Plan Review Details - Permit 18050390
Plan Review Stops For Permit 18050390
Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status N Date 2018-09-01 Cont ID  
Sent By shill Date 2018-09-01 Time 18:46 Rev Time 0.00
Received By shill Date 2018-09-01 Time 18:46 Sent To  
Notes
2018-09-01 18:47:06AIPP NOT REQUIRED PER EMAIL FROM SYBILLE WELTER
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2018-10-03 Cont ID  
Sent By dbattles Date 2018-10-03 Time 08:04 Rev Time 0.00
Received By dbattles Date 2018-10-03 Time 08:04 Sent To  
Notes
2018-10-03 08:05:09PROVISO:
 1-ROOFING-PENDING TILE ATTACHMENT AND PRODUCT APPROVAL
 AND ENHANCED NAILING (IF APPLICABLE).
 2-THRASH CHUTE AND ALUMINUM CAP AS SHOWN ON PLANS.
 3-TRUSS SUBMITTAL
 4-CANOPY SUBMITTAL
 5-FLOORING SUBMITTAL
 6-THRESHOLD INSPECTION PLAN
 7-SHORING/RE-SHORING SUBMITTAL
 8-HANDRAIL/GUARDRAIL ENGINEERING

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-09-14 Cont ID  
Sent By dbattles Date 2018-09-14 Time 08:18 Rev Time 0.00
Received By dbattles Date 2018-09-14 Time 08:18 Sent To  
Notes
2018-09-14 08:18:49PROVISO:
 1-ROOFING-PENDING TILE ATTACHMENT AND PRODUCT APPROVAL
 AND ENHANCED NAILING (IF APPLICABLE).
 2-TRASH CHUTE AND ALUMINUM CAP AS SHOWN ON PLANS.
 3-TRUSS SUBMITTAL
 4-CANOPY SUBMITTAL
 5-FLOORING SUBMITTAL
 6-THRESHOLD INSPECTION PLAN
 7-SHORING/RE-SHORING SUBMITTAL
 8-HANDRAIL/GUARDRAIL ENGINEERING

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-09-06 Cont ID  
Sent By dbattles Date 2018-09-06 Time 14:49 Rev Time 0.00
Received By dbattles Date 2018-09-06 Time 13:49 Sent To  
Notes
2018-09-06 14:53:37PROVISO:
 1-ROOFING-PENDING TILE ATTACHMENT AND PRODUCT APPROVAL
 AND ENHANCED NAILING (IF APPLICABLE).
 2-THRASH CHUTE AND ALUMINUM CAP AS SHOWN ON PLANS.
 3-TRUSS SUBMITTAL
 4-CANOPY SUBMITTAL
 5-FLOORING SUBMITTAL
 6-THRESHOLD INSPECTION PLAN
 7-SHORING/RE-SHORING SUBMITTAL
 8-HANDRAIL/GUARDRAIL ENGINEERING

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-08-27 Cont ID  
Sent By dbattles Date 2018-08-27 Time 10:45 Rev Time 0.00
Received By dbattles Date 2018-08-24 Time 13:35 Sent To  
Notes
2018-08-27 10:48:07****CORRECTIONS****
 W.P.B. PERMIT: 18050390
 REVIEWED: AUGUST 27, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1- IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
 -PENDING
  
  
 2-6- OK.
  
  
 7- SHEET A0.09 LIFE SAFETY FLOOR PLAN TYPICAL LEVEL:
 TRASH ROOM AND TRASH CHUTE NEED TO BE FIRE RATED. SEC.
 713 FBC.
  
 7-2 2-HR RATING WAS ADDED TO SHEET A6.04, BUT PLEASE
 ADD 2-HOUR RATING TO SHEET A-0.09 TO MATCH.
  
  
 8-19- OK.
  
  
 20-PROVIDE 2 HOUR FIRE RATED ASSEMBLY DETAILS AND
 SPECIFICATIONS FOR POURED CONCRETE SHEARWALLS AT
 STAIRWAYS AND ELEVATOR SHAFT. SEC. 713.4 FBC. DETAILS
 PROVIDED ON SHEET A8.01 IS FOR CONCRETE BLOCK WALLS
 ONLY.
  
 20-2-PROVIDE FIRE RATED LISTED WALL TYPES TO BE USED IN
 ALL FIRE RATED WALL ASSEMBLIES.
  
  
 23- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
  
 A)FLAT ROOF SINGLE PLY ROOFING NOA 15-0203.23
 SUBMITTED. CLEARLY MARK WHICH APPROVED ASSEMBLY IS
 GOING TO BE INSTALLED. NOTE: IF THE SELECTED ASSEMBLY
 DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES,
 THEN SIGNED AND SEALED RAS 117 CALCULATIONS ARE
 REQUIRED.
 B)CONCRETE ROOF TILE NOA 16-0112.07: DESIGNER OF RECORD
 TO SPECIFY ROOF TILE FASTENING METHOD AS REQUIRED BY
 SEC. 107.2.1.1 CITY AMENDMENTS. IF SPECIFYING TILE
 ADHESIVE, THEN PROVIDE PRODUCT APPROVAL FOR LISTED
 ADHESIVE.
 C) OK.
 D) OK.
 E) CHUTE ALUMINUM CAP AS SHOWN ON PLANS.
  
 A-E-DEFERRED SUBMITTALS
  
  
 24- OK.
  
  
 25- PROVIDE COMPLETE TRUSS PACKAGE SUBMITTAL REVIEWED
 BY THE DESIGNER OF RECORD. SEC. 107.3.4.1 CITY
 AMENDMENTS.
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
  
 -DEFERRED TRUSS SUBMITTAL
  
  
 26-30- OK.
  
 31- OK.
  
 32- OK.
  
  
 33- PROVIDE COMPLETE ENGINEERED DETAILS AND
 SPECIFICATIONS FOR THE CONSTRUCTION OF ALL THE ENTRY
 CANOPIES. SEC. 1601.1 FBC.
  
 -DEFFERED CANOPY SUBMITTAL
  
  
 34- FLOORING UNDERLAYMENT (NOTE: THIS MAY BE SUBMITTED
 LATER AS A DEFERRED SUBMITTAL).
 1- SOUND INSULATION MATERIAL:
 A) PROVIDE 2 COPIES OF THE FLAME SPREAD INDEX AND SMOKE
 DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84
 OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 6TH EDITION
 (2017).
 B) PROVIDE 2 COPIES OF THE SOUND TRANSMISSION CLASS
 (STC) TEST DONE IN ACCORDANCE WITH ASTM E 90 AS
 REQUIRED BY SEC. 1207.2 OF FBC 6TH EDITION (2017).
 C) PROVIDE 2 COPIES OF THE IMPACT INSULATION CLASS
 (IIC) TEST DONE IN ACCORDANCE WITH ASTM E 492 AS
 REQUIRED BY SEC. 1207.3 OF FBC 6TH EDITION (2017).
  
 -DEFFERED FLOORING SUBMITTAL
  
  
 35- OK.
  
 360- VALUATION DECLARED IN THE PERMIT APPLICATION IS
 LOW. SEC. 109.3 CITY AMENDMENTS. UPDATE VALUATION.
 SEC. 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 -PLEASE PROVIDE EVALUATION BASED IN ICC 2018 VALUES
  
  
 37- SEC. 110.7 CITY AMENDMENTS: SHORING. FOR THRESHOLD
 BUILDINGS, SHORING AND ASSOCIATED FORMWORK OR FALSEWORK
 SHALL BE
 DESIGNED AND INSPECTED BY A FLORIDA LICENSED
 PROFESSIONAL ENGINEER, EMPLOYED BY THE PERMIT HOLDER
 OR SUBCONTRACTOR, PRIOR TO ANY REQUIRED MANDATORY
 INSPECTIONS BY THE THRESHOLD BUILDING INSPECTOR. ALL
 SHORING AND RESHORING PROCEDURES, PLANS AND DETAILS
 SHALL BE SUBMITTED TO THE ENFORCEMENT AGENCY
 FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 -DEFERRED SHORING/RE-SHORING SUBMITTAL
 (SEE THRESHOLD REVIEW FOR ADDITIONAL COMMENTS)
  
  
 38-41 OK.
  
  
 SEE LIST BELOW FOR REQUESTED DEFERRED SUBMITTALS:
 1-ROOFING-PENDING TILE ATTACHMENT AND PRODUCT APPROVAL
 AND ENHANCED NAILING (IF APPLICABLE).
 2- THRASH CHUTE AND ALUMINUM CAP AS SHOWN ON PLANS.
 3-TRUSS SUBMITTAL
 4-CANOPY SUBMITTAL
 5-FLOORING SUBMITTAL
 6-THRESHOLD INSPECTION PLAN
 7-SHORING/RE-SHORING SUBMITTAL
 8-HANDRAIL/GUARDRAIL ENGINEERING
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-06-29 Cont ID  
Sent By jgomez Date 2018-06-28 Time 18:07 Rev Time 0.00
Received By jgomez Date 2018-06-18 Time 10:41 Sent To I
Notes
2018-06-18 16:35:29 
  
 ****NOTE: COMMENTS WERE UPDATED BECAUSE THEY WERE
 DUPLICATED. 07/09/18 JG>
  
  
  
 NEW 4 STORY APARTMENT BUILDING (R2). BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017).
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
 1- IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
 2- A)SURVEYS NEED THE SURVEYORS SEAL AND SIGNATURE.
 CHAPTER 472 F.S.
 B) PROVIDE SURVEY WITH PROPOSED BUILDING AND SETBACKS.
 SEC. 107.3.5.1 CITY AMENDMENTS.
  
