Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-10-30 Cont ID  
Sent By dbattles Date 2018-10-30 Time 08:02 Rev Time 0.00
Received By dbattles Date 2018-10-30 Time 08:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-10-02 Cont ID  
Sent By dbattles Date 2018-10-02 Time 08:35 Rev Time 0.00
Received By dbattles Date 2018-10-01 Time 09:32 Sent To  
Notes
2018-10-02 08:37:05****CORRECTIONS****
 W.P.B. PERMIT: 18050348
 3RD REVIEW: OCTOBER 2, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. OK
  
 2. NO COMMENT RESPONSE SHEET PROVIDED SO I CAN?T SEE
 HOW A DRAINAGE PLAN IS BEING IMPLEMENTED TO MAINTAIN
 DRAINAGE WITH THE SITE.
 PLEASE PROVIDE SITE DRAINAGE PLAN ACCORDING TO THE
 FOLLOWING CODE REFERENCES-[FBC AMENDED 107.5][FBC
 110.9][FBC R401.3]
  
 3. FBC 110.9, PROVIDE A DETAIL TO SHOW HOW ADJACENT
 PROPERTIES WILL BE PROTECTED (SILT FENCE).
  
 3. ADDITIONAL COMMENT-A SILT FENCE DETAIL CAN BE FOUND
 AT-
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 4. OK
  
 5. FBC R 311.2, REVISE PLAN TO SHOW ENTRY DOOR WITH
 MINIMUM 32" CLEAR WIDTH.
  
 6. FBC 107, REVISE PLAN TO INCLUDE ALL DOOR SIZES
 (EXAMPLE; ENTRY DOOR, WIC).
  
 7. FBC 107, FBC R 301, REVISE PLAN TO SHOW ALL WINDOW
 SIZES (EXAMPLE; ENTRY DOOR SIDELITE).
  
 8. A1GH, DOOR FROM GARAGE TO GUEST HOUSE, REVISE PLAN
 TO SHOW COMPLIANCE WITH FBC R 303.5.1.
  
 5-8. ADDITIONAL COMMENT-THESE CAN ALL BE ADDRESSED BY
 ADDING A WINDOW AND DOOR SCHEDULE.
  
 9. A1ADD, A1GH, WALL BETWEEN GARAGE AND RESIDENCE,
 CLARIFY CONSTRUCTION AND INSULATION, FBC R 302.6. NOTE
 THAT INSULATION IS SHOWN GRAPHICALLY ON A PORTION OF
 THE WALL ON A1ADD; NOT CLEAR WHY THIS ISN'T CONTINUOUS
 ON ALL GARAGE WALLS SEPARATING GARAGE FROM RESIDENCE.
  
 9. ADDITIONAL COMMENT-THIS COMMENT WAS BEACAUSE THERE
 IS INSULATION HATCH AT GARAGE WALL, BUT THE HATCH ISN?T
 APPLIED ALONG THE WHOLE GARAGE /HOUSE DIVIDING WALL.
 PLEASE SHOW THE INSULATION HATCHING TO SHOW CONTINUOUS
 THERMAL BARRIER.
 FOR CONSISTENCY CAN THE HATCH BE APPLIED TO BOTH NEW
 GARAGES, OR SHOW WALL TYPE DETAIL COMMON TO GARAGE
 SEPARATION.
  
 10-12. OK
  
 NEW COMMENTS FROM GUEST HOUSE REMOVAL:
  
 13. CONSOLIDATE THE AREA TABULATIONS.
 SHOW EXISTING UNDER AIR AND EXISTING TOTAL (3301 UNDER
 AIR AND 4298 TOTAL ACCORDING TO PROPERTY APPRAISERS)
 NEW ADDITION UNDER AIR AND NEW TOTAL.
 NEW TOTAL UNDER AIR AND NEW TOTAL SQ. FOOTAGE.
 THE NEW TABLE SHOULD REPLACE THE TABLES ON S-1, A-1 ADD
 AND A1 ADD-W.
  
