Plan Review Details - Permit 18050463
Plan Review Stops For Permit 18050463
Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2018-06-08 Cont ID  
Sent By hhall Date 2018-06-08 Time 12:32 Rev Time 0.00
Received By hhall Date 2018-06-08 Time 12:32 Sent To I
Notes
2018-06-08 12:33:41PASSED - NO UTILITY CONFLICTS
 GREASE TRAP OUTSIDE OF BUILDING

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2018-05-30 Cont ID  
Sent By thunt Date 2018-06-01 Time 15:07 Rev Time 0.00
Received By hhall Date 2018-05-30 Time 13:15 Sent To P
Notes
2018-05-30 13:17:03FAILED - SUBMIT GREASE INTERCEPTOR LOCATION PLAN

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-06-29 Cont ID  
Sent By thunt Date 2018-06-29 Time 14:12 Rev Time 0.00
Received By thunt Date 2018-06-19 Time 13:41 Sent To I
Notes
2018-06-20 13:41:56RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-06-08 Cont ID  
Sent By cpuell Date 2018-06-08 Time 14:19 Rev Time 0.00
Received By cpuell Date 2018-06-06 Time 11:30 Sent To  
Notes
2018-06-07 11:30:48RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-01 Cont ID  
Sent By thunt Date 2018-06-01 Time 15:07 Rev Time 0.00
Received By thunt Date 2018-05-10 Time 15:49 Sent To ENG
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-06-29 Cont ID  
Sent By thunt Date 2018-06-29 Time 14:12 Rev Time 0.00
Received By thunt Date 2018-06-29 Time 14:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-06-07 Cont ID  
Sent By thunt Date 2018-06-07 Time 14:56 Rev Time 0.00
Received By thunt Date 2018-06-07 Time 14:56 Sent To ENG
Notes
2018-06-07 15:01:4506/07/2018 2ND INTERCEPTOR REVIEW**DENIED**
  
 1) TRASH CAN WASH MUST BE VENTED. FBC P 901.2.1
  
 2) NO SIZING OF INTERCEPTOR PROVIDED. 1003.3.4
 HYDROMECHANICAL GREASE INTERCEPTORS, FATS, OILS AND
 GREASES DISPOSAL SYSTEMS AND AUTOMATIC GREASE REMOVAL
 DEVICES.
 HYDROMECHANICAL GREASE INTERCEPTORS; FATS, OILS, AND
 GREASES DISPOSAL SYSTEMS AND AUTOMATIC GREASE REMOVAL
 DEVICES SHALL BE SIZED IN ACCORDANCE WITH ASME
 A112.14.3, ASME A112.14.4, ASME A112.14.6, CSA B481.3
 OR PDI G101. HYDROMECHANICAL GREASE INTERCEPTORS; FATS,
 OILS, AND GREASES DISPOSAL SYSTEMS; AND AUTOMATIC
 GREASE REMOVAL DEVICES SHALL BE DESIGNED AND TESTED IN
 ACCORDANCE WITH ASME A112.14.3, ASME A112.14.4, CSA
 B481.1, PDI G101 OR PDI G102. HYDROMECHANICAL GREASE
 INTERCEPTORS; FATS, OILS, AND GREASES DISPOSAL SYSTEMS;
 AND AUTOMATIC GREASE REMOVAL DEVICES SHALL BE INSTALLED
 IN ACCORDANCE WITH THE MANUFACTURER?S INSTRUCTIONS.
 WHERE MANUFACTURER?S INSTRUCTIONS ARE NOT PROVIDED,
 HYDROMECHANICAL GREASE INTERCEPTORS; FATS, OILS, AND
 GREASES DISPOSAL SYSTEMS; AND AUTOMATIC GREASE REMOVAL
 DEVICES SHALL BE INSTALLED IN COMPLIANCE WITH ASME
 A112.14.3, ASME A112.14.4, ASME A112.14.6, CSA B481.3
 OR PDI G101.
  
 EXCEPTION: GREASE INTERCEPTORS THAT ARE SIZED,
 CONSTRUCTED AND APPROVED IN ACCORDANCE WITH RULE 64E-6,
 FLORIDA ADMINISTRATIVE CODE AND THAT ARE LOCATED
 OUTSIDE THE BUILDING SHALL NOT BE REQUIRED TO MEET THE
 REQUIREMENTS OF THIS SECTION.
  
 1003.3.4.1GREASE INTERCEPTOR CAPACITY.
 GREASE INTERCEPTORS SHALL HAVE THE GREASE RETENTION
 CAPACITY INDICATED IN TABLE 1003.3.4.1 FOR THE
 FLOW-THROUGH RATES INDICATED.
  
 3) SPECIFICATION FOR INTERCEPTOR ON PLAN ARE TOO SMALL
 AND CAN NOT BE READ. FBC 107.2.5
  
 4) VALUE IS TOO LOW. PROVIDE A SIGNED BONA FIDE
 CONTRACT SHOW ALL COST INCLUDING THE GREASE INTERCEPTOR
 AS IT WAS NOT INCLUDED WITH THE MAIN PERMIT. FBC 109.3
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-06-01 Cont ID  
Sent By thunt Date 2018-06-01 Time 15:05 Rev Time 0.00
Received By thunt Date 2018-06-01 Time 15:05 Sent To I
Notes
2018-06-01 15:07:2306/01/2018 1ST PLUMBING REVIEW**DENIED**
  
 NO REVIEW OF GREASE INTERCEPTOR WAS DONE UNDER MASTER #
 17060359. PLAN REVIEW ADDED NOTE SEE BELOW ON
 04/30/2018
  
 SEPARATE PERMIT AND PLANS REQUIRED WITH SIZING
 CALCULATIONS FOR NEW GREASE INTERCEPTOR.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  
 PLEASE FREE FELL TO CALL ME TO DISCUSS IF NEEDED.
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  