Plan Review Details - Permit 18050330
Plan Review Stops For Permit 18050330
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-08-11 Cont ID  
Sent By shill Date 2018-08-11 Time 17:26 Rev Time 0.00
Received By shill Date 2018-08-11 Time 17:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-05-27 Cont ID  
Sent By shill Date 2018-05-27 Time 20:09 Rev Time 0.00
Received By shill Date 2018-05-27 Time 20:03 Sent To  
Notes
2018-05-27 20:08:58****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED
 SETS OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 2. A3, ROOMS 913, 915, 920, 921 DO NOT APPEAR TO HAVE
 THE 18" MANEUVERING CLEARANCE, PULL SIDE, REQUIRED BY
 FBC A FIGURE 404.2.1(A), REVISE TO SHOW COMPLIANCE.
  
 3. FBC 107, PROVIDE DETAILAS FOR ACCESSIBILITY FOR THE
 TWO SPECIMEN ROOMS.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-07-27 Cont ID  
Sent By ppetty Date 2018-07-27 Time 10:39 Rev Time 0.00
Received By ppetty Date 2018-07-27 Time 10:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-05-22 Cont ID  
Sent By jpearson Date 2018-05-22 Time 13:41 Rev Time 0.00
Received By jpearson Date 2018-05-22 Time 12:15 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-07-12 Cont ID  
Sent By pleduc Date 2018-07-12 Time   Rev Time 0.00
Received By pleduc Date 2018-07-12 Time 13:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-05-16 Cont ID  
Sent By pleduc Date 2018-05-16 Time   Rev Time 0.00
Received By pleduc Date 2018-05-16 Time 09:21 Sent To  
Notes
2018-05-16 11:09:14THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND
 SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY
 CERTIFIED LIFE SAFETY CONTRACTORS.
  
  
  
 2) ANY AND ALL WORK ON THE FIRE ALARM AND FIRE
 SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP
 DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
  
  
 3) THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-11 Cont ID  
Sent By shill Date 2018-08-11 Time 17:26 Rev Time 0.00
Received By shill Date 2018-07-09 Time 14:26 Sent To  
Notes
2018-07-11 14:27:01B13

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-06 Cont ID  
Sent By gjohnson Date 2018-06-06 Time 13:50 Rev Time 0.00
Received By gjohnson Date 2018-05-08 Time 12:59 Sent To  
Notes
2018-05-09 12:59:20B20

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-08-04 Cont ID  
Sent By hmoser Date 2018-08-04 Time 10:19 Rev Time 0.00
Received By hmoser Date 2018-08-04 Time 10:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-05-17 Cont ID  
Sent By hmoser Date 2018-05-17 Time 13:45 Rev Time 0.00
Received By hmoser Date 2018-05-17 Time 13:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-08-10 Cont ID  
Sent By gjohnson Date 2018-08-10 Time 07:55 Rev Time 0.00
Received By gjohnson Date 2018-08-10 Time 07:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-06-06 Cont ID  
Sent By gjohnson Date 2018-06-06 Time 13:29 Rev Time 0.00
Received By gjohnson Date 2018-06-06 Time 13:29 Sent To  
Notes
2018-06-06 13:50:161ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE SINKS IN ROOMS 902 AND 915 SHALL COMPLY WITH FBC
 ACC 212.3 , 606.2, 606.3
  
 2. PLEASE PROVIDE COST BREAK DOWN TO SHOW COMPLIANCE
 WITH FBC ACC
 202.4.1 DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.
 WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH
 OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE
 ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE
 ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE
 FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 3. SHT. A-1 UNDER PLUMBING FIXTURE IT LIST A DRINKING
 FOUNTAIN BUT NONE IS SHOWN ON THE PLAN PLEASE CLARIFY.
 PER WPB AMEND TO FBC 107.2.1
  
 4. SHT. A-3 PLAN NOTE 02 LIST A HI LO WATER FOUNTAIN
 BUT NONE IS SHOWN ON THE PLAN PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 5. IS THERE AN EXISTING HOT WATER RECIRCULATION LINE.
 THE HOT WATER ON THE NEW SINKS SHALL COMPLY WITH FBC PL
 607.2
  
 6. EACH DROP ON THE WATER SYSTEM SHALL HAVE A SHUT OFF
 VALVE WITH ACCESS TO IT. PER FBC PL 606.1 (5)
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  