Plan Review Details - Permit 18050512
Plan Review Stops For Permit 18050512
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-08-20 Cont ID  
Sent By cthroop Date 2018-08-20 Time 10:18 Rev Time 0.00
Received By cthroop Date 2018-08-20 Time 10:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-08-03 Cont ID  
Sent By cthroop Date 2018-08-03 Time 14:33 Rev Time 0.00
Received By cthroop Date 2018-08-03 Time 14:11 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-06-13 Cont ID  
Sent By cthroop Date 2018-06-13 Time 08:06 Rev Time 0.00
Received By cthroop Date 2018-06-11 Time 11:17 Sent To  
Notes
2018-06-13 08:48:06BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. VALUE APPEARS LOW FOR PROPOSED SCOPE OF WORK.
 THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE.
 YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE
 OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
  
 CITY OF WPB CHPT. 1 ? VALUE
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 2. REFERENCE WALL TYPE W-3 ON PLAN PAGE A-2 - PROVIDE
 INSULATION TYPE AND R-VALUE FOR EXTERIOR WALL INFILL.
 3. PROVIDE DEMENSIONS ON PROPOSED FLOOR PLANS.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 4. REFERENCE CONCRETE CURB DETAIL ON PLAN PAGE S-1. ANY
 CHANGE TO DESIGN MUST BE REVIEWED AND APPROVED BY
 DESINER OF RECORD.
 PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE,
 DATE AND SEAL OF THE ENGINEER PER FL ADMIN. CODE RULE
 61G15-23.001.
  
 5. PROVIDE SITE PLAN. SHOW LOCATION OF BUILDING TO
 OTHER STRUCTURES AND PROPERTY LINES.
 FBC 107.3.5.3 ? PROVIDE A SITE PLAN TO DEMONSTRATE
 SETBACKS AND BUILDING SEPARATION.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-08-02 Cont ID  
Sent By jleahy Date 2018-08-02 Time 11:24 Rev Time 0.00
Received By jleahy Date 2018-08-02 Time 11:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-06-06 Cont ID  
Sent By jleahy Date 2018-06-06 Time 12:55 Rev Time 0.00
Received By jleahy Date 2018-06-06 Time 12:55 Sent To  
Notes
2018-06-06 13:49:15FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E-1
  
 SMOKE ALARM MISSING AT THE BOTTOM OF THE STAIRWAY FOR
 THE SECOND FLOOR UNIT. ONE ON EACH LEVEL.
  
 R314.3 SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
  
 3.ON EACH ADDITIONAL STORY OF THE DWELLING, INCLUDING
 BASEMENTS AND HABITABLE ATTICS AND NOT INCLUDING CRAWL
 SPACES AND UNINHABITABLE ATTICS. IN DWELLINGS OR
 DWELLING UNITS WITH SPLIT LEVELS AND WITHOUT AN
 INTERVENING DOOR BETWEEN THE ADJACENT LEVELS, A SMOKE
 ALARM INSTALLED ON THE UPPER LEVEL SHALL SUFFICE FOR
 THE ADJACENT LOWER LEVEL PROVIDED THAT THE LOWER LEVEL
 IS LESS THAN ONE FULL STORY BELOW THE UPPER LEVEL.
  
 4.SMOKE ALARMS SHALL BE INSTALLED NOT LESS THAN 3 FEET
 (914 MM) HORIZONTALLY FROM THE DOOR OR OPENING OF A
 BATHROOM THAT CONTAINS A BATHTUB OR SHOWER UNLESS THIS
 WOULD PREVENT PLACEMENT OF A SMOKE ALARM REQUIRED BY
 SECTION R314.3.
  
 R314.3.1INSTALLATION NEAR COOKING APPLIANCES
 .
 SMOKE ALARMS SHALL NOT BE INSTALLED IN THE FOLLOWING
 LOCATIONS UNLESS THIS WOULD PREVENT PLACEMENT OF A
 SMOKE ALARM IN A LOCATION REQUIRED BY SECTION R314.3.
  
 1.IONIZATION SMOKE ALARMS SHALL NOT BE INSTALLED LESS
 THAN 20 FEET (6096 MM) HORIZONTALLY FROM A PERMANENTLY
 INSTALLED COOKING APPLIANCE.
  
 2.IONIZATION SMOKE ALARMS WITH AN ALARM-SILENCING
 SWITCH SHALL NOT BE INSTALLED LESS THAN 10 FEET (3048
 MM) HORIZONTALLY FROM A PERMANENTLY INSTALLED COOKING
 APPLIANCE.
  
 3.PHOTOELECTRIC SMOKE ALARMS SHALL NOT BE INSTALLED
 LESS THAN 6 FEET (1828 MM) HORIZONTALLY FROM A
 PERMANENTLY INSTALLED COOKING APPLIANCE
  
 KITCHEN OUTLET MISSING IN KITCHEN ON COUNTER NEXT TO
 STOVE 12" OR LARGER.
  