 14. CONSOLIDATE THE ENERGY CALCULATIONS. PUT ALL AREA,
 INCLUDING THE NEW SPACE CONNECTED THE PREVIOUS LAYOUTS,
 INTO ONE ENERGY CALCULATION SUBMITTAL.
  
 15. SHEET C-1 REMOVE THE WORD GUEST HOUSE FROM TITLE
 BLOCK, MAIN TITLE AND DRAWING INDEX.
  
 16. SHEET A-1 PROVIDE NEW SHEET W/O GUEST HOUSE IN THE
 TITLE BLOCK AND THE PBC STAMP FOR IMPACT WOULD NO
 LONGER BE VALID FOR THIS PROJECT. (SEE IMPACT REVIEW
 FOR COMMENTS ON IMPACT).
  
 17. SHEET A-4 REMOVE GUEST HOUSE FROM TITLE BLOCK.
  
 18. [FBC R302.10]PROVIDE CUT SHEET FOR ICYNENE(ICC-ES
 REPORT OR EQUAL) WITH THE TYPE SELECTED TO ESTABLISH
 THICKNESS NEEDED TO MEET REQUIRED R-VALUE, FLAME SPREAD
 INDEX AND SMOKE DEVELOPED INDEX.
 ICYNENE REQUIRES THERMAL BARRIER FROM ATTIC. IF THERE
 IS MECHANICAL EQUIPMENT IN THE SPACE THAN IT REQUIRES
 IGNITION BARRIER.
  
 19. [FBC AMENDED 107.3.4.1]PROVIDE PRODUCT APPROVALS
 FOR ROOFING, OR INDICATE THAT YOU WOULD LIKE THEM
 DEFERED.
 10/4/18 CUSTOMER REQUESTED DEFERAL AND R-STOP IS
 CHANGED TO "N" STATUS TO INDICATE THAT ROOFER WILL
 PROVIDE SUBMITTAL UNDER ROOFING SUB PERMIT.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-08-21 Cont ID  
Sent By shill Date 2018-08-21 Time 17:47 Rev Time 0.00
Received By shill Date 2018-08-21 Time 14:22 Sent To  
Notes
2018-08-21 17:47:46****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINAL
 (SOILS REPORTS), FS471, FAC61G15-23.002.
  
 2. FBC 107.2.5, DRAINAGE PLAN IS REQUIRED. SEE ALSO FBC
 110.9:
  
 110.9 IMPACT OF CONSTRUCTION. ALL CONSTRUCTION ACTIVITY
 REGULATED BY THIS CODE SHALL BE PERFORMED
 IN A MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION
 OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID PROPERTY PURSUANT
 TO A CONSENT GRANTED BY THE APPLICABLE
 PROPERTY OWNER, UNDER TERMS OR CONDITIONS AGREEABLE TO
 THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES, BUT IS NOT LIMITED TO, THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFFS, DEBRIS,
 AND THE STORAGE OF CONSTRUCTION MATERIALS. NEW
 CONSTRUCTION ACTIVITY SHALL NOT ADVERSELY
 IMPACT LEGAL HISTORIC SURFACE WATER DRAINAGE FLOWS
 SERVING ADJACENT PROPERTIES, AND MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE DRAINAGE PATTERNS OF THE AFFECTED SITES.
 ACCORDINGLY, DEVELOPERS, CONTRACTORS AND
 OWNERS OF ALL NEW RESIDENTIAL DEVELOPMENT, INCLUDING
 ADDITIONS, POOLS, PATIOS, DRIVEWAYS, DECKS
 OR SIMILAR ITEMS, ON EXISTING PROPERTIES RESULTING IN A
 SIGNIFICANT DECREASE OF PERMEABLE LAND
 AREA ON ANY PARCEL OR HAS ALTERED THE DRAINAGE FLOW ON
 THE DEVELOPED PROPERTY SHALL, AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE
 WITH THIS PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATION FROM A LICENSED
 PROFESSIONAL SHALL BE SUBMITTED TO THE INSPECTOR IN
 ORDER TO RECEIVE APPROVAL OF THE FINAL
 INSPECTION.
  