 C)ACCORDING TO THE NEW FLOOD MAPS THAT WENT INTO EFFECT
 ON OCTOBER 5TH 2017, THIS PROPERTY IS LOCATED IN
 EXPOSURE "X" NOT A8. REVISE AS REQUIRED AND PROVIDE
 CURRENT MAP COMMUNITY PANEL NUMBER ALSO. CITY ORDINANCE
 4729-17. REVISE SURVEYOR'S NOTE #5.
  
 4- SHEET A0.04 ARCHITECTURAL PROJECT SPECIFIC NOTES:
 A)PROJECT DATA/CODE REFERENCE INFORMATION SPECIFIES
 CONSTRUCTION TYPE III-B. REVISE INFORMATION ON EXTERIOR
 BEARING WALLS ON SAME PAGE TO SPECIFY 2 HOUR FIRE
 RATING NOT 1 HOUR. TABLE 601 FBC.
  
 B) INFORMATION BELOW "UNIT MAJOR COMPONENT MATRIX"
 REFERENCES 2014 FLORIDA ACCESSIBILITY CODE SEC.
 233.3.1.2. THE CURRENT CODE IS THE 2017 FBC
 ACCESSIBILITY. REVISE AS REQUIRED. CHAPTER 553 F.S.
 NOTE: ALSO REVISE CALCULATION FOR ROLL-IN SHOWER.
 CALCULATION SHALL BE (87X.15)TO REFLECT THE 15% OF
 TOTAL RESIDENTIAL UNITS NOT (87X.12). SEC. 107.2.1 CITY
 AMENDMENTS.
  
 C) PROJECT DATA/CODE REFERENCE INFORMATION SPECIFIES
 FLOOD ZONE A-8. COORDINATE WITH ITEM #2(C) ABOVE FOR
 CORRECT FLOOD ZONE AND REVISE AS REQUIRED. CITY
 ORDINANCE 4729-17.
  
 5- SHEET A0.07 LIFE SAFETY NOTES AND CODE INFORMATION:
 A) BUILDING CODE ANALYSIS ITEM #4 SPECIFIES
 CONSTRUCTION TYPE III-B. REVISE INFORMATION ON EXTERIOR
 BEARING WALLS ON SAME PAGE TO SPECIFY 2 HOUR FIRE
 RATING NOT 1 HOUR.
 ALSO, PROPOSED BUILDING HEIGHT IS NOT CLEAR. 56'-2"
 DOESN'T MATCH BUILDING ELEVATIONS AND WALL SECTIONS.
 REVISE/CLARIFY.
  
 B) BUILDING CODE ANALYSIS ITEM #5 SPECIFIES FBC TABLE
 1005.1. THERE IS NOT TABLE 1005.1. REVISE AS REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 C) BUILDING CODE ANALYSIS ITEM #6 SPECIFIES FBC TABLE
 1016.1. THERE IS NOT TABLE 1005.1. REVISE AS REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 D) REVISE BUILDING CODE ANALYSIS ITEM # 9 FOR INTERIOR
 WALL AND CEILING REQUIREMENTS. THERE IS NOT TABLE FBC
 803.9 AND 804.4.1. REVISE AS REQUIRED. SEC. 107.2.1
 CITY AMENDMENTS.
  
 E) REVISE INFORMATION ON ITEM #12 OF BUILDING CODE
 ANALYSIS. THIS PROJECT IS LOCATED IN THE CITY WEST PALM
 BEACH NOT CITY OF MIAMI. SEC. 107.2.1 CITY AMENDMENTS.
  
 6- SHEET A0.08 LIFE SAFETY FLOOR PLAN GROUND LEVEL:
 A) REVISE NUMBER OF OCCUPANTS FOR THE WELLNESS CENTER.
 FOR THE PURPOSE OF OCCUPANT LOAD USE THE EXERCISE ROOMS
 OCCUPANT LOAD FACTOR OF 50SF (GROSS) NOT BUSINESS 100SF
 (GROSS). REVISE AS REQUIRED. SEE TABLE 1004.1.2 FBC AND
 REVISE AS REQUIRED.
  
 B) REVISE NUMBER OF OCCUPANTS FOR THE MULTIPURPOSE
 ROOM. THIS IS NOT BUSINESS OCCUPANCY. FOR THE PURPOSE
 OF OCCUPANT LOAD USE THE ASSEMBLY OPTION THAT BEST
 REFLECTS THE USE OF THIS ROOM. SEE TABLE 1004.1.2 FBC
 AND REVISE AS REQUIRED.
  
 7- SHEET A0.09 LIFE SAFETY FLOOR PLAN TYPICAL LEVEL:
 TRASH ROOM AND TRASH CHUTE NEED TO BE FIRE RATED. SEC.
 713 FBC.
  
 8- SHEET A0.11 ZONING DATA:
 A) BUILDING HEIGHT IS NOT CLEAR. BUILDING HEIGHT SHOWN
 ON THE PROJECT INFO. DOESN'T MATCH HEIGHT SHOWN ON
 EXTERIOR ELEVATIONS AND SECTIONS AND ON PROJECT DATA
 INFORMATION SHOWN ON OTHER SHEETS. REVISE AS REQUIRED
 TO MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 B) NOTE: PARKING REQUIREMENTS WILL BE REVIEWED AFTER
 ZONING FINAL APPROVAL ON REQUIRED NUMBER OF PARKING
 SPACES. ACCORDING TO FOOTNOTE * AT THE BOTTOM OF
 PROJECT INFO. IT LOOKS LIKE THERE MAY BE A CITY WAIVER
 (40% REDUCTION) ON REQUIRED PARKING SPACE FOR SENIOR
 HOUSING.
  
 C) BUILDING AREA CALCULATION IS NOT CLEAR. WHY SAME
 AREA FOR LEVEL 1 AND LEVELS 2 TO 4. ALSO, COORDINATE
 WITH BUILDING AREA ON OTHER3 SHEETS AND REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS
  
 9- SHEET A1-03 FLOOR PLAN ROOF: SPECIFY LOCATION AND
 SIZE OF ROOF VENTS SPECIFIED ON THE ROOF PLAN GENERAL
 NOTES TO SHOW COMPLIANCE WITH ROOF CROSS VENTILATION
 SEC. 1203.2 FBC.
  
 10-SHEET A3.01 ENLARGED PLANS UNIT TYPE:
 A) KEYED ITEMS ON REFLECTED CEILING PLAN DON'T MATCH
 UNIT KEYNOTES. WHAT'S AW, AV?
 SEC. 107.2.1 CITY AMENDMENTS.
  
 B) KEYED ITEMS ON FINISH PLAN DON'T MATCH UNIT
 KEYNOTES. WHAT'S PT-1, PT-2?
 SEC. 107.2.1 CITY AMENDMENTS.
  
 11- SHEET A3.02 ENLARGED PLANS UNIT TYPE:
 KEYED ITEMS ON FINISH PLAN DON'T MATCH UNIT KEYNOTES.
 WHAT'S PT-1, PT-2?
 SEC. 107.2.1 CITY AMENDMENTS.
  
 12- SHEET A4.01 EXTERIOR ELEVATIONS (NORTH AND EAST):
 A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 ATTACHMENT OF ALL ORNAMENTAL PRECAST CONCRETE BRACKETS.
 SEC. 1601.1 FBC.
  
 B)PROVIDE PROVIDE COMPLETE DETAILS AND SPECIFICATIONS
 FOR THE FOAM BAND SHOWING COMPLIANCE WITH SEC. 2603.5
 FBC.
  
 C) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION AND INSTALLATION OF THE DECORATIVE
 ELEMENTS #09.
 SPECIFY ALL MATERIALS AND FASTENERS. SEC. 106.1.1 FBC.
  
 13- SHEET A4.12 ENLARGED PLANS AND INT. ELEVATIONS
 BATHROOM: PROVIDE DETAILS AND SPECIFICATIONS FOR
 REINFORCING AROUND TOILETS, TUBS AND SHOWERS OF ALL
 BATHROOMS AS REQUIRED BY REQUIREMENT #6 OF FAIR HOUSING
 ACT.
  
 14-SHEET A4.13 ENLARGED PLANS AND INT. ELEV. KITCHEN
 TYP. UNITS: CLARIFY WHY THE DIMENSION BETWEEN BOTTOM
 KITCHEN CABINETS AND TOP KITCHEN CABINETS ARE DIFFERENT
 ON CABINETS MILLWORK DETAIL #07 AND KITCHEN ELEVATIONS
 #08 AND #09?. SEC. 107.2.1 CITY AMENDMENTS. ALSO,
 DIMENSION OF TOP CABINETS IS DIFFERENT. CLARIFY.
 NOTE: SAME COMMENT APPLIES TO SHEET A4-14.
  
 15- SHEET A5-02 WALL SECTIONS:
 A) TYPE III BUILDINGS DON'T ALLOW NON-COMBUSTIBLE
 MATERIALS ON EXTERIOR WALL. REVISE WALL SECTION KEYNOTE
 #16. FIRE RETARDANT WOOD MAY BE USED. SEC. 602.3 FBC.
 SAME APPLIES TO SHEET A5-03.
  