  
 PAGE E-2
  
 OUTLET NEEDED ON FRONT AND REAR OF UNIT #4 OUTSIDE
  
 E3901.7 OUTDOOR OUTLETS.
 NOT LESS THAN ONE RECEPTACLE OUTLET THAT IS READILY
 ACCESSIBLE FROM GRADE LEVEL AND LOCATED NOT MORE THAN 6
 FEET, 6 INCHES (1981 MM) ABOVE GRADE, SHALL BE
 INSTALLED OUTDOORS AT THE FRONT AND BACK OF EACH
 DWELLING UNIT HAVING DIRECT ACCESS TO GRADE LEVEL.
 BALCONIES, DECKS, AND PORCHES THAT ARE ACCESSIBLE FROM
 INSIDE OF THE DWELLING UNIT SHALL HAVE AT LEAST ONE
 RECEPTACLE OUTLET INSTALLED WITHIN THE PERIMETER OF THE
 BALCONY, DECK, OR PORCH. THE RECEPTACLE SHALL BE
 LOCATED NOT MORE THAN 6 FEET, 6 INCHES (1981 MM) ABOVE
 THE BALCONY, DECK, OR PORCH SURFACE. [210.52(E)]
  
  
 PAGE E-3
  
 LOAD CALCULATIONS SHOULD BE DONE IN ACCORDANCE WITH THE
 CODE, YOU CAN NOT TAKE A DEMAND ON EACH UNIT AND THEN
 JUST ADD THEM TOGETHER TO GET A TOTAL.
  
 250.94 INTERSYSTEM BONDING SYSTEM REQUIRED

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2018-06-13 Cont ID  
Sent By cthroop Date 2018-06-13 Time 09:09 Rev Time 0.00
Received By cthroop Date 2018-06-13 Time 09:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2018-05-21 Cont ID  
Sent By pleduc Date 2018-05-21 Time 10:13 Rev Time 0.00
Received By pleduc Date 2018-05-18 Time 16:55 Sent To  
Notes
2018-05-21 10:14:37THE PLANS INDICATED THIS IS A DUPLEX, EXEMPT FROM FIRE
 CODE REVIEW.

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-07-20 Cont ID  
Sent By tklarge Date 2018-07-20 Time 04:53 Rev Time 0.00
Received By tklarge Date 2018-07-20 Time 04:34 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-06-08 Cont ID  
Sent By tklarge Date 2018-06-08 Time 15:02 Rev Time 0.00
Received By tklarge Date 2018-06-08 Time 08:19 Sent To  
Notes
2018-06-08 08:19:271) SHT. A-1.1 - SHOW THE DISTANCE OF THE TANKLESS WATER
 HEATERS FROM ALL OPERABLE WINDOWS, DOORS AND BUILDING
 OPENINGS (INCLUDING SOFFIT VENTS). THE LOCATION OF THE
 TANKLESS WATER HEATERS SHALL COMPLY WITH THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS. WPB AMEND. TO
 FBC SEC. 107.2.1.
 2) SUBMIT TWO COPIES OF THE MANUFACTURER'S INSTALLATION
 MANUAL FOR THE TANKLESS WATER HEATERS. WPB AMEND. TO
 FBC SEC. 107.2.1.
 3) INDICATE ON THE PLAN IF THE FIREPLACE IS GAS OR
 SOLIDD FUEL BURNING.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2018-07-19 Cont ID  
Sent By fmittner Date 2018-07-19 Time 10:32 Rev Time 0.00
Received By fmittner Date 2018-07-19 Time 10:32 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2018-05-23 Cont ID  
Sent By fmittner Date 2018-05-23 Time 13:53 Rev Time 0.00
Received By fmittner Date 2018-05-23 Time 13:53 Sent To  
Notes
2018-05-23 13:54:41WINDOW PRODUCT/DETAILS NOT CLEAR....NEW WINDOWS SHALL
 BE 6/1 SINGLE HUNG WOOD OR ALUMINUM, WHITE FRAME, CLEAR
 GLASS. QUESTIONS CONTACT: FRIEDERIKE MITTNER, CITY
 HISTORIC PRESERVATION PLANNER AT (561) 822-1457 OR
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-03 Cont ID  
Sent By cthroop Date 2018-08-03 Time 14:34 Rev Time 0.00
Received By cthroop Date 2018-07-03 Time 15:20 Sent To  
Notes
2018-07-05 15:21:22C30

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-13 Cont ID  
Sent By cthroop Date 2018-06-13 Time 09:09 Rev Time 0.00
Received By cthroop Date 2018-05-10 Time 13:47 Sent To I
Notes
2018-05-14 13:47:44C13
 **TRAVELLING TOGETHER - 18050512 & 18050513**

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2018-08-03 Cont ID  
Sent By cthroop Date 2018-08-03 Time 14:33 Rev Time 0.00
Received By cthroop Date 2018-08-03 Time 14:11 Sent To  
Notes
2018-08-03 14:34:27NO NOTES

