Plan Review Details - Permit 18050358
Plan Review Stops For Permit 18050358
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-10-29 Cont ID  
Sent By shill Date 2018-10-29 Time 07:39 Rev Time 0.00
Received By shill Date 2018-10-29 Time 07:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-06-15 Cont ID  
Sent By shill Date 2018-06-15 Time 13:18 Rev Time 0.00
Received By shill Date 2018-06-15 Time 13:11 Sent To  
Notes
2018-06-15 13:21:51****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. PROVIDE A SITE PLAN WHICH SHOWS LOCATION OF PROPOSED
 IMPROVEMENT, FBC 107.
  
 2. PROVIDE STRUCTURAL DETAILS FOR THE FOUNTAIN,
 FOUNTAIN SCULPTURE BASE, TANK, ETC (ALL ITEMS SHOWN ON
 WF06). S611 WAS SUBMITTED BUT APPEARS TO SHOW
 STRUCTURAL INFORMATION FOR OTHER ITEMS WHICH ARE
 INCLUDED IN PERMIT 18040801. NOTE THAT ALTHOUGH I
 PASSED THAT REVIEW, IT WAS LACKING THE STRUCTURAL
 INFORMATION. PLEASE HAVE SHEET S611 ADDED TO PERMIT
 18040801.
  
 3. REVISE PLAN TO INCLUDE WIND DESIGN CRITERIA, FBC B
 1603.1.4, 1609 (WIND SPEED, EXPOSURE).
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-06-07 Cont ID  
Sent By jpearson Date 2018-06-07 Time 10:31 Rev Time 0.00
Received By jpearson Date 2018-06-07 Time 10:31 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2018-06-08 Cont ID  
Sent By gjohnson Date 2018-06-08 Time 15:33 Rev Time 0.00
Received By gjohnson Date 2018-06-08 Time 15:33 Sent To  
Notes
2018-06-08 15:34:21GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT AND PLANS IS REQUIRED FOR THE GAS
 INSTALLATION OR MODIFICATION OF SYSTEM.
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-29 Cont ID  
Sent By shill Date 2018-10-29 Time 07:45 Rev Time 0.00
Received By shill Date 2018-09-14 Time 10:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-07-11 Cont ID  
Sent By cpuell Date 2018-07-11 Time 08:55 Rev Time 0.00
Received By cpuell Date 2018-05-16 Time 15:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-06-08 Cont ID  
Sent By gjohnson Date 2018-06-08 Time 15:34 Rev Time 0.00
Received By gjohnson Date 2018-06-08 Time 15:34 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2018-06-15 Cont ID  
Sent By shill Date 2018-06-15 Time 13:12 Rev Time 0.00
Received By shill Date 2018-06-15 Time 13:11 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-07-11 Cont ID  
Sent By JR Date 2018-07-11 Time 08:43 Rev Time 0.00
Received By jroach Date 2018-07-11 Time 08:43 Sent To  
Notes
***NONE***