 B) REVISE WALL SECTION KEYNOTE #21 AND #22. DESIGNER OF
 RECORD TO PROVIDE DETAILS AND SPECIFICATIONS FOR SOFFIT
 METAL STUD FRAMING AND FOR DRYWALL SHEATHING. THIS IS
 NOT DONE BY THE METAL STUD MANUFACTURER. SEC. 1601.1
 FBC. SAME APPLIES TO SHEET A5-03.
  
 C) PROVIDE DETAIL AND SPECIFICATIONS FOR ROOF
 INSULATION ON PITCHED ROOF. SEC. C103.2 FBC-ENERGY
 CONSERVATION. SAME APPLIES TO SHEET A5-03.
  
 D) CLARIFY WALL SECTION KEYNOTE #13 AND #19. FIRE
 RETARDED WOOD? SEC. 107.2.1 CITY AMENDMENTS. SAME
 APPLIES TO SHEET A5-03.
  
 16- SHEET A6.01- ENLARGED PLANS AND SECTION STAIR NO
 01: BOTTOM EXTENSION AT STAIRS OF FLOOR PLAN GROUND
 LEVEL NEED TO BE COMPLY WITH SEC. 505.10.3
 FBC-ACCESSIBILITY. EXTENSION ON BOTH SIDES OF STAIRS
 NEED TO COMPLY. THEY NEED TO EXTEND AT THE SLOPE OF THE
 STAIR. ONE OF THEM IS TURNING. THIS IS ONLY ALLOWED
 WHEN CONNECTING TO ANOTHER HANDRAIL. SAME APPLIES TO
 SHEET A6-02.
  
 17- SHEET A6.03 - ENLARGED PLANS AND SECTION ELEVATOR:
 A) REVISE ELEVATOR GENERAL NOTE #1. REVISE THE STANDARD
 REFERENCED. SEE CHAPTER 35 FB FOR CORRECT ASME SECTION
 AND CURRENT EDITION AND REVISE AS REQUIRED.
  
 B) UPDATE ALL ELEVATOR GENERAL NOTES. PROVIDE CORRECT
 CODE SECTIONS REFERENCING THE CURRENT 2017
 FBC-ACCESSIBILITY.
  
 C) PROVIDE SIZE OF ELEVATOR CARS SHOWING COMPLIANCE
 WITH SEC. 3002.4 FBC FOR AMBULANCE STRETCHER.
  
 18- WINDOW TAG "B" ON WINDOW SCHEDULE ON SHEET A8.11
 EXTERIOR OPENING SCHEDULES STATES THAT THIS WINDOW IS
 "NOT USED".
 BUT ARCHITECTURAL FLOOR PLANS SHOW WINDOW "B" ON UNIT
 TYPE "A" LOCATED ON NORTH EAST CORNER. REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 19- DOOR TYPES SHOWN ON THE DOOR TYPE ELEVATIONS DON'T
 MATCH DOOR TYPE SHOWN ON THE DOOR SCHEDULES AND FLOOR
 PLANS. REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 20- PROVIDE 2 HOUR FIRE RATED ASSEMBLY DETAILS AND
 SPECIFICATIONS FOR POURED CONCRETE SHEARWALLS AT
 STAIRWAYS AND ELEVATOR SHAFT. SEC. 713.4 FBC. DETAILS
 PROVIDED ON SHEET A8.01 IS FOR CONCRETE BLOCK WALLS
 ONLY.
  
 21- SHEET A9.02-STAIR AND RAILING DETAILS: CLARIFY
 DETAIL 09 TYPICAL HANDRAIL DETAIL AT LOWER LANDING. IT
 DOESN'T SEEM TO COMPLY WITH SEC. 505.10.3
 FBC-ACCESSIBILITY. THE HANDRAIL NEEDS TO RETURN TO THE
 WALL, GUARD, OR LANDING SURFACE.
  
  
 22- PROVIDE COMPLETE DETAIL AND SPECS SHOWING HOW THE
 WOOD TRUSS CONNECTOR #1 SIMPSON META16 IS INSTALLED. IT
 MAY NOT SEEM TO WORK BASED ON THE PROPOSED
 INSTALLATION. SEC. 107.2.1 CITY AMENDMENTS.
  
 23- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
  
 A)FLAT ROOF SINGLE PLY ROOFING NOA 15-0203.23
 SUBMITTED. CLEARLY MARK WHICH APPROVED ASSEMBLY IS
 GOING TO BE INSTALLED. NOTE: IF THE SELECTED ASSEMBLY
 DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES,
 THEN SIGNED AND SEALED RAS 117 CALCULATIONS ARE
 REQUIRED.
  
 B)CONCRETE ROOF TILE NOA 16-0112.07: DESIGNER OF RECORD
 TO SPECIFY ROOF TILE FASTENING METHOD AS REQUIRED BY
 SEC. 107.2.1.1 CITY AMENDMENTS. IF SPECIFYING TILE
 ADHESIVE, THEN PROVIDE PRODUCT APPROVAL FOR LISTED
 ADHESIVE.
  
 C) ALUMINUM STOREFRONT SYSTEM NOA 17-1114.02 SUBMITTED.
 CLEARLY SPECIFY MULLION AND WINDOW SIZES. SEC. 1601.1
 FBC.
  
 D) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 E) CHUTE ALUMINUM CAP AS SHOWN ON PLANS.
  
 24-- DESIGNER OF RECORD TO REVIEW AND APPROVE IN
 WRITING (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS
 AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 25- PROVIDE COMPLETE TRUSS PACKAGE SUBMITTAL REVIEWED
 BY THE DESIGNER OF RECORD. SEC. 107.3.4.1 CITY
 AMENDMENTS.
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
  
 26- ALL ENGINEER DOCUMENTS THAT ARE SUBMITTED FOR
 PUBLIC RECORDS NEED TO HAVE ORIGINAL SEAL AND SIGNATURE
 AS REQUIRED BY CHAPTER 471 F.S. WHEN SUBMITTING
 DOCUMENTS FOR PUBLIC RECORDS. PROVIDE HARD COPIES WITH
 ORIGINAL SEAL AND SIGNATURE FOR ALL DOCUMENTS THAT WERE
 NOT SUBMITTED WITH DIGITAL SIGNATURE.
  
 27- PROVIDE COMPLETE ENGINEERED DETAILS AND
 SPECIFICATIONS FOR THE CONSTRUCTION OF ALL THE ENTRY
 CANOPIES. SEC. 1601.1 FBC.
  
 28- TRASH ROOM DOOR TYPE ELEVATION TYPE I SHOWN ON
 SHEET A8.21 FOR DOOR #1220 DOESN'T MATCH SIZE SHOWN ON
 THE DOOR SCHEDULE. ALSO. NOA 10-1014.05 LISTED N THE
 DOOR ELEVATION IS EXPIRED. REVISE AS REQUIRED TO MATCH.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 29- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
  
 A)FLAT ROOF SINGLE PLY ROOFING NOA 15-0203.23
 SUBMITTED. CLEARLY MARK WHICH APPROVED ASSEMBLY IS
 GOING TO BE INSTALLED. NOTE: IF THE SELECTED ASSEMBLY
 DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES,
 THEN SIGNED AND SEALED RAS 117 CALCULATIONS ARE
 REQUIRED.
  
 B)CONCRETE ROOF TILE NOA 16-0112.07: DESIGNER OF RECORD
 TO SPECIFY ROOF TILE FASTENING METHOD AS REQUIRED BY
 SEC. 107.2.1.1 CITY AMENDMENTS. IF SPECIFYING TILE
 ADHESIVE, THEN PROVIDE PRODUCT APPROVAL FOR LISTED
 ADHESIVE.
  
 C) ALUMINUM STOREFRONT SYSTEM NOA 17-1114.02 SUBMITTED.
 CLEARLY SPECIFY MULLION AND WINDOW SIZES. SEC. 1601.1
 FBC.
  
 D) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 E) ROOF VENTS FOR CONCRETE ROOF TILE INSTALLATION AND
 CLEARLY SPECIFY LOCATION ON ROOF.
  
 F)ROOF ATTIC ACCESS DOORS SHOWN ON ROOF PLAN.
  
 G) FIXED WINDOWS AS SHOWN ON PLANS.
  
 H) CORRELATE EACH DOOR NOA SUBMITTED WITH THE PROPOSED
 LOCATION/ROOM.
  
 30- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 31- PROVIDE COMPLETE TRUSS PACKAGE SUBMITTAL REVIEWED
 BY THE DESIGNER OF RECORD. SEC. 107.3.4.1 CITY
 AMENDMENTS.
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
  
 32- ALL ENGINEER DOCUMENTS THAT ARE SUBMITTED FOR
 PUBLIC RECORDS NEED TO HAVE ORIGINAL SEAL AND SIGNATURE
 AS REQUIRED BY CHAPTER 471 F.S. WHEN SUBMITTING
 DOCUMENTS FOR PUBLIC RECORDS. PROVIDE HARD COPIES WITH
 ORIGINAL SEAL AND SIGNATURE FOR ALL DOCUMENTS THAT WERE
 NOT SUBMITTED WITH DIGITAL SIGNATURE.
  
 33- PROVIDE COMPLETE ENGINEERED DETAILS AND
 SPECIFICATIONS FOR THE CONSTRUCTION OF ALL THE ENTRY
 CANOPIES. SEC. 1601.1 FBC.
  