 2ND REVIEW, DRAINAGE WAS SHOWN AT THE COURTYARD, BUT
 DRAINAGE FOR THE AREA BETWEEN PROPOSED GUEST HOUSE AND
 PROPERTY LINE NOT SHOWN. IT IS NOT CLEAR WHERE THE
 WATER COLLECTED BY THE DRAINS WILL BE DISCHARGED. NO
 ELEVATIONS SHOWN FOR THE TWO PROPERTY LINES AND
 ADJACENT PROPERTIES.
  
 3. FBC 110.9, PROVIDE A DETAIL TO SHOW HOW ADJACENT
 PROPERTIES WILL BE PROTECTED (SILT FENCE).
  
 4. OK
  
 5. FBC R 311.2, REVISE PLAN TO SHOW ENTRY DOOR WITH
 MINIMUM 32" CLEAR WIDTH.
  
 6. FBC 107, REVISE PLAN TO INCLUDE ALL DOOR SIZES
 (EXAMPLE; ENTRY DOOR, WIC).
  
 7. FBC 107, FBC R 301, REVISE PLAN TO SHOW ALL WINDOW
 SIZES (EXAMPLE; ENTRY DOOR SIDELITE).
  
 8. A1GH, DOOR FROM GARAGE TO GUEST HOUSE, REVISE PLAN
 TO SHOW COMPLIANCE WITH FBC R 303.5.1.
  
 9. A1ADD, A1GH, WALL BETWEEN GARAGE AND RESIDENCE,
 CLARIFY CONSTRUCTION AND INSULATION, FBC R 302.6. NOTE
 THAT INSULATION IS SHOWN GRAPHICALLY ON A PORTION OF
 THE WALL ON A1ADD; NOT CLEAR WHY THIS ISN'T CONTINUOUS
 ON ALL GARAGE WALLS SEPARATING GARAGE FROM RESIDENCE.
  
 10. A3ADD, IT APPEARS SOME CONNECTORS ARE NOT
 SPECIFIED. SEE COURTYARD, BEDROOM A, CHECK ALL.
  
 11. FBC 107, PRODUCT APPROVALS ARE TO BE REVIEWED BY
 DESIGNER OF RECORD.
  
 12. WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED
 SETS OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS".
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-06-18 Cont ID  
Sent By shill Date 2018-06-18 Time 18:05 Rev Time 0.00
Received By shill Date 2018-06-18 Time 07:40 Sent To  
Notes
2018-06-18 18:07:01****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINAL
 (SOILS REPORTS), FS471, FAC61G15-23.002.
  
 2. FBC 107.2.5, DRAINAGE PLAN IS REQUIRED. SEE ALSO FBC
 110.9:
  
 110.9 IMPACT OF CONSTRUCTION. ALL CONSTRUCTION ACTIVITY
 REGULATED BY THIS CODE SHALL BE PERFORMED
 IN A MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION
 OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID PROPERTY PURSUANT
 TO A CONSENT GRANTED BY THE APPLICABLE
 PROPERTY OWNER, UNDER TERMS OR CONDITIONS AGREEABLE TO
 THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES, BUT IS NOT LIMITED TO, THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFFS, DEBRIS,
 AND THE STORAGE OF CONSTRUCTION MATERIALS. NEW
 CONSTRUCTION ACTIVITY SHALL NOT ADVERSELY
 IMPACT LEGAL HISTORIC SURFACE WATER DRAINAGE FLOWS
 SERVING ADJACENT PROPERTIES, AND MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE DRAINAGE PATTERNS OF THE AFFECTED SITES.
 ACCORDINGLY, DEVELOPERS, CONTRACTORS AND
 OWNERS OF ALL NEW RESIDENTIAL DEVELOPMENT, INCLUDING
 ADDITIONS, POOLS, PATIOS, DRIVEWAYS, DECKS
 OR SIMILAR ITEMS, ON EXISTING PROPERTIES RESULTING IN A
 SIGNIFICANT DECREASE OF PERMEABLE LAND
 AREA ON ANY PARCEL OR HAS ALTERED THE DRAINAGE FLOW ON
 THE DEVELOPED PROPERTY SHALL, AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE
 WITH THIS PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATION FROM A LICENSED
 PROFESSIONAL SHALL BE SUBMITTED TO THE INSPECTOR IN
 ORDER TO RECEIVE APPROVAL OF THE FINAL
 INSPECTION.
  