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2018-06-13 Cont ID  
Sent By cthroop Date 2018-06-13 Time 08:07 Rev Time 0.00
Received By cthroop Date 2018-06-11 Time 11:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-08-01 Cont ID  
Sent By hmoser Date 2018-08-01 Time 15:50 Rev Time 0.00
Received By hmoser Date 2018-08-01 Time 15:46 Sent To E
Notes
2018-08-01 15:50:13PASS PROVISO
 REFER TO SECTION R403.36 AIR HANDLING UNITS.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-07-25 Cont ID  
Sent By hmoser Date 2018-07-25 Time 15:00 Rev Time 0.00
Received By hmoser Date 2018-07-25 Time 11:41 Sent To  
Notes
2018-07-25 15:00:21PASS PROVISO
 REFER TO SECTION R403.3.6 AIR HANDLING UNITS
 2017 FLORIDA ENERGY CODE.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-06-11 Cont ID  
Sent By ccole Date 2018-06-11 Time 09:01 Rev Time 0.00
Received By ccole Date 2018-06-11 Time 08:55 Sent To  
Notes
2018-06-11 09:38:101ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18050512
 UNITS 1 & 2
 6/11/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 AC SYSTEMS- SECTION 312.1 FBC M.
  
 2) INDICATE HOW THE APARTMENTS ARE TO BE VENTILATED-
 NATURALLY IN ACCORDANCE WITH SECTION 402 FBC M, OR
 MECHANICALLY PER SECTION 403 FBC M. CHOOSE WHICHEVER
 METHOD AND PROVIDE CALCULATIONS.
  
 3) DESIGN CRITERIA: PROVIDE A LIST OF CURRENT CODES AND
 STANDARDS USED IN THE DESIGN OF THE PROPOSED PROJECT.
  
 4) INDICATE THE"CLASSIFICATION OF WORK" FOR THE
 PROPOSED PROJECT IN ACCORDANCE WITH SECTIONS 502, 503,
 504, 505, 506, 507, 508, & 09 FBC EX.
  
 5) SHEET M1: THE 2ND FLOOR AC CLOSET DOOR SHALL BE
 NON-COMBUSTIBLE OR HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT MORE
 THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E84 OR UL
 723.
  
 6) M1: THE PLANS INDICATE FIRE PLACES IN THE LIVING
 ROOMS OF THE1ST AND 2ND FLOOR APARTMENTS. PROVIDE
 COMPLETE INFOMATION ABOUT THESE UNITS- MAKES AND MODEL
 NUMBERS, TYPE OF FUEL, COMBUSTION AIR, VENTING PLANS,
 CLEARANCES TO COMBUSTIBLES ETC. MANUFACTURER'S
 SPECIFICATIONS MUST BE SUBMITTED WITH APPROVAL STAMPS
 BY THE EOR- SECTIONS 903 & 905 FBC M, AND SECTIONS 602,
 604, & 605 FBC FG.
  
 7) M1: SUBMIT MANUFACTURER'S SPECIFICATION FOR THE
 DRYER, RECIRCULATION HOOD, AND THE RANGE- SECTIONS
 504.1,505.1, & 917.1, FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-07-20 Cont ID  
Sent By tklarge Date 2018-07-20 Time 04:33 Rev Time 0.00
Received By tklarge Date 2018-07-20 Time 03:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-06-08 Cont ID  
Sent By tklarge Date 2018-06-08 Time 14:59 Rev Time 0.00
Received By tklarge Date 2018-06-07 Time 08:24 Sent To  
Notes
2018-06-07 14:21:441) THE WATER SUPPLY VALVES FOR THE STACKABLE
 WASHER/DRYER UNIT SHALL BE PROVIDED WITH ACCESS. 2017
 FBC-PLUMBING SEC.606.3.
 2) SHT. A-13 - SHOW THE WIDTH OF THE SHOWER IN UNIT #4
 ON THE FLOOR PLANS. THE SIZE OF THE SHOWER SHALL COMPLY
 WITH 2017 FBCV-PLUMBING SEC. 417.4.
 3) SHOW THE FIXTURE CLEARANCES OF THE PLUMBING FIXTURES
 IN ALL THE UNITS PER 2017 FBC-PLUMBING SEC.405.
 4) SUBMIT FIRESTOPPING DETAILS FOR ALL PIPE PENTRATIONS
 THROUGH THE FLOOR TO THE 2ND FLOOR.
 5) THE DEVELOPED LENGTH OF HOT OR TEMPERED WATER PIPING
 FROM THE SOURCE OF HOT WATER TO THE FIXTURES THAT
 REQUIRE HOT OR TEMPERED WATER SHALL NOT EXCEED 50 FEET
 PER 2017 FBC-PLUMBING SEC.607.2.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
  

Review Stop Z ZONING
Rev No 1 Status P Date 2018-05-23 Cont ID  
Sent By fmittner Date 2018-05-23 Time 13:54 Rev Time 0.00
Received By fmittner Date 2018-05-23 Time 13:54 Sent To  
Notes
***NONE***