 34- FLOORING UNDERLAYMENT (NOTE: THIS MAY BE SUBMITTED
 LATER AS A DEFERRED SUBMITTAL).
 1- SOUND INSULATION MATERIAL:
 A) PROVIDE 2 COPIES OF THE FLAME SPREAD INDEX AND SMOKE
 DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84
 OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 6TH EDITION
 (2017).
 B) PROVIDE 2 COPIES OF THE SOUND TRANSMISSION CLASS
 (STC) TEST DONE IN ACCORDANCE WITH ASTM E 90 AS
 REQUIRED BY SEC. 1207.2 OF FBC 6TH EDITION (2017).
 C) PROVIDE 2 COPIES OF THE IMPACT INSULATION CLASS
 (IIC) TEST DONE IN ACCORDANCE WITH ASTM E 492 AS
 REQUIRED BY SEC. 1207.3 OF FBC 6TH EDITION (2017).
  
 35- PROVIDE SITE PLAN SHOWING COMPLIANCE WITH THE
 ACCESSIBLE ROUTE FROM THE PUBLIC STREET AS REQUIRED BY
 SEC. 206.2.1 FBC ACCESSIBILITY.
  
 360- VALUATION DECLARED IN THE PERMIT APPLICATION IS
 LOW. SEC. 109.3 CITY AMENDMENTS. UPDATE VALUATION.
 SEC. 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 37- SEC. 110.7 CITY AMENDMENTS: SHORING. FOR THRESHOLD
 BUILDINGS, SHORING AND ASSOCIATED FORMWORK OR FALSEWORK
 SHALL BE
 DESIGNED AND INSPECTED BY A FLORIDA LICENSED
 PROFESSIONAL ENGINEER, EMPLOYED BY THE PERMIT HOLDER
 OR SUBCONTRACTOR, PRIOR TO ANY REQUIRED MANDATORY
 INSPECTIONS BY THE THRESHOLD BUILDING INSPECTOR. ALL
 SHORING AND RESHORING PROCEDURES, PLANS AND DETAILS
 SHALL BE SUBMITTED TO THE ENFORCEMENT AGENCY
 FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 38- SEC. 110.8 CITY AMENDMENTS: THRESHOLD BUILDING.
  
 CITY AMENDMENTS SEC. 110.8.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM STRUCTURAL
 INSPECTIONS ON A THRESHOLD BUILDING PURSUANT TO A
 STRUCTURAL INSPECTION PLAN PREPARED BY THE
 ENGINEER OR ARCHITECT OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A
 THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL
 INSPECTION PLANS IS TO PROVIDE SPECIFIC
 INSPECTION PROCEDURES AND SCHEDULES SO THAT THE
 BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS. THE SPECIAL
 INSPECTOR MAY NOT SERVE AS A
 SURROGATE IN CARRYING OUT THE RESPONSIBILITIES OF THE
 BUILDING OFFICIAL, THE ARCHITECT OR THE
 ENGINEER OF RECORD. THE CONTRACTOR'S CONTRACTUAL OR
 STATUTORY OBLIGATIONS ARE NOT RELIEVED BY
 ANY ACTION OF THE SPECIAL INSPECTOR.
  
 NOTE: SPECIAL INSPECTOR IS REQUIRED. CONTACT JULIO
 GOMEZ (561)805-6712 FOR MORE INFORMATION REGARDING
 SPECIAL INSPECTOR REQUIREMENTS AND APPROVAL. SEC. 110.8
 CITY AMENDMENTS
  
 CITY AMENDMENT SEC. 110.8.4.4 ALL PLANS FOR THE
 BUILDING WHICH ARE REQUIRED TO BE SIGNED AND SEALED
 BY THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A
 STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE
 APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE
 FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND CHAPTER 633.
 FLORIDA STATUTES.
  
 39-ART IN PUBLIC PLACES
 THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES
 ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR
 NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT
 APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL
 PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE.
 PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND
 CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V,
 ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 SEC. 78-129. - PUBLIC ART ASSESSMENT FOR PRIVATE
 DEVELOPMENT.
 (A) APPLICABILITY. THE PROVISIONS OF THIS ARTICLE AND
 THE PUBLIC ART ASSESSMENT SECTION SHALL APPLY TO ALL
 PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW
 CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN
 EXISTING BUILDING, WHERE TOTAL CONSTRUCTION COSTS ARE
 EQUAL TO OR GREATER THAN $750,000.00. ALL BUILDINGS
 WITHIN NEW PLANNED DEVELOPMENTS SHALL BE ASSESSED
 CUMULATIVELY TOWARDS THIS ART IN PUBLIC PLACES
 REQUIREMENT, EVEN IF THE BUILDINGS ARE PERMITTED
 SEPARATELY OR DEVELOPED IN PHASES. THE PROVISIONS OF
 THIS SECTION APPLY TO NEW DEVELOPMENT OR NEW
 CONSTRUCTION WITHIN EXISTING PLANNED DEVELOPMENTS.
  
 FOR CONTACT INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR
 822-1515 E-MAIL: [email protected]
  
 40- PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 41- NOTE: CLARIFY IF THIS BUILDING IS GOING TO BE USED
 AS AN ASSISTED LIVING FACILITY. SEE ELECTRICAL
 COMMENTS. PLAN REVIEW WAS DONE BASED ON AN RESIDENTIAL
 R2 OCCUPANCY. ASSISTED LIVING FACILITIES ARE REVIEWED
 UNDER THE INSTITUTIONAL OCCUPANCY AND CODE REQUIREMENTS
 DIFFER. CLEARLY STATE ON PLANS PROPOSED USE. SEC. 301.1
 FBC.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-09-06 Cont ID  
Sent By jpearson Date 2018-09-06 Time 10:52 Rev Time 0.00
Received By jpearson Date 2018-09-06 Time 10:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-08-09 Cont ID  
Sent By jpearson Date 2018-08-09 Time 10:05 Rev Time 0.00
Received By jpearson Date 2018-08-09 Time 10:05 Sent To  
Notes
2018-08-09 10:05:53CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED.
 7. LABELING OF MAINS IS CONFUSING. PLAN SHOWS MAIN 3 OF
 3 FOR HOUSE LOADS AND THEN SHOWS MAIN 1 OF 2 FOR
 EMERGENCY LOADS ON THE SAME SHEET. IT APPEARS THAT YOU
 WILL HAVE 4 MAINS IN THE MAIN ELECTRICAL ROOM AND ONE
 MAIN FOR THE FIRE PUMP. PROVIDE LABELING THAT CLEARLY
 EXPLAINS THE LOCATION AND NAME OF EACH OF THE MAINS.
 NEC 230.2(E) (SHEET E-3.02 SHOWS A LOAD CALCULATION OF
 1040.6 AMPS FOR MAIN 2, BUT KEY NOTE 3 SHOWS MAIN 2 AS
 800 AMP. THIS CONFLICTS WITH THE PANEL SCHEDULE FOR
 MS-1 WHICH SHOWS MAIN 2 AS 1200 AMP. CORRECT
 DISCREPANCY.)
 8. CORRECTED.
 9. CORRECTED.
 10. CORRECTED.
 11. CORRECTED.
 12. CORRECTED.
 13. CORRECTED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-06-06 Cont ID  
Sent By jpearson Date 2018-06-06 Time 12:40 Rev Time 0.00
Received By jpearson Date 2018-06-06 Time 12:40 Sent To  
Notes
2018-06-06 12:40:54CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. IT APPEARS FROM THE DESIGN THAT THIS IS AN ASSISTED
 LIVING FACILITY. WILL THIS FACILITY BE LICENSED AS
 ASSISTED LIVING? PROVIDE CLARIFICATION. WPB FBC 107.2.1
 2. IF THIS IS AN ASSISTED LIVING FACILITY, PROVIDE
 DETAILS OF COMPLIANCE WITH THE EMERGENCY ENVIRONMENTAL
 CONTROL REQUIRED PER FLORIDA ADMINISTRATIVE CODE, RULE
 58A-5.036
 3. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC
 105.1, 107.2.1
 4. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C
 EQUIPMENT PER CODE IN THE AC ROOMS. ADDITIONALLY, SOME
 OF THE RECEPTACLES SHOWS ON THE ROOF ARE NOT WITHIN 25
 FEET OF THE FURTHEST UNIT. PROVIDE CORRECTIONS. NEC
 210.63
 5. GROUND WIRE LABELED AS G-5 ON SHEET E-3.01 IS NOT
 SIZED PROPERLY. THIS CONDUCTOR MUST BE SIZED FOR THE
 2/0 FEEDERS PER TABLE 250.66. PROVIDE CORRECTION. NEC
 250.66
 6. GROUNDING ELECTRODE CONDUCTORS FOR EACH MAIN SHOULD
 BE TIED TO A COMMON GROUNDING ELECTRODE AND ALL
 CONNECTED TOGETHER IN ACCORDANCE WITH CODE. PROVIDE
 CORRECTION. THE FIRE PUMP AND GENERATOR GROUNDING
 ELECTRODE CONDUCTORS ARE SHOWN SEPARATE. ADDITIONALLY,
 THE GENERATOR APPEARS TO NOT BE A SEPARATELY DERIVED
 SYSTEM AS IT IS SHOWN WITH A 3 POLE TRANSFER SWITCH.
 THEREFORE, IT WOULD NOT BE CODE COMPLIANT TO INSTALL A
 GROUNDING ELECTRODE SYSTEM IN THIS LOCATION. PROVIDE
 CLARIFICATION AND/OR CORRECTIONS. NEC 250.64(D), 250.30
 7. LABELING OF MAINS IS CONFUSING. PLAN SHOWS MAIN 3 OF
 3 FOR HOUSE LOADS AND THEN SHOWS MAIN 1 OF 2 FOR
 EMERGENCY LOADS ON THE SAME SHEET. IT APPEARS THAT YOU
 WILL HAVE 4 MAINS IN THE MAIN ELECTRICAL ROOM AND ONE
 MAIN FOR THE FIRE PUMP. PROVIDE LABELING THAT CLEARLY
 EXPLAINS THE LOCATION AND NAME OF EACH OF THE MAINS.
 NEC 230.2(E)
 8. HDP SHOWS A 400 AMP BREAKER AND FEEDER TO PANEL L,
 BUT THE PANEL SCHEDULE FOR PANEL L STATES THAT THE
 PANEL IS RATED FOR 225 AMPS. PROVIDE CORRECTION. NEC
 215.2, 408.30, 408.36
 9. PROVIDE DETAILS OF COMPLIANCE WITH NEC 240.87 FOR
 1200 AMP BREAKER IN MS1. NEC 240.87
 10. SHEET E-3.02 DOES NOT SHOW THE LOAD CALCULATION FOR
 MAIN 1 OF 3. PROVIDE CORRECTION. NEC 220
 11. PROVIDE GFCI PROTECTION FOR DISHWASHER IN EACH
 UNIT. NEC 210.8(D)
 12. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 EACH PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 13. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2018-09-06 Cont ID  
Sent By RRossano Date 2018-09-06 Time   Rev Time 1.00
Received By rrossano Date 2018-09-05 Time   Sent To I
Notes
2018-09-06 11:55:41PERMIT UNDER REVIEW AT ENGINEERING.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2018-08-24 Cont ID  
Sent By RRossano Date 2018-08-24 Time   Rev Time 1.00
Received By rrossano Date 2018-08-23 Time   Sent To B
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2018-06-09 Cont ID  
Sent By shill Date 2018-06-09 Time 19:34 Rev Time 0.00
Received By shill Date 2018-06-09 Time 19:34 Sent To  
Notes
2018-06-09 19:34:46CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-08-01 Cont ID  
Sent By scaldero Date 2018-08-01 Time 14:04 Rev Time 0.00
Received By scaldero Date 2018-08-01 Time 13:52 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-05-22 Cont ID  
Sent By scaldero Date 2018-05-22 Time 13:43 Rev Time 0.00
Received By scaldero Date 2018-05-21 Time 13:41 Sent To  
Notes
2018-05-22 13:43:31PERMIT # 18050390
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) PER NFPA 241 SECTION 8.7.2.3, WHERE UNDERGROUND
 WATER MAINS AND HYDRANTS ARE TO BE PROVIDED, THEY SHALL
 BE INSTALLED, COMPLETED, AND IN SERVICE PRIOR TO
 CONSTRUCTION WORK.
 SEPARATE PLANS AND PERMITS NEEDED FOR PRIVATE
 UNDERGROUND FIRE LINE AND FIRE HYDRANTS.
  