 3. FBC 110.9, PROVIDE A DETAIL TO SHOW HOW ADJACENT
 PROPERTIES WILL BE PROTECTED (SILT FENCE).
  
 4. FBC R 314, R 315, NO SMOKE/CO ALARMS SHOWN FOR HOUSE
 ADDITION OR EXISTING HOUSE, SMOKE ALARM ONLY SHOWN FOR
 GUEST HOUSE, REVISE.
  
 5. FBC R 311.2, REVISE PLAN TO SHOW ENTRY DOOR WITH
 MINIMUM 32" CLEAR WIDTH.
  
 6. FBC 107, REVISE PLAN TO INCLUDE ALL DOOR SIZES
 (EXAMPLE; ENTRY DOOR, WIC).
  
 7. FBC 107, FBC R 301, REVISE PLAN TO SHOW ALL WINDOW
 SIZES (EXAMPLE; ENTRY DOOR SIDELITE).
  
 8. A1GH, DOOR FROM GARAGE TO GUEST HOUSE, REVISE PLAN
 TO SHOW COMPLIANCE WITH FBC R 303.5.1.
  
 9. A1ADD, A1GH, WALL BETWEEN GARAGE AND RESIDENCE,
 CLARIFY CONSTRUCTION AND INSULATION, FBC R 302.6. NOTE
 THAT INSULATION IS SHOWN GRAPHICALLY ON A PORTION OF
 THE WALL ON A1ADD; NOT CLEAR WHY THIS ISN'T CONTINUOUS
 ON ALL GARAGE WALLS SEPARATING GARAGE FROM RESIDENCE.
  
 10. A3ADD, IT APPEARS SOME CONNECTORS ARE NOT
 SPECIFIED. SEE COURTYARD, BEDROOM A, CHECK ALL.
  
 11. FBC 107, PRODUCT APPROVALS ARE TO BE REVIEWED BY
 DESIGNER OF RECORD.
  
 12. WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED
 SETS OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS".
  
