Plan Review Details - Permit 18050464
Plan Review Stops For Permit 18050464
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-05-27 Cont ID  
Sent By shill Date 2018-05-27 Time 19:21 Rev Time 0.00
Received By shill Date 2018-05-27 Time 19:15 Sent To  
Notes
2018-05-27 19:21:44****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED
 SETS OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PAGES VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 2. FBC B 1609, THIS PARCEL IS LOCATED IN EXPOSURE C,
 REVISE DESIGN CRITERIA AND PRESSURES ACCORDINGLY.
  
 3. FBC 107, ENERGY CALC INPUT DATA IS INCOMPLETE; NO
 FENESTRATION SHOWN. REVISE OR CLARIFY. CHECK ALL.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-05-20 Cont ID  
Sent By jpearson Date 2018-05-20 Time 14:10 Rev Time 0.00
Received By jpearson Date 2018-05-20 Time 14:10 Sent To  
Notes
2018-05-20 14:10:26CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PANEL SCHEDULE PROVIDED ONLY SHOWS LOADS FOR 2 OF
 THE PHASES OF A 3 PHASE SYSTEM. PROVIDE A 3 PHASE
 PANELS SCHEDULE DETAILING THE LOAD FOR EACH PHASE TO
 CONFIRM THAT THE PANEL IS NOT OVERLOADED. SEE COMMENT
 #2 FOR WATER HEATER. ADDITIONALLY, ASSUMED LOADS CANNOT
 BE ACCEPTED. THIS PANEL IS CLOSE TO BEING OVERLOADED,
 PROVIDE ACCURATE LOAD CALCULATION. NEC 215.5, 408.4,
 408.30; WPB FBC 107.2.1
 2. PANEL SCHEDULE SHOWS A SR-20L WATER HEATER ON A 208
 VOLT CIRCUIT. THE MANUFACTURERS SPEC SHEET FOR THIS
 UNIT STATES THAT IT DRAWS 4160 WATTS, NOT 2400 AS SHOWN
 IN PANEL SCHEDULE. CLARIFY AND/OR CORRECT. NEC 110.3;
 WPB FBC 107.2.1
 3. PROVIDE GFCI PROTECTION FOR DRINKING FOUNTAIN. THE
 GFCI DEVICE MUST BE READILY ACCESSIBLE. NEC 422.5,
 422.52
 4. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-05-15 Cont ID  
Sent By pleduc Date 2018-05-15 Time   Rev Time 0.00
Received By pleduc Date 2018-05-14 Time 15:24 Sent To  
Notes
2018-05-15 13:44:42THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THERE IS NO INDICATION OF COMPLIANCE WITH THE
 CURRENT EDITION OF THE FLORIDA FIRE PREVENTION CODE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 6TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2015 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
 THERE DOES NOT APPEAR TO BE ANY CONFLICT; HOWEVER,
 PLEASE TAKE NOTE AND ENSURE COMPLIANCE AS THAT IS HOW
 IT WILL BE INSPECTED BY FIRE INSPECTORS.
  
  
  
 2) SHEET E 1 - THERE IS AN EXIT SIGN INDICATED AT THE
 END OF THE REAR CORRIDOR LEADING INTO A CONFERNECE
 ROOM. FROM THE CONFERNECE ROOM THERE IS A DOOR LEADING
 TO THE WAREHOUSE AND AN EXIT FROM THE WAREHOUSE.
  
 THE OCCUPANCY CAN SUUPORT THE ONE EXIT AT THE FRONT,
 BUT THE EXIT SIGN AT THE CONFERENCE ROOM DOOR NEEDS TO
 BE MOVE TO INSIDE THE CONFERENCE ROOM LEADING TO THE
 CORRIDOR.
  
 THE WAREHOUSE EXIT SIGN CAN STAD ALONE FROM THAT AREA.
  
 PER NFPA 101, CHAPTER 38 NEW BUSINESS
  
 38.2 MEANS OF EGRESS REQUIREMENTS.
 38.2.1 GENERAL.
 38.2.1.1 ALL MEANS OF EGRESS SHALL BE IN ACCORDANCE
 WITH CHAPTER 7 AND
 THIS CHAPTER.
  