 2) SHEET E1.01A: THERE IS A NOTE THAT STATES: "BUILDING
 IS FULLY SUPPLIED WITH SPRINKLER SYSTEM; THEREFORE,
 SMOKE AND HEAT DETECTORS ARE NOT REQUIRED THROUGHOUT
 THE BUILDING......"
 PER NFPA 101 - 30.3.4.45: SMOKE ALARMS SHALL BE
 INSTALLED IN ACCORDANCE WITH 9.6.2.10 IN EVERY SLEEPING
 AREA, OUTSIDE EVERY SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS, AND ON ALL LEVELS OF THE
 DEWLLING UNIT, INCLUDING BASEMENTS.
  
 3) IF, AND WHERE, APPLICABLE: STRUCTURES WITH LIGHT
 FRAME FLOOR/ROOF TRUSS CONSTRUCTION SHALL BE IDENTIFIED
 WITH A SIGN AFFIXED TO THE BUILDING.
 THE SIGN SHALL FEATURE A MALTESE CROSS 8-INCHES WIDE
 AND 8-INCHES TALL AND BE OF A BRIGHT RED REFLECTIVE
 COLOR AND BEAR THE APPROPRIATE LETTER R/F/RF
 DESIGNATION PER FLORIDA STATUTE 633.027 AND FLORIDA
 ADMINISTRATIVE CODE 69A-60.0081.
  
 4) SHEET FP-2.01: UNIT TYPE "B" APPEARS TO HAVE
 INSUFFICIENT FIRE SPRINKLER COVERAGE OF THE LIVING
 AREA.
  
 5) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2018-10-03 Cont ID  
Sent By lmarchan Date 2018-10-03 Time 10:10 Rev Time 0.00
Received By lmarchan Date 2018-10-02 Time 10:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-09-18 Cont ID  
Sent By cpuell Date 2018-09-18 Time 17:21 Rev Time 0.00
Received By cpuell Date 2018-09-12 Time 12:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-09-07 Cont ID  
Sent By cpuell Date 2018-09-07 Time 13:22 Rev Time 0.00
Received By cpuell Date 2018-09-05 Time 16:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-27 Cont ID  
Sent By dbattles Date 2018-08-27 Time 11:01 Rev Time 0.00
Received By dbattles Date 2018-07-31 Time 13:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-29 Cont ID  
Sent By jgomez Date 2018-06-29 Time 16:18 Rev Time 0.00
Received By jgomez Date 2018-05-14 Time 08:49 Sent To I
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2018-09-26 Cont ID  
Sent By lmarchan Date 2018-09-26 Time 09:28 Rev Time 0.00
Received By lmarchan Date 2018-09-21 Time 10:43 Sent To  
Notes
2018-10-01 12:38:06MU-2018-033090-0000 ATTACHED IN SUPPORTING DOCUMENTS.
2018-09-21 10:43:119/21/18 EMAILED COUNTY FOR IMPACT REVIEW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2018-09-06 Cont ID  
Sent By dbattles Date 2018-09-06 Time 14:56 Rev Time 0.00
Received By dbattles Date 2018-09-06 Time 14:56 Sent To  
Notes
2018-09-06 14:58:23PENDING :
 IMPACT FEE QUESTIONNAIRE. THE FORM CAN BE FOUND AT:
 HTTP://DISCOVE
 R.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QU
 ESTIONNAIRE.PDF
 -UPLOAD TO PROJECT DOX
  
 [FBC AMENDED 109]PLANS WILL BE REVIEWED BY THE PBC
 IMPACT FEE OFFICE DIGITALLY VIA PROJECTDOX UPON
 NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR
 WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE
 WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY
 UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE. THE FORM CAN BE FOUND AT: HTTP://DISCOVE
 R.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QU
 ESTIONNAIRE.PDF UPON APPROVAL AND FEE PAYMENT, PLEASE
 UPLOAD THE RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected]

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-08-24 Cont ID  
Sent By dbattles Date 2018-08-24 Time 13:39 Rev Time 0.00
Received By dbattles Date 2018-08-24 Time 13:39 Sent To  
Notes
2018-08-24 13:39:41[FBC AMENDED 109]PLANS WILL BE REVIEWED BY THE PBC
 IMPACT FEE OFFICE DIGITALLY VIA PROJECTDOX UPON
 NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR
 WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE
 WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY
 UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE. THE FORM CAN BE FOUND AT: HTTP://DISCOVE
 R.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QU
 ESTIONNAIRE.PDF UPON APPROVAL AND FEE PAYMENT, PLEASE
 UPLOAD THE RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected]

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-06-29 Cont ID  
Sent By jgomez Date 2018-06-29 Time 08:15 Rev Time 0.00
Received By jgomez Date 2018-06-29 Time 08:14 Sent To  
Notes
2018-06-29 08:15:43IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2018-09-13 Cont ID  
Sent By ccole Date 2018-09-13 Time 14:58 Rev Time 0.00
Received By ccole Date 2018-09-13 Time 14:50 Sent To  
Notes
2018-09-13 14:59:20MECHANICAL PROVISO
 DEFERRED SUBMITTALS:
  
 GENERATOR
 CLOTHES DRYERS
 FIRE/SMOKE DAMPERS
 FIRE DAMPERS
 SMOKE DETECTORS
 O/A MOTORIZED DAMPERS
 AC STANDS
 LOUVERS
 KITCHEN EXHAUST HOODS
 FIRE-RATED FUSIBLE LINK LOUVERED AC CLOSET DOORS.
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2018-09-06 Cont ID  
Sent By ccole Date 2018-09-06 Time 17:45 Rev Time 0.00
Received By ccole Date 2018-09-06 Time 10:40 Sent To  
Notes
2018-09-06 17:49:433RD REVIEW FBC-2017 MECHANICAL
 PERMIT #18050390
 9/6/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 LISTED BELOW ARE THE REMAINING COMMENTS FROM THE SECOND
 REVIEW THAT WERE NOT ADDRESSED- PLEASE COMPLY. COMMENT
 #9 IS AN ADVISORY COMMENT PERTAINING TO THE DEFERRED
 SUBMITTALS
  
 1) PROVIDE A PRODUCT DATA SHEET FROM THE MANUFACTURER
 FOR THE 90 MINUTE FIRE-RATED AC CLOSET DOORS 215C,
 315C, AND 415C THAT WILL BE EQUIPPED WITH THE 30"X30'
 RETURN GRILLS AND FIRE DAMPERS. PLEASE CLARIFY WHY THE
 DOORS 101A, 201C, 301C, AND 401C WHICH ARE ALSO AC
 CLOSET DOORS IN THE NW CORRIDOR DO NOT HAVE THE RETURN
 GRILLS AND FIRE DAMPERS, AND WHY THESE DOORS ARE ONLY
 45 MINUTE DOORS.
  