 13. PROVIDE VALUE FOR THE FOLLOWING; SEPARATE PERMITS
 ARE REQUIRED:
  
 ADDITION
 GUEST HOUSE
 GENERATOR
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-10-02 Cont ID  
Sent By jpearson Date 2018-10-02 Time 12:00 Rev Time 0.00
Received By jpearson Date 2018-10-02 Time 10:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-08-06 Cont ID  
Sent By ppetty Date 2018-08-06 Time 11:07 Rev Time 0.00
Received By ppetty Date 2018-08-06 Time 11:07 Sent To  
Notes
2018-08-06 11:07:40CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. OK
 2. THE NEC SPECIFIED FOR DESIGN IS NOT THE CURRENT
 CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE CURRENT
 CODES ABOVE)
 3. PROVIDE LOAD CALCULATION FOR 400 AMP SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE
 E3602.2
 4. NOTE ON PLAN FOR AFCI COMPLIANCE IS NOT ACCURATE.
 ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE,
 15- AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. PROVIDE CORRECTION. NEC
 210.12; FBC RE E3902.16
 5. OK
 6. PROVIDE ACCURATE RISER DIAGRAM. PLAN STATES THAT A
 GENERATOR WILL BE INSTALLED, BUT NO TRANSFER SWITCHES
 ARE SHOWN. ALSO PROVIDE WIRE SIZE FOR FEEDERS AND
 GROUNDING ELECTRODE CONDUCTORS TO CONFIRM CODE
 COMPLIANCE. NEC 215.5, 230, 250.50, 250.94, 408.30; FBC
 RE E3706.1, E3608.1, E3609.3; WPB FBC 107.2.1
 7. OK
 8. RECEPTACLES IN STORAGE AREAS REQUIRE GFCI
 PROTECTION. PROVIDE CORRECTION. NEC 210.8; FBC RE
 E3902.2
 9. OK
 10. OK
 11. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 12. OK
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER
 561-805-6742
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-06-07 Cont ID  
Sent By jpearson Date 2018-06-07 Time 09:32 Rev Time 0.00
Received By jpearson Date 2018-06-06 Time 13:54 Sent To  
Notes
2018-06-07 09:32:23CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (BOTH
 COPIES) IS REQUIRED TO BEAR THE NAME AND BE SIGNED AND
 SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN.
 PROVIDE CORRECTION. WPB FBC 107.1, 107.2; FS 471, 481
 2. THE NEC SPECIFIED FOR DESIGN IS NOT THE CURRENT
 CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE CURRENT
 CODES ABOVE)
 3. PROVIDE LOAD CALCULATION FOR 400 AMP SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE
 E3602.2
 4. NOTE ON PLAN FOR AFCI COMPLIANCE IS NOT ACCURATE.
 ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE,
 15- AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. PROVIDE CORRECTION. NEC
 210.12; FBC RE E3902.16
 5. PROVIDE BLOCK NOTE THAT THE GENERATOR REQUIRES A
 SEPARATE PERMIT. WPB FBC 105.1, 107.2.1
 6. PROVIDE ACCURATE RISER DIAGRAM. PLAN STATES THAT A
 GENERATOR WILL BE INSTALLED, BUT NO TRANSFER SWITCHES
 ARE SHOWN. ALSO PROVIDE WIRE SIZE FOR FEEDERS AND
 GROUNDING ELECTRODE CONDUCTORS TO CONFIRM CODE
 COMPLIANCE. NEC 215.5, 230, 250.50, 250.94, 408.30; FBC
 RE E3706.1, E3608.1, E3609.3; WPB FBC 107.2.1
 7. GFCI PROTECTION IS REQUIRED FOR ALL OUTLETS IN
 GARAGE, INCLUDING GARAGE DOOR OPENERS AND
 REFRIGERATORS. PROVIDE CORRECTION. NEC 210.8; FBC RE
 E3902.2
 8. RECEPTACLES IN STORAGE AREAS REQUIRE GFCI
 PROTECTION. PROVIDE CORRECTION. NEC 210.8; FBC RE
 E3902.2
 9. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C
 EQUIPMENT WITHIN 25 FEET OF THE EQUIPMENT PER CODE,
 INCLUDING THE MINI-SPLIT UNITS. NEC 210.63; FBC RE
 E3901.12
 10. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. SHOW ON PLAN ALL EXISTING ALARMS. INCLUDE
 MAIN HOUSE EXISTING FLOOR PLAN. IF NONE ARE EXISTING OR
 NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC RE R314.3,
 R315.1; WPB FBC 107.2.1
 11. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 12. PROVIDE GFCI PROTECTED OUTLET ON THE KITCHEN
 PENINSULA AT A LOCATION WHERE THERE IS NOT THE 12 INCH
 COUNTER TOP OVERHANG.. NEC 210.8, 210.52(C)(3); FBC RE
 E3901.4.3, 3901.4.5
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2018-09-04 Cont ID  
Sent By gjohnson Date 2018-09-04 Time 11:34 Rev Time 0.00
Received By gjohnson Date 2018-09-04 Time 11:34 Sent To  
Notes
2018-09-04 11:35:50GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT AND PLANS IS REQUIRED FOR THE GAS
 INSTALLATION OR MODIFICATION OF SYSTEM.
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-10-30 Cont ID  
Sent By gjohnson Date 2018-10-30 Time 09:17 Rev Time 0.00
Received By gjohnson Date 2018-10-26 Time 12:40 Sent To  
Notes
2018-10-26 12:51:58LIBRARY

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-10-16 Cont ID  
Sent By gjohnson Date 2018-10-16 Time 09:49 Rev Time 0.00
Received By gjohnson Date 2018-09-11 Time 10:59 Sent To  
Notes
2018-09-13 10:59:18R35

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-30 Cont ID  
Sent By shill Date 2018-08-30 Time 16:03 Rev Time 0.00
Received By shill Date 2018-07-09 Time 14:22 Sent To  
Notes
2018-07-11 14:22:30R35