 38.2.4.3 A SINGLE EXIT SHALL BE PERMITTED FOR A ROOM OR
 AREA WITH A TOTAL
 OCCUPANT LOAD OF LESS THAN 100 PERSONS, PROVIDED THAT
 ALL OF THE
 FOLLOWING CRITERIA ARE MET:
 (1) THE EXIT SHALL DISCHARGE DIRECTLY TO THE OUTSIDE AT
 THE LEVEL OF EXIT
 DISCHARGE FOR THE BUILDING.
 (2) THE TOTAL DISTANCE OF TRAVEL FROM ANY POINT,
 INCLUDING TRAVEL WITHIN
 THE EXIT, SHALL NOT EXCEED 100 FT (30 M).
 (3) THE TOTAL DISTANCE OF TRAVEL SPECIFIED IN
 38.2.4.3(2) SHALL BE ON THE
 SAME STORY, OR, IF TRAVERSING OF STAIRS IS NECESSARY,
 SUCH STAIRS SHALL
 NOT EXCEED 15 FT (4570 MM) IN HEIGHT, AND BOTH OF THE
 FOLLOWING
 ALSO SHALL APPLY:
 (A) INTERIOR STAIRS SHALL BE PROVIDED WITH COMPLETE
 ENCLOSURES TO
 SEPARATE THEM FROM ANY OTHER PART OF THE BUILDING, WITH
 NO
 DOOR OPENINGS THEREIN.
 (B) A SINGLE OUTSIDE STAIR IN ACCORDANCE WITH 7.2.2
 SHALL BE
 PERMITTED TO SERVE ALL STORIES PERMITTED WITHIN THE 15
 FT (4570
 MM) VERTICAL TRAVEL LIMITATION
  
 PER NFPA 101, CHAPTER 7 MEANS OF EGRESS.
  
 7.5.1.6 EXIT ACCESS FROM ROOMS OR SPACES SHALL BE
 PERMITTED TO BE
 THROUGH ADJOINING OR INTERVENING ROOMS OR AREAS,
 PROVIDED THAT SUCH
 ROOMS OR AREAS ARE ACCESSORY TO THE AREA SERVED.
 FOYERS, LOBBIES, AND
 RECEPTION ROOMS CONSTRUCTED AS REQUIRED FOR CORRIDORS
 SHALL NOT BE
 CONSTRUED AS INTERVENING ROOMS. EXIT ACCESS SHALL BE
 ARRANGED SO
 THAT IT IS NOT NECESSARY TO PASS THROUGH ANY AREA
 IDENTIFIED UNDER
 PROTECTION FROM HAZARDS IN CHAPTERS 11 THROUGH 43.
  
 PLEASE CHANGE THE LOCATION OF THE REAR EXIT SIGN.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-05 Cont ID  
Sent By gjohnson Date 2018-06-05 Time 15:44 Rev Time 0.00
Received By gjohnson Date 2018-05-10 Time 11:16 Sent To  
Notes
2018-05-11 11:16:26B30

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-05-15 Cont ID  
Sent By ccole Date 2018-05-15 Time 17:10 Rev Time 0.00
Received By ccole Date 2018-05-15 Time 17:10 Sent To  
Notes
2018-05-15 17:25:451ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18050464
 5/15/18
  
 CODES IN EFFECT:
 FBC BC- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC MC- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC RE- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC-SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1: REFER TO SECTION 1609.1.1 FBC BC AND
 PROVIDE THE WIND LOAD DESIGN CRITERIA IN ACCORDANCE
 WITH ASCE 7-2010 INCLUDING ULTIMATE WINDSPEED, EXPOSURE
 CATEGORY, IMPORTANCE FACTOR, AND DESIGN PRESSURES-
 LATERAL AND UPLIFT. INDICATE HOW THE FAT BOY CLIP WILL
 BE ATTACHED TO THE CONDENSER AND TO THE STAND, AND
 SUBMIT A FL. PRODUCT APPROVAL OR MIAMI-DADE NOA.
  
 2) M-2: PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE NEW
 AHU'S. SHOW THE PIPING RUNS AND DISCHARGE LOCATIONS.
  
 3) M-2: PROVIDE AUTOMATICALLY CONTROLLED SHUTOFF
 DAMPERS FOR THE O/A INTAKE DUCTS- SECTION C403.2.4.3
 FBC-17 ENERGY CONSERVATION.THE DAMPERS SHALL BE EITHER
 MOTORIZED OR GRAVITY TYPE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-06-05 Cont ID  
Sent By gjohnson Date 2018-06-05 Time 15:44 Rev Time 0.00
Received By gjohnson Date 2018-06-04 Time 16:55 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-05-29 Cont ID  
Sent By AW Date 2018-05-29 Time   Rev Time  
Received By awooten Date 2018-05-29 Time   Sent To  
Notes
***NONE***