 8) PROVIDE A COMPLETE SUBMITTAL PACKAGE IS REQUIRED FOR
 THE GENERATOR INCLUDING THE UL2200 CERTIFICATE OF
 COMPLIANCE, AND ALL MECHANICAL ACCESSORIES INCLUDING
 THE FUEL PIPINGS, VENT AND EXHAUST PIPINGS, WALL
 THIMBLE, TERMINATION CAPS, AND WALL BRACKETS AND
 SUPPORTS. PLEASE NOTE THAT WIND LOAD ENGINEERING WILL
 BE REQUIRED FOR INSTALLATION OF THE EXTERIOR EXHAUST
 VENT ASSEMBLY THAT IS SHOWN ALONG THE EAST WALL BY THE
 GENERATOR ROOM
  
 9) PLEASE REVIEW THE FOLLOWING LIST OF REQUIRED
 SUBMITTALS TO BE APPROVED BY THE DESIGN PROFESSIONAL OF
 RECORD AND SUBMITTED WITH APPROVAL STAMPS.
  
 GENERATOR
 CLOTHES DRYERS (SUBMITTED).
 FIRE/SMOKE DAMPERS
 FIRE DAMPERS
 SMOKE DETECTORS
 O/A MOTORIZED DAMPERS
 AC STANDS
 LOUVERS
 KITCHEN EXHAUST HOODS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-08-22 Cont ID  
Sent By ccole Date 2018-08-22 Time 10:28 Rev Time 0.00
Received By ccole Date 2018-08-21 Time 08:42 Sent To  
Notes
2018-08-22 11:17:262ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18050390
 8/22/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A PRODUCT DATA SHEET FROM THE MANUFACTURER
 FOR THE 90 MINUTE FIRE-RATED AC CLOSET DOORS 215C,
 315C, AND 415C THAT WILL BE EQUIPPED WITH THE 30"X30'
 RETURN GRILLS AND FIRE DAMPERS. PLEASE CLARIFY WHY THE
 DOORS 101A, 201C, 301C, AND 401C WHICH ARE ALSO AC
 CLOSET DOORS IN THE NW CORRIDOR DO NOT HAVE THE RETURN
 GRILLS AND FIRE DAMPERS, AND WHY THESE DOORS ARE ONLY
 45 MINUTE DOORS.
  
 2) M1.03B: PLEASE REVISE NOTE #7 TO INDICATE CLASS 1
 MOTORIZED DAMPERS.
  
 3) M2.02: THERE IS A MISSING FIRE DAMPER WHERE THE
 10X10 EXHAUST DUCT PENETRATES THE FIRE-RATED TRASH
 ROOM/CORRIDOR WALL- SECTION 607.5.2 FBC M.
  
 4) M2.02: THE 16X6 O/A INTAKE AND EXHAUST REGISTERS IN
 THE EXTERIOR SOFFIT SHALL BE CORROSION RESISTANT AND
 SHALL BE PROTECTED AGAINST WEATHER CONDITIONS- SECTIONS
 401.5 AND 501.3.2 FBC M.
  
 5) M5.03: PLEASE PROVIDE A HORIZONTAL FIRE DAMPER
 DETAIL FOR THE O/A AND EXHAUST RISER DUCTS- SECTION
 607.6.2 FBC M.
  
 6) M3.01: 2ND REQUEST TO REVISE THE OUTDOOR AIR
 CALCULATION SCHEDULE WHICH IS INCORRECTLY INDICATING
 FCU-F FOR THE LAUNDRY INSTEAD OF FCU-C.
  
 7) THE CONDENSER STAND NOA #13-0321.06 HAS BEEN
 SUPERSEDED BY NOA #15-0205.01. PLEASE PROVIDE A COPY OF
 THE NOA WITH APPROVAL STAMP BY THE EOR.
  
 8) PROVIDE A COMPLETE SUBMITTAL PACKAGE IS REQUIRED FOR
 THE GENERATOR INCLUDING THE UL2200 CERTIFICATE OF
 COMPLIANCE, AND ALL MECHANICAL ACCESSORIES INCLUDING
 THE FUEL PIPINGS, VENT AND EXHAUST PIPINGS, WALL
 THIMBLE, TERMINATION CAPS, AND WALL BRACKETS AND
 SUPPORTS. PLEASE NOTE THAT WIND LOAD ENGINEERING WILL
 BE REQUIRED FOR INSTALLATION OF THE EXTERIOR EXHAUST
 VENT ASSEMBLY THAT IS SHOWN ALONG THE EAST WALL BY THE
 GENERATOR ROOM
  
 9) PLEASE REVIEW THE FOLLOWING LIST OF REQUIRED
 SUBMITTALS TO BE APPROVED BY THE DESIGN PROFESSIONAL OF
 RECORD AND SUBMITTED WITH APPROVAL STAMPS.
  
 GENERATOR
 CLOTHES DRYERS (SUBMITTED).
 FIRE/SMOKE DAMPERS
 FIRE DAMPERS
 SMOKE DETECTORS
 O/A MOTORIZED DAMPERS
 AC STANDS
 LOUVERS
 KITCHEN EXHAUST HOODS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-06-06 Cont ID  
Sent By ccole Date 2018-06-01 Time 15:42 Rev Time 0.00
Received By ccole Date 2018-06-01 Time 08:37 Sent To  
Notes
2018-06-01 15:43:491ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18050390
 6/1/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1.01A & M1.01A: SHOW THE O/A INLET AND
 EXHAUST OUTLET LOCATIONS FOR THE UNITS- SECTIONS 401.4
 AND 501.3.1 FBC M. SUBMIT A FL. PRODUCT APPROVAL OR
 MIAMI-DADE NOA FOR THE LOUVERS- RULE 9N-3 FAC.
  
 2) PROVIDE EXHAUST AND AIR BALANCE CALCULATIONS FOR THE
 TRASH ROOM TO VERIFY COMPLIANCE WITH SECTION 601.2
 EXCEPTION 1.
  
 3) M2.01 & M3.01: PROVIDE MECHANICAL VENTILATION
 CALCULATIONS FOR THE FIRST FLOOR UNITS IN THE OUTDOOR
 AIR CALCULATION SCHEDULE- TABLE 403.3.1 FBC M.
  
 4) M2.02, COMMON LAUNDRY: A) SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE CLOTHES DRYERS- SECTION 504.1
 FBC M. B) SHOW HOW MAKEUP AIR IS BEING PROVIDED AND
 PROVIDE AN AIR BALANCE CALCULATION- SECTION 504.6. C)
 INDICATE THE TYPE OF DRYER DUCTS TO BE INSTALLED AND
 THICKNESSES. D) SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE DRYER PLENUM BOX.
  
 5) M2.02: SHOW THE INLET LOCATION OF THE O/A DUCT THAT
 IS SUPPLYING FCU-5 AND FCU-D. THIS NO SHAFT SHOWN ON
 THE 2ND-4TH PLANS, OR ON THE RISER DRAWINGS ON M4.01.
  
 6) M3.01: THE OUTDOOR AIR CALCULATION SCHEDULE IS
 INCORRECTLY INDICATING FCU-F FOR THE LAUNDRY INSTEAD OF
 FCU-C.
  
 7) M4.01: PLEASE SHOW THE LOCATIONS OF THE RISERS AND
 SHAFTS ON THE MECHANICAL FLOOR PLANS. CORRECTLY
 IDENTIFY THEM AS 2HR FIRE-RATED SHAFT ENCLOSURES IN
 ACCORDANCE WITH SECTION 713 FBC B.
  
 8) PROVIDE WIND LOAD ENGINEERING AND THE DESIGN
 CRITERIA FOR INSTALLATION OF THE ROOFTOP CONDENSERS
 SECTION 301.15 FBC M, AND SECTION 1609 FBC B. PLEASE
 SUBMIT A FL. PRODUCT APPROVAL OR MIAMI-DADE NOA FOR THE
 AC STANDS.
  
 9) PLEASE REVIEW THE FOLLOWING LIST OF REQUITED
 SUBMITTALS TO BE APPROVED BY THE DESIGN PROFESSIONAL OF
 RECORD AND SUBMITTED WITH APPROVAL STAMPS.
  