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-18 Cont ID  
Sent By shill Date 2018-06-18 Time 18:07 Rev Time 0.00
Received By shill Date 2018-05-08 Time 11:48 Sent To  
Notes
2018-05-09 11:48:48R28

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 5 Status P Date 2018-10-30 Cont ID  
Sent By dbattles Date 2018-10-30 Time 16:26 Rev Time 0.00
Received By dbattles Date 2018-10-30 Time 16:26 Sent To  
Notes
2018-10-30 16:27:14M.U.-15496

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status F Date 2018-10-30 Cont ID  
Sent By dbattles Date 2018-10-30 Time 08:02 Rev Time 0.00
Received By dbattles Date 2018-10-30 Time 08:02 Sent To  
Notes
2018-10-30 08:03:04IMPACT FEES WERE PAID, BUT THE LAYOUT HAS CHANGED AND
 THE SHEET WITH THE PBC FEE STAMP IS BEING REMOVED AS IT
 IS NO LONGER VALID.
 UPON RESOLVING THE CURRENT COMMENTS, A COPY OF PLANS
 SHOULD BE CHECKED OUT AND BROUGHT BACK TO PBC FOR NEW
 STAMP BASED ON THE REVISED AREA TABULATIONS REQUESTED
 IN 3RD ROUND BUILDING COMMENTS.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2018-10-02 Cont ID  
Sent By dbattles Date 2018-10-02 Time 08:37 Rev Time 0.00
Received By dbattles Date 2018-10-02 Time 08:37 Sent To  
Notes
2018-10-02 08:41:09IMPACT FEES WERE PAID, BUT THE LAYOUT HAS CHANGED AND
 THE SHEET WITH THE PBC FEE STAMP IS BEING REMOVED AS IT
 IS NO LONGER VALID.
 UPON RESOLVING THE CURRENT COMMENTS, A COPY OF PLANS
 SHOULD BE CHECKED OUT AND BROUGHT BACK TO PBC FOR NEW
 STAMP BASED ON THE REVISED AREA TABULATIONS REQUESTED
 IN 3RD ROUND BUILDING COMMENTS.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2018-08-21 Cont ID  
Sent By shill Date 2018-08-21 Time 17:24 Rev Time 0.00
Received By shill Date 2018-08-21 Time 17:24 Sent To  
Notes
2018-08-21 17:24:56MU-2018-015500
 $5398.15
  
 MU-2018-015496
 $21.91
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-06-18 Cont ID  
Sent By shill Date 2018-06-18 Time 07:41 Rev Time 0.00
Received By shill Date 2018-06-18 Time 07:40 Sent To  
Notes
2018-06-18 07:42:51****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS REQUIRED.
 THE PLANS ARE TO BE STAMPED AND THE RECEIPT SHOWING
 THAT FEES DUE, IF APPLICABLE, PROVIDED.
  
 A STAMPED PLAN WAS PROVIDED SHOWING REVIEW 18-15500,
 $5398.15 DUE (GUEST HOUSE) AND REVIEW 18-15496, $21.91
 DUE (ADDITION), BUT THE RECEIPT SHOWING THAT FEES DUE
 WERE PAID WAS NOT PROVIDED. PLEASE PROVIDE.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2018-10-27 Cont ID  
Sent By cmontell Date 2018-10-27 Time 05:13 Rev Time 0.00
Received By cmontell Date 2018-10-27 Time 05:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2018-10-13 Cont ID  
Sent By cmontell Date 2018-10-13 Time 07:21 Rev Time 0.00
Received By cmontell Date 2018-10-13 Time 07:20 Sent To  
Notes
2018-10-13 07:21:07MECHANICAL PLAN REVIEW FAIL
  
 1 - PLANS NEED TO BE SIGNED BY CONTRACTOR
  
 2 - MINISPLIT SYSTEMS FOR GARAGE NOT LISTED ON ENERGY
 CALC
  
 CHRIS MONTELLO
 561-805-6733
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-07-23 Cont ID  
Sent By cmontell Date 2018-07-23 Time 14:07 Rev Time 0.00
Received By cmontell Date 2018-07-23 Time 13:55 Sent To  
Notes
2018-07-23 14:07:30MECHANICAL PLAN REVIEW FAIL
  
