Plan Review Details - Permit 18050326
Plan Review Stops For Permit 18050326
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-08-20 Cont ID  
Sent By dbattles Date 2018-08-20 Time 09:40 Rev Time 0.00
Received By dbattles Date 2018-08-20 Time 09:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-07-20 Cont ID  
Sent By dbattles Date 2018-07-20 Time 07:43 Rev Time 0.00
Received By dbattles Date 2018-07-20 Time 07:43 Sent To  
Notes
2018-07-20 07:46:34****CORRECTIONS****
 W.P.B. PERMIT: 1850326
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC EB = FBC EXISTING BUILDING
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1.[FBC 107.2.1]ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. THE SIGNATURE PROVIDED NEEDS TO HAVE THE NAME
 OF PERSON PRINTED AS WELL.
  
 2.[FBC R702.3.5]PROVIDE DETAIL OF NEW WALL. SPACING OF
 STUDS, THICKNESS OF DRYWALL OR OTHER WALL COVERING IF
 APPLICABLE.
  
 3.[FBC R702.4.2]PROVIDE TILE BACKER THAT COMPLIES WITH
 TABLE R702.4.2
  
 4.[FBC R308.1]SHOWER ENCLOSURES TO COMPLY WITH SAFETY
 GLASS STANDARDS IN FBC R308.1
  
 NOTE:
 THE PLANS STATE THAT A SEPARATE PERMIT WILL BE ACQUIRED
 FOR WINDOWS AND DOORS.
 I WOULD SUGGEST YOU DO THE WINDOWS AND DOORS AS A
 REVISION TO THIS PERMIT.
 IT WILL BE MORE COST EFFECTIVE SINCE YOU PAY ONLY FLAT
 RATE PER SHEET ADDED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-06-14 Cont ID  
Sent By cthroop Date 2018-06-14 Time 13:30 Rev Time 0.00
Received By cthroop Date 2018-06-13 Time 17:18 Sent To  
Notes
2018-06-14 13:36:53BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE TITLE BLOCK ON COVER PAGE. INCLUDE GOVERNING
 CODES AND LEVEL OF ALTERATION (1,2 OR 3).
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 2. PROVIDE DETAIL FOR OPENING OF EXTERIOR WALL FOR
 FRENCH DOORS.
  
 3. PROVIDE PRODUCT APPROVALS FOR PROPOSED DOORS.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE DOOR SUBMITTALS.
  
 4. VERIFY WALL TO BE REMOVED BETWEEN FAMILY ROOM AND
 FLORIDA ROOM IS NON LOAD BEARING.
  
 5. PROVIDE DEMENSIONS ON PLANS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-07-24 Cont ID  
Sent By ppetty Date 2018-07-24 Time 09:55 Rev Time 0.00
Received By ppetty Date 2018-07-24 Time 09:51 Sent To  
Notes
2018-07-24 09:55:10CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. OK
 2. OK
 3. OK
 4. OK
 6. OK
 7. OK
 8. OK
 9. OK
 10. OK
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER
 561-805-6742
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-08-15 Cont ID  
Sent By ppetty Date 2018-08-15 Time 08:27 Rev Time 0.00
Received By ppetty Date 2018-08-15 Time 08:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-05-23 Cont ID  
Sent By jpearson Date 2018-05-23 Time 16:47 Rev Time 0.00
Received By jpearson Date 2018-05-23 Time 07:54 Sent To  
Notes
2018-05-23 16:47:47CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE SMOKE ALARMS IN EACH LOCATION REQUIRED PER
 CODE. SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE
 EXISTING OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC
 RE R314.3, R315.1; WPB FBC 107.2.1
 2. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. PROVIDE
 CORRECTION. NEC 210.12; FBC RE E3902.16
 3. RECEPTACLES IN KITCHEN REQUIRE GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.6
 4. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 5. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP
 CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN.
 PROVIDE CORRECTION. NEC 210.11(C)(3), 210.52(D); FBC RE
 E3703.4, E3901.6
 6. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14
 7. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1
 8. LIGHTS IN CLOSETS APPEAR TO BE STANDARD RECESS
 LIGHTS. PER CODE: LIGHTING WITH OPEN OR PARTIALLY
 ENCLOSED LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS
 SHALL NOT BE PERMITTED IN CLOTHES CLOSETS. PROVIDE
 CORRECTION. NEC 410.16; FBC RE E4003.12
 9. RISER DIAGRAM SHOWS 1/0 CONDUCTORS FEEDING A 200 AMP
 PANEL. 1/0 WIRE IS NOT RATED FOR 200 AMPS. PROVIDE
 CORRECTION. NEC 310.15(B)(7) AND (B)(16); FBC RE
 E3603.1, E3705.1
 10. ELECTRICAL PANEL SCHEDULE SHOWS A 4KW LOAD FOR
 WATER HEATER, BUT THE PLUMBING PLAN SHOWS TWO TANKLESS
 WATER HEATERS. PROVIDE CLARIFICATION AND/OR CORRECTION
 AS NEEDED. NEC 220; FBC RE 3602.2; WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-08-20 Cont ID  
Sent By dbattles Date 2018-08-20 Time 09:40 Rev Time 0.00
Received By dbattles Date 2018-08-16 Time 15:39 Sent To  
Notes
2018-08-17 15:40:03RESUB ROUTED TO DBATTLES