 GENERATOR
 CLOTHES DRYERS
 FIRE/SMOKE DAMPERS
 FIRE DAMPERS
 SMOKE DETECTORS
 O/A MOTORIZED DAMPERS
 AC STANDS
 LOUVERS
 KITCHEN EXHAUST HOODS
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-08-23 Cont ID  
Sent By gjohnson Date 2018-08-23 Time 16:28 Rev Time 0.00
Received By gjohnson Date 2018-08-23 Time 16:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-06-12 Cont ID  
Sent By gjohnson Date 2018-06-12 Time 08:42 Rev Time 0.00
Received By gjohnson Date 2018-06-07 Time 14:21 Sent To  
Notes
2018-06-12 10:00:191ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE INDICATE ON THE PLAN WHICH UNITS COMPLY WITH
 FHA AND LABEL THE DESIGN SPECIFICATION FOR THE
 BATHEOOMS A OR B PER FHA DESIGN MANUAL SPECIFICATION #7
  
 2. SHT. A4.11 THE TOILET PAPER DISPENSER SHALL COMPLY
 WITH FBC ACC 604.7 SHOW ON PLAN.
  
 3. SHT. A4.12 DETAIL #03 THE 30X48 CLEAR FLOOR SPACE
 FOR THE TUB SHALL LINE UP WITH THE CONTROL END OF THR
 TUB. PER FHA DESIGN MANUAL PG. 7.53 REQUIREMENT #7
  
 4. SHT. A4.12 PLEASE LABEL THE BATHROOM DETAILS AS TO
 WHICH UNITS THEY APPLY TOO AND WHICH CODES INCLUDING
 THE DESIGN SPEC FOR THE BATHROOMS COMPLYING WITH FHA
 DESIGN MANUAL.
  
 5. SHT. A4.12 DETAIL #19-20 THE DEPTH OF THE VANITY'S
 IN THE FHA BATHROOMS SHALL BE 24" MAX PER FHA DESIGN
 MANUAL REQUIREMENT #7 PG. 7.43- 7.44
  
 6. SHT. A6.03 DETAIL #6 THE NOTE ON THR ELEVATOR SUMP
 PIT SHOWS A 18X18X24 BUT SHT P1.01B SHOWS IT AT
 24"X24"X24" PLEASE CLARIFY PER WPB AMEND TO FBC107.2.1
  
 7. PLEASE PROVIDE AN ENLARGED PLUMBING FLOOR PLAN FOR
 THE UFAS UNITS ON THE GROUNDD FLOOR. PER WPB AMEND TO
 FBC107.2.1
  
 8. SHT. P3.01 THE DETAIL FOR UNIT TYPE B SHOWS A FLOOR
 DRAIN THE FLOOR PLAN DOES NOT SHOW A FLOOR DRAIN ON THE
 UPPER FLOORS PLEASE CLARIFY. PER WPB AMEND TO
 FBC107.2.1
  
 9. PLEASE PROVIDE MANUFACTURE SPECIFICATIONS FOR THE
 WATER SUB METER IT SHALL BE NON FLAMMABLE AND LEAD FREE
 AND MEET NSF 372.
 PROVIDE MANUFACTURE SPECIFICATION FOR THE THERMOSTATIC
 MIXING VALVE, ELEVATOR SUMP PUMP AND BOOSTER PUMP. PER
 WPB AMEND TO FBC107.2.1
  
 10. THE LAVATORY IN THE COMMON BATHROOM ON THE GROUN
 FLOOR SHALL COMPLY WITH FBC ACC 416.5 TEMPERED WATER
 FOR PUBLIC HAND-WASHING FACILITIES.
 TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND
 GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES
 PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3.
  
 11. PLACE NOTE ON PLAN. SEPARATE PERMIT REQUIRED FOR
 THE BACK FLOWS ON THE FIRE MAIN AND POTABLE WATER
 SERVICE. PER WEST PALM BEACH UTILITIES DEPT.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P-IRRIGATE IRRIGATION REVIEW
Rev No 1 Status P Date 2018-06-08 Cont ID  
Sent By gjohnson Date 2018-06-08 Time 16:14 Rev Time 0.00
Received By gjohnson Date 2018-06-08 Time 16:14 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2018-10-03 Cont ID  
Sent By dbattles Date 2018-10-03 Time 08:11 Rev Time 0.00
Received By dbattles Date 2018-10-03 Time 08:11 Sent To  
Notes
2018-10-03 08:12:26SEE PROVISO IN BUILDING REVIEW.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2018-08-27 Cont ID  
Sent By dbattles Date 2018-08-27 Time 10:49 Rev Time 0.00
Received By dbattles Date 2018-08-24 Time 13:35 Sent To  
Notes
2018-08-27 10:51:07REQUESTED DEFERRED SUBMITTAL.
 FLAT ROOF AND TILE ROOF PRODUCT APPROVALS WERE
 SUBMITTED AND APPROVED.
 DEFERRED SUBMITTAL TO INCLUDE TILE ROOF ATTACHMENT AND
 ENHANCED NAILING IF APPLICABLE.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2018-06-29 Cont ID  
Sent By jgomez Date 2018-06-29 Time 08:16 Rev Time 0.00
Received By jgomez Date 2018-06-29 Time 08:16 Sent To  
Notes
2018-06-29 08:17:341- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
  
 A)FLAT ROOF SINGLE PLY ROOFING NOA 15-0203.23
 SUBMITTED. CLEARLY MARK WHICH APPROVED ASSEMBLY IS
 GOING TO BE INSTALLED. NOTE: IF THE SELECTED ASSEMBLY
 DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES,
 THEN SIGNED AND SEALED RAS 117 CALCULATIONS ARE
 REQUIRED.
  
 B)CONCRETE ROOF TILE NOA 16-0112.07: DESIGNER OF RECORD
 TO SPECIFY ROOF TILE FASTENING METHOD AS REQUIRED BY
 SEC. 107.2.1.1 CITY AMENDMENTS. IF SPECIFYING TILE
 ADHESIVE, THEN PROVIDE PRODUCT APPROVAL FOR LISTED
 ADHESIVE.
  
 C) ROOF VENTS FOR CONCRETE ROOF TILE INSTALLATION AND
 CLEARLY SPECIFY LOCATION ON ROOF.
  
 D)ROOF ATTIC ACCESS DOORS SHOWN ON ROOF PLAN.
  
 2-- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2018-09-14 Cont ID  
Sent By dbattles Date 2018-09-14 Time 08:21 Rev Time 0.00
Received By dbattles Date 2018-09-14 Time 08:21 Sent To  
Notes
2018-09-14 08:21:51NEW SHEETS VERIFIED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2018-09-06 Cont ID  
Sent By dbattles Date 2018-09-06 Time 14:50 Rev Time 0.00
Received By dbattles Date 2018-09-06 Time 14:50 Sent To  
Notes
2018-09-06 14:51:09SHEET M-5.04 NEEDS DIGITAL SIGNATURE

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2018-08-27 Cont ID  
Sent By dbattles Date 2018-08-27 Time 10:48 Rev Time 0.00
Received By dbattles Date 2018-08-27 Time 10:48 Sent To  
Notes
2018-08-27 10:49:23PENDING REVIEW OF REVISED SHEETS.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-06-30 Cont ID  
Sent By shill Date 2018-06-30 Time 10:25 Rev Time 0.00
Received By shill Date 2018-06-30 Time 10:25 Sent To  
Notes
2018-06-30 10:25:25SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. DIGITAL SIGNATURES/SEALS (PLAN PAGES) ARE IN
 ACCORDANCE WITH FS 471, FS 481 AS NOTED. NEW SHEETS
 SUBMITTED IN THE NEXT REVIEW CYCLE REQUIRE REVIEW.
  
 SURVEY NOT DIGITALLY SIGNED AND SEALED; PROVIDE PAPER
 ORIGINAL
  
 ARCH SHEETS SIGNED AND SEALED OK BY ROBERT K. MORISETTE
 ?? (ROBERT K. MORRISETTE??) BUT DISCREPANCY IN SPELLING
 OF NAME (DBPR VS PLAN VS SIGNATURE/SEAL) - THIS COMMENT
 DOES NOT NEED TO BE ADDRESSED BUT PLEASE HAVE ARCHITECT
 ACKNOWLEDGE DISCREPANCY
  
 CIVIL SHEETS ARE OK - DIGITALLY S&S BY EDUARDO A GARCES
 MOYA, PE 84186
 STRUCTURAL SHEETS ARE OK - DIGITALLY S&S BY CHRISTIAN
 AQINO, PE 74647
 MECHANICAL SHEETS ARE OK - DIGITALLY S&S BY RAFAEL
 PENA, PE 16395
 ELECTRICAL SHEETS ARE OK - DIGITALLY S&S BY JOSE A.
 RAMIREZ, PE 60224
 PLUMBING SHEETS ARE OK - DIGITALLY S&S BY RAFAEL PENA,
 PE 16395
 FP SHEETS ARE OK - DIGITALLY S&S BY RAFAEL PENA, PE
 16395
  
 2. ENERGY CALCS S&S (IN SUPPORTING DOCUMENTS FOLDER) IS
 OK; NEED RE-REVIEW IF REPLACED BY A NEW DOCUMENT.
  
 3. PERC TEST AND SOILS REPORT (IN SUPPORTING DOCUMENTS
 FOLDER) IS NOT DIGITALLY SIGNED AND SEALED IN
 ACCORDANCE WITH FS471. A PAPER ORIGINAL MAY BE PROVIDED
 TO RESOLVE THIS COMMENT (AT END OF PLAN REVIEW
 PROCESS), OR UPLOAD A DIGITALLY SIGNED AND SEALED
 DOCUMENT.
  