 1 - PLANS NEED TO BE SIGNED BY CONTRACTOR
  
 2 - MINISPLIT SYSTEMS FOR GARAGE NOT LISTED ON ENERGY
 CALC
  
 CHRIS MONTELLO
 561-805-6733
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-06-04 Cont ID  
Sent By cmontell Date 2018-06-04 Time 15:20 Rev Time 0.00
Received By cmontell Date 2018-06-04 Time 14:59 Sent To  
Notes
2018-06-04 15:01:19MINISPLIT SYSTEMS FOR GARAGE NOT LISTED ON ENERGY CALC
  
 CHRIS MONTELLO
 561-805-6733
 [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2018-10-30 Cont ID  
Sent By gjohnson Date 2018-10-30 Time 09:16 Rev Time 0.00
Received By gjohnson Date 2018-10-30 Time 09:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2018-10-16 Cont ID  
Sent By gjohnson Date 2018-10-16 Time 09:30 Rev Time 0.00
Received By gjohnson Date 2018-10-16 Time 07:28 Sent To  
Notes
2018-10-16 09:49:493RD REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE SANITARY IISOMETRIC FOR THE ADDITION IS MISSING
 FROM A-5 PLEASE PROVIDE SANITARY ISOMETRIC DRAWINGS FOR
 ALL NEW PLUMBING WORK. PER WPB AMEND TO FBC
 107.3.5.3(13)
  
 2. PREVIOUS COMMENT THE KITCHEN SINK IS LABELED AS A
 BAR ON THE SANITARY SOMETRIC FOR THE ADDITION AND THE
 BREAKFAST BAR SINK IS MISSING PLEASE CORRECT THESE
 DEFICIENCY'S BEFORE RESUBMITTING. PER WPB AMEND TO FBC
 107.3.5.3(13)
  
 3. THE SANITARY ISOMETRIC DRAWING FOR THE GUEST HOUSE
 IS MISSING THE BRANCH FOR THE 3RD LAUNDRY ROOM BETWEEN
 THE EXERCISE ROOM AND EXISTING HOUSE PLEASE CLARIFY.
 PER WPB AMEND TO FBC 107.3.5.3(13)
  
 4. PLEASE LABEL THE WATER HEATER FOR THE NEW GUEST
 HOUSE AND ADDITION ON EXISTING HOUSE. PER WPB AMEND TO
 FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-08-30 Cont ID  
Sent By shill Date 2018-08-30 Time 16:00 Rev Time 0.00
Received By jesmith Date 2018-08-30 Time 16:00 Sent To  
Notes
2018-08-30 16:01:51PERMIT 18050348
  
 2ND REVIEW: FBC 2017 6TH EDITION
 DENIED
  
 PLUMBING REVIEW
  
 1. PLAN SHEET A-5; ADDITION PLUMBING RISER DIAGRAM
 NOTATES BAR (BAR SK) AT LOCATION THAT IS INDICATED ON
 A-1 ADD TO BE THE KITCHEN SINK. PLEASE CLARIFY.
 2. SCOPE OF WORK FOR ADDITION AND GUEST HOUSE PLUMBING
 CALLS FOR SUPPLY AND INSTALLATION OF TANKLESS GAS WATER
 HEATERS. LOCATE ON THE PLANS.
 3. PLAN SHEET A-5 ADDITION PLUMBING RISER DIAGRAM;
 PROVIDE SIZE ON FIXTURE BRANCH TO LAUNDRY FIXTURES
 4. THERE IS NO GAS INDICATED ON THE PLANS.
  A. A GAS SUB PERMIT WILL BE REQUIRED.
  B. SPECS FOR UNIT WILL BE REQUIRED.
  C. CALCULATIONS AND PIPING TYPE/MATERIAL FOR PIPING
 WILL BE REQUIRED.
  D. GAS PIPING DIAGRAM WILL BE REQUIRED TO INCLUDE
 DEVELOPED LENGTHS WILL BE REQUIRED.
  E. COMBUSTION AIR AND EXHAUST VENT AND ROUTING OF SAME
 WILL BE REQUIRED FOR GAS WATER HEATERS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-06-12 Cont ID  
Sent By gjohnson Date 2018-06-12 Time 16:25 Rev Time 0.00
Received By gjohnson Date 2018-06-12 Time 15:15 Sent To  
Notes
2018-06-12 16:35:131ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. A-5 THE BREAKFAST BAR IS MISSING FROM THE
 ADDITION SANITARY ISOMETRIC PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.3.5.3(12)
  
