORRECT.
  
 3) THE TRUSS ANCHOR ID TAGS FOR THE GIRDERS ON REVISED
 SHEET S-3 ARE SHOWN AT THE WRONG LOCATIONS. THE LINES
 ARE DRAWN TO THE WRONG TRUSSES. FBC 107.2.1
  
 4) THE EXPOSURE CATEGORY ON REVISED SHEET S-3 HAS BEEN
 CHANGED FROM THE APPROVED PLANS FROM C TO D AND THE
 WIND PRESSURES WERE INCREASED ACCORDINGLY. IN ORDER FOR
 THIS CHANGE TO BE APPROVED, THE OTHER PLAN SHEETS FROM
 THE APPROVED PLANS THAT SPECIFY THE EXPOSURE CATEGORY
 OR THE WIND LOAD PRESSURES WILL ALSO NEED TO BE
 REVISED. THE PRODUCT APPROVALS FOR THE COMPONENTS AND
 CLADDING WILL NEED TO BE REVIEWED TO SEE IF THEY WILL
 COMPLY WITH THE INCREASED PRESSURES FOR EXPOSURE D. FBC
 107.2.1
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-05-18 Cont ID  
Sent By cthroop Date 2018-05-18 Time 19:14 Rev Time 0.00
Received By rmcdouga Date 2018-05-18 Time 13:44 Sent To I
Notes
2018-05-18 16:19:17PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 REVISED TRUSS DRAWINGS DENIED BY BUILDING
  
 1) THE TRUSS LAYOUT PLAN SPECIFIES THE STRUCTURAL
 CONNECTORS FOR THE TRUSS TO TRUSS CONNECTIONS. THESE
 CONNECTIONS ARE NOT SPECIFIED ON THE STRUCTURAL PLANS
 BY THE ARCHITECT. THE NOTE ON THE STRUCTURAL PLANS
 STATES "CONNECTION BY TRUSS COMPANY" FOR THESE
 CONNECTIONS. THEREFORE, THE LAYOUT PLAN WHICH SPECIFIES
 THE STRUCTURAL CONNECTORS IS REQUIRED TO BE SIGNED AND
 SEALED. FBC107.1 GENERAL. SUBMITTAL DOCUMENTS
 CONSISTING OF CONSTRUCTION DOCUMENTS, STATEMENT OF
 SPECIAL INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA
 SHALL BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION. THE CONSTRUCTION DOCUMENTS SHALL BE
 PREPARED BY A REGISTERED DESIGN PROFESSIONAL WHERE
 REQUIRED BY CHAPTER 471, FLORIDA STATUTES & 61G15
 FLORIDA ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA
 STATUTES & 61G1 FLORIDA ADMINISTRATIVE CODE. WHERE
 SPECIAL CONDITIONS EXIST, THE BUILDING OFFICIAL IS
 AUTHORIZED TO REQUIRE ADDITIONAL CONSTRUCTION DOCUMENTS
 TO BE PREPARED BY A
 REGISTERED DESIGN PROFESSIONAL.
  
 2) THE TOP CORD DEAD LOAD FOR THE ROOF TRUSSES ON THE
 TRUSS DRAWINGS IS 7.0 PSF WHICH IS LESS THAN THE 15 PSF
 LISTED ON THE REVISED ROOF FRAMING PLAN S-3. THE PLANS
 SPECIFY A 4.5 : 12 SLOPE ROOF WITH CLAY "S" TILE.
 PLEASE REVIEW AND DETERMINE THE PROPER TOP CORD ROOF
 LOAD. FBC 107.2.1
  
 TRUSS DRAWING REPAIRS DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE TRUSS DRAWINGS ARE NOT SIGNED BY THE ENGINEER.
 61G15-23.003 PROCEDURES FOR PHYSICALLY SIGNING AND
 SEALING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS. ENGINEERING PLANS, SPECIFICATIONS, REPORTS
 OR OTHER DOCUMENTS WHICH MUST BE SIGNED, DATED AND
 SEALED IN ACCORDANCE WITH THE PROVISIONS OF SECTION
 471.025, F.S., AND RULE 61G15-23.001, F.A.C. MAY BE
 PHYSICALLY SIGNED, DATED AND SEALED AS PROVIDED HEREIN
 BY THE PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
 (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE
 LICENSEE'S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE'S SIGNATURE SHALL NOT BE
 USED.
 (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY
 CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY
 OVERLAPPING THE LICENSEE?S SIGNATURE ON EACH PAGE
 REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL
 NOT RENDER THE SIGNATURE ILLEGIBLE.
  
 2) PROVIDE A SIGNED AND SEALED LETTER FROM THE ENGINEER
 THAT PROVIDES AN EXPLANATION OF HIS TRUSS "REPAIR"
 DOCUMENTS AND THE REASON THAT IT IS BEING DONE. SPECIFY
 THE MATERIAL THAT IS BEING INSTALLED ON THE FLOOR.
 PROVIDE THE THICKNESS AND THE WEIGHT OF THE MATERIAL
 THAT IS TO BE INSTALLED. FBC 107.2.1.2
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-06-20 Cont ID  
Sent By rmcdouga Date 2018-06-20 Time 17:37 Rev Time 0.00
Received By rmcdouga Date 2018-06-12 Time 14:57 Sent To  
Notes
2018-06-13 14:57:12RESUB OF REVISION ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-18 Cont ID  
Sent By rmcdouga Date 2018-05-18 Time 19:14 Rev Time 0.00
Received By rmcdouga Date 2018-05-11 Time 10:43 Sent To  
Notes
2018-05-17 11:16:4005/17/18 REVISION SENT TO ROBERT MCDOUGAL.
  