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-15 Cont ID  
Sent By gjohnson Date 2018-08-15 Time 09:43 Rev Time 0.00
Received By gjohnson Date 2018-06-27 Time 14:58 Sent To  
Notes
2018-06-28 14:58:43R25

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-14 Cont ID  
Sent By cthroop Date 2018-06-14 Time 13:36 Rev Time 0.00
Received By cthroop Date 2018-05-08 Time 11:09 Sent To I
Notes
2018-05-09 11:09:54R08

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-07-16 Cont ID  
Sent By cmontell Date 2018-07-16 Time 14:56 Rev Time 0.00
Received By cmontell Date 2018-07-16 Time 15:00 Sent To  
Notes
2018-07-16 15:00:21NO MECHANICAL WORK TO BE DONE SEE SCOPE OF WORK
  
 CHRIS MONTELLO
 561-805-6733
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2018-05-22 Cont ID  
Sent By cmontell Date 2018-05-22 Time 14:56 Rev Time 0.00
Received By cmontell Date 2018-05-22 Time 14:54 Sent To  
Notes
2018-05-22 14:55:47NO MECHANICAL WORK TO BE DONE SEE SCOPE OF WORK
  
 CHRIS MONTELLO
 561-805-6733
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-08-15 Cont ID  
Sent By gjohnson Date 2018-08-15 Time 09:43 Rev Time 0.00
Received By gjohnson Date 2018-08-15 Time 09:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-06-06 Cont ID  
Sent By thunt Date 2018-06-06 Time 05:54 Rev Time 0.00
Received By thunt Date 2018-06-06 Time 05:54 Sent To  
Notes
2018-06-06 05:56:3406/06/2018 1ST PLUMBING REVIEW**DENIED**
  
 1) PROVIDE LEVEL OF ALTERATION AND TOTAL PERCENT OF
 WORK AREA. FBC R-EXISTING 501.2
  
 2) PROVIDE THE SPECIFICATIONS/ INSTALLATION MANUALS
 ALONG WITH FLOW CHARTS FOR THE TANKLESS WATER HEATERS.
 FBC 107.2.1
  
 3) PROVIDE AN EXISTING FLOOR PLAN LAY OUT. FBC 107.2.1
  
 4) PROVIDE WALL DIMENSION FOR EACH ROOM TO SHOW THE
 MINIMAL CLEARANCES FOR THE PLUMBING FIXTURES WILL
 COMPLY. FBC R P2705.1
  
 5) IS THE COPPER PIPING SHOWN AS EXISTING IN THE LIVING
 ROOM THE ONLY EXISTING WATER PIPING THAT WILL BE REUSED
 IN THE NEW SYSTEM? FBC 107.2.1
  
 6) YOUR SANITARY ISOMETRIC IS SHOWING AS A WASTE & VENT
 IN BATH #1 AND GUEST BATH. TOILETS AND GARBAGE
 DISPOSALS ARE NOT PERMITTED TO DISCHARGE INTO THIS TYPE
 OF SYSTEM PER FBC R P3111.1. PLEASE SHOW HOW YOU INTENT
 TO VENT THESE TWO BATHROOM GROUPS.
  
  
 TIM HUNT
  PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
  CITY OF WEST PALM BEACH DEVELOPMENT SERVICES
 DEPARTMENT
  BUILDING DIVISION
  561-805-6695
  [email protected]
  