 2. PLEASE SHOW LOCATION OF WATER TYPE AND SIZE. PER WPB
 AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2018-10-02 Cont ID  
Sent By dbattles Date 2018-10-02 Time 09:55 Rev Time 0.00
Received By dbattles Date 2018-10-02 Time 09:55 Sent To  
Notes
2018-10-02 09:56:1510/4/18 CUSTOMER REQUESTED DEFERAL AND R-STOP IS
 CHANGED TO "N" STATUS TO INDICATE THAT ROOFER WILL
 PROVIDE SUBMITTAL UNDER ROOFING SUB PERMIT.
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718

Review Stop Z ZONING
Rev No 4 Status P Date   Cont ID  
Sent By   Date 2018-10-26 Time   Rev Time 0.00
Received By pgreilic Date 2018-10-26 Time 15:01 Sent To  
Notes
2018-10-26 15:02:01PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2018-09-20 Time   Rev Time 0.00
Received By pgreilic Date 2018-09-18 Time 11:09 Sent To  
Notes
2018-09-20 10:45:461.) LANDSCAPE PERMIT REQUIRED
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2018-08-09 Time   Rev Time 0.00
Received By pgreilic Date 2018-08-07 Time 12:05 Sent To  
Notes
2018-08-09 09:23:471.) SEC. 94-304 (B) ACCESSORY STRUCTURES IN RESIDENTIAL
 DISTRICTS. (1) MAXIMUM SQUARE FOOTAGE. THE TOTAL FLOOR
 AREA OF ALL ROOFED ACCESSORY BUILDINGS ON A PROPERTY
 SHALL NOT EXCEED 75 PERCENT OF THE GROSS FLOOR AREA OF
 THE PRIMARY STRUCTURE WITH A MAXIMUM FLOOR AREA OF
 1,000 SQUARE FEET.
 2.) SEPARATE PERMIT REQUIRED FOR DRIVEWAY, HOWEVER,
 ONLY ONE DRIVEWAY ACCESS POINT PERMITTED WITH A MAX OF
 20. FT. AT OPENING OR CIRCULAR DRIVEWAY CONFIGURATION
 3.) 94-482 (A) LOCATION AND SURFACE. REQUIRED
 OFF-STREET PARKING SPACES FOR LESS THAN THREE
 RESIDENTIAL DWELLING UNITS SHALL BE PROVIDED ON THE
 PROPERTY ON WHICH THE UNITS ARE LOCATED. REQUIRED
 PARKING MAY BE LOCATED IN A FRONT YARD; HOWEVER, THE
 LESSER OF 1,000 SQUARE FEET OR 75 PERCENT OF THE FRONT
 YARD AREA SHALL BE LANDSCAPED WITH LIVING PLANT
 MATERIAL (SUCH AS GRASS, GROUND COVER, SHRUBS, HEDGES,
 VINES OR TREES).
 4.) LANDSCAPE PERMIT REQUIRED
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By PG Date 2018-05-21 Time   Rev Time 0.00
Received By pgreilic Date 2018-05-18 Time 14:21 Sent To  
Notes
2018-07-05 16:28:51SUBMIT LANDSCAPE PERMIT SHOWING MEETS CURRENT LANDSCAP
 CODE REQUIREMENTS.
2018-05-21 14:22:101.) LABEL ALL SETBACKS OF PROPOSED ADDITION AND GUEST
 HOUSE
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]