Plan Review Details - Permit 18050484
Plan Review Stops For Permit 18050484
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-06-07 Cont ID  
Sent By jwitmer Date 2018-05-31 Time 13:24 Rev Time 0.00
Received By shill Date 2018-06-07 Time 19:13 Sent To  
Notes
2018-05-31 15:11:03CLICKED ON THE BUIDING LINE BY MISTAKE JLEAHY

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2018-06-22 Cont ID  
Sent By jleahy Date 2018-06-21 Time 09:56 Rev Time 0.00
Received By jpearson Date 2018-06-21 Time 09:56 Sent To I
Notes
2018-06-22 10:12:05CHANGED STATUS TO NR AND REMOVED ELECTRICAL SHEETS FROM
 THIS REVISION PER EMAIL FROM EOR.
  
  
  
2018-06-21 09:56:38CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE BLOCK NOTE THAT FIRE PUMP WILL BE UNDER
 SEPARATE PERMIT. WPB FBC 105.1, 107.2.1
 2. PROVIDE CORRECTED LOAD CALCULATION WITH ADDITION OF
 FIRE PUMP LOAD. NEC 220; WPB FBC 107.2.1, 107.3.5
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-05-31 Cont ID  
Sent By jleahy Date 2018-05-31 Time 15:10 Rev Time 0.00
Received By jleahy Date 2018-05-31 Time 15:09 Sent To  
Notes
2018-05-31 15:10:00FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E-DEW-02A
  
 CLOUDED AREA AT BOTTOM SHOWING FP NEED TO KNOW WHAT
 CIRCUITS ARE NEEDED AND SIZES AND WHERE FED FROM.
  
  
 PAGE E-DEW-15A
  
 SHOW LOCATION OF FIRE PUMP IN BUILDING. THE BLOWUP OF
 THE ROOM DOES NOT SHOW WHERE IT IS LOCATED.
  
 FIRE PUMP SKID AS A DESCRIPTION IS NOT ACCEPTABLE WHAT
 SIZE IS THE PUMP DOES IT HAVE AND CONTROLLER IF SO
 SUBMIT ALL PAPER WORK SHOWING LISTINGS FOR ALL FIRE
 PUMP EQUIPMENT.
  
 SOURCES OF POWER ARE THESE FROM FPL CITY DOES NOT
 ACCEPT FPL AS A RELIABLE SOURCE.
  
 HOW DO THE FEEDS ENTER THE BUILDING?? UNDERGROUND? WHAT
 TYPE OF PIPE? SIZE OF CONDUCTORS?
  
  
 REVISION SHOWS NO ADDED VALUE FOR THE FIRE PUMP AND
 CONTROLLER PLEASE ADD TO NEXT REVISION.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO
 PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG
 WITH THE CITY RESUBMITTAL FORM. ADDITIONALLY, INSERT
 CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE OR VOID THE PREVIOUSLY REVIEWED
 SHEETS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-05-18 Cont ID  
Sent By pleduc Date 2018-05-18 Time   Rev Time 0.00
Received By pleduc Date 2018-05-18 Time 12:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By jpearson Date 2018-06-22 Time 10:12 Rev Time 0.00
Received By lmarchan Date 2018-06-15 Time 15:55 Sent To  
Notes
2018-06-18 15:55:19RESUB OF REVISION ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-07 Cont ID  
Sent By shill Date 2018-06-07 Time 19:14 Rev Time 0.00
Received By shill Date 2018-05-10 Time 13:37 Sent To  
Notes
2018-05-15 10:34:00B03

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-05-23 Cont ID  
Sent By hmoser Date 2018-05-23 Time 14:50 Rev Time 0.00
Received By hmoser Date 2018-05-23 Time 14:49 Sent To  
Notes
***NONE***