 4. STRUCTURAL CALCS S&S (IN SUPPORTING DOCUMENTS
 FOLDER) IS OK; NEED RE-REVIEW IF REPLACED BY A NEW
 DOCUMENT.
  
  
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 5 Status P Date 2018-10-03 Cont ID  
Sent By dbattles Date 2018-10-03 Time 08:05 Rev Time 0.00
Received By dbattles Date 2018-10-03 Time 08:05 Sent To  
Notes
2018-10-03 08:09:55THRESHOLD INSPECTOR:
 JAMES J. FLAIG, P.E. #21083 AND S.I. #660
 561-736-4900
  
 ADDITIONAL INSPECTORS:
 JAMES HARPER BN#4544
 561-414-4389
  
 DIGITAL COPY SAVED ON FRONT SCREEN AS ATTACHMENT.

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 4 Status F Date 2018-09-14 Cont ID  
Sent By dbattles Date 2018-09-14 Time 16:26 Rev Time 0.00
Received By dbattles Date 2018-09-14 Time 16:26 Sent To  
Notes
2018-09-14 16:34:281. PROVIDE THE THRESHOLD INSPECTOR AGREEMENT ON THE
 FORM THAT HAS BEEN SENT VIA E-MAIL ON 9/14/18
  
 2. PLEASE PROVIDE RESUME OF THE THRESHOLD INSPECTOR.
  
 3. PROVIDE ADDITIONAL NAMES OF INSPECTORS THAT MAY
 PERFORM INSPECTIONS ON THE PROVIDED FORM.
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 3 Status F Date 2018-09-06 Cont ID  
Sent By dbattles Date 2018-09-06 Time 14:56 Rev Time 0.00
Received By dbattles Date 2018-09-06 Time 14:55 Sent To  
Notes
2018-09-06 14:55:55553.79(5) 2016, THIS IS A THRESHOLD BUILDING. THE
 FOLLOWING IS REQUIRED PRIOR TO COMMENCEMENT:
  
 1. COMPLETE THE THRESHOLD / SPECIAL INSPECTOR AGREEMENT
 OF UNDERSTANDING;
 PLEASE CONTACT [email protected] TO SEND THIS FORM TO
 THE RESPONSIBLE PARTY.
  
 2. PROVIDE RESUMES AND COPIES OF LICENSES FOR ALL
 PROPOSED INSPECTORS.
  
 3. ALL PLANS ARE TO INCLUDE THE THRESHOLD STATEMENT
 REQUIRED BY FS553.79(7)(D).
 PLEASE LEAD ME TO WHERE THIS STATEMENT CAN BE FOUND ON
 PLANS, OR PROVIDE ON GENERAL NOTE SHEET FOR
 ARCHITECTURAL AND STRUCTURAL PLANS.
  
 (D)ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED TO BE
 SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRESAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS CHAPTER 553 AND CHAPTER 633.
  
 4. THRESHOLD INSPECTION PLAN REQUIRED, FS553.79(5)A).
 -IN PLANS SHEET S1.0 AND S1.1

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status F Date 2018-08-27 Cont ID  
Sent By dbattles Date 2018-08-27 Time 11:01 Rev Time 0.00
Received By dbattles Date 2018-08-27 Time 11:01 Sent To  
Notes
2018-08-27 11:00:57553.79(5) 2016, THIS IS A THRESHOLD BUILDING. THE
 FOLLOWING IS REQUIRED PRIOR TO COMMENCEMENT:
  
 1. COMPLETE THE THRESHOLD / SPECIAL INSPECTOR AGREEMENT
 OF UNDERSTANDING;
 PLEASE CONTACT [email protected] TO SEND THIS FORM TO
 THE RESPONSIBLE PARTY.
  
 2. PROVIDE RESUMES AND COPIES OF LICENSES FOR ALL
 PROPOSED INSPECTORS.
  
 3. ALL PLANS ARE TO INCLUDE THE THRESHOLD STATEMENT
 REQUIRED BY FS553.79(7)(D).
 PLEASE LEAD ME TO WHERE THIS STATEMENT CAN BE FOUND ON
 PLANS, OR PROVIDE ON GENERAL NOTE SHEET FOR
 ARCHITECTURAL AND STRUCTURAL PLANS.
  
 (D)ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED TO BE
 SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRESAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS CHAPTER 553 AND CHAPTER 633.
  
 4. THRESHOLD INSPECTION PLAN REQUIRED, FS553.79(5)A).
 -IN PLANS SHEET S1.0 AND S1.1
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2018-06-30 Time   Rev Time 0.00
Received By   Date 2018-06-30 Time   Sent To  
Notes
2018-06-30 10:00:43SEE BUILDING REVIEW
  

Review Stop Z ZONING
Rev No 3 Status P Date 2018-09-07 Cont ID  
Sent By llouie Date 2018-09-07 Time   Rev Time 0.00
Received By llouie Date 2018-09-07 Time   Sent To  
Notes
2018-09-06 16:15:04PROVISOS:
  
 1.) A MINOR PD AMENDMENT IS REQUIRED FOR THE AS-BUILT
 PRIOR TO CERTIFICATE OF OCCUPANCY (C.O.).
  
 2.) PARKING STALL STRIPING SHALL BE CONSISTENT WITH THE
 CITY'S STANDARDS FOR STRIPING.
  
 3.) SEPERATE PERMIT REQUIRED FOR LANDSCAPING.
  
  
 NOTE: PLEASE SEE ATTACHED EMAIL FROM RELATED REGARDING
 THE COUNTY ROW PERMIT.
  

Review Stop Z ZONING
Rev No 2 Status F Date 2018-08-07 Cont ID  
Sent By llouie Date 2018-08-07 Time   Rev Time 0.00
Received By llouie Date 2018-08-07 Time   Sent To  
Notes
2018-08-07 12:05:45** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) PER THE SITE PLAN CONDITIONAL APPROVAL LETTER,
 ISSUED 6/20/18, NO BUILDING PERMITS WILL BE ISSUED
 UNTIL A COPY OF THE RIGHT-OF-WAY PERMIT FOR THE
 MODIFICATION TO THE ENTRANCE OF THE DEVELOPMENT FROM
 COMMUNITY DRIVE IS OBTAINED FROM PALM BEACH COUNTY.
  
 2.) IT SEEMS THE BUILDING FOOTPRINT MAY HAVE SHIFTED IN
 THE BUILDING PERMIT SET, AS THE BUILDING SETBACKS DO
 NOT MATCH THE SETBACKS IN THE APPROVED SITE PLAN.
 PLEASE ADDRESS FOR CONSISTENCY. IF THE BUILDING
 SETBACKS HAVE CHANGED, THEN A MINOR AMENDMENT TO THE
 PLANNED DEVELOPMENT (PD) WILL BE REQUIRED TO MATCH THE
 BUILDING PERMIT SET PRIOR TO BUILDING PERMIT.
  
 3.) PAVEMENT MARKING DETAILS ON SHEET C-18.0 IS
 INCONSISTENT WITH THE STRIPING REQUIREMENTS OF THE
 ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDRS). PLEASE
 CORRECT.
  
 4.) ZONING DATA ON SHEET A0.11 DOES NOT MATCH THE
 ZONING DATA IN THE APPROVED SITE PLAN. CHANGES TO THE
 DATA SINCE SITE PLAN APPROVAL HAS BEEN DETECTED (I.E.
 BUILDING SETBACKS, BUILDING AREA, ETC.). A MINOR PD
 AMENDMENT IS REQUIRED FOR CHANGES TO THE APPROVED SITE
 PLAN.
  
 5.) DIMENSIONS PROVIDED IN THE ARCHITECTURAL ELEVATIONS
 DOES NOT MATCH THE DIMENSIONS PROVIDED IN THE APPROVED
 PLANS. PLEASE ADDRESS.
  
 NOTES:
  
 * SEPARATE PERMITS REQUIRED FOR THE FOLLOWING:
 LANDSCAPE AND IRRIGATION
  
 * REVISION MAY RESULT IN ADDITIONAL COMMENTS.
  
 *REFERENCE: PB 997B/ORDINANCE NO. 4757-17 AND MAJOR PD
 AMENDMENT SITE PLAN CONDITIONAL APPROVAL LETTER ISSUED
 ON 6/20/18
  
 * ZONE: RPD
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2018-05-21 Cont ID  
Sent By LL Date 2018-05-21 Time   Rev Time  
Received By llouie Date 2018-05-21 Time   Sent To  
Notes
2018-05-21 14:58:40** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) THE PROJECT HAS NOT BEEN GRANTED FINAL SITE PLAN
 APPROVAL. SITE PLAN APPROVAL SHALL BE GRANTED BY THE
 PLANNING AND ZONING DIVISION PRIOR TO BUILDING PERMIT
 REVIEW AND APPROVAL. ALL PLANS FOR THIS PERMIT SHALL
 MATCH THE FINAL APPROVED SITE PLAN.
  
  
 NOTES:
  
 * REFERENCE: ORDINANCE NO. 4757-17
  
 * REVISION MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: RPD (UNDERLYING MF32)
  
 * SEPARATE PERMITS REQUIRED FOR: LANDSCAPING,
 IRRIGATION, LIGHTING, PAVEMENT STRIPING AND SIGNAGE.
  
 * A TREE ALTERATION PERMIT IS REQUIRED PRIOR TO THE
 REMOVAL OF ANY EXISTING TREES OR PALMS ON THE PROPERTY.
 CONTACT RAY CARANCI, CITY LANDSCAPE PLANNER, AT (561)
 822-1462.
  