Plan Review Details - Permit 18050313
Plan Review Stops For Permit 18050313
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-08-30 Cont ID  
Sent By dbattles Date 2018-08-30 Time 11:38 Rev Time 0.00
Received By dbattles Date 2018-08-30 Time 11:37 Sent To  
Notes
2018-08-30 11:39:22DB SPOKE TO KAHN ON 8/30/18 AND AGREED TO ADJUST
 SPACING FROM 10" TO 7.5 PER ADJUSTMENT FACTOR FOR ALL
 POINT ANCHORS.
 SHEETS MARKED UP IN RED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-07-30 Cont ID  
Sent By dbattles Date 2018-07-30 Time 14:24 Rev Time 0.00
Received By dbattles Date 2018-07-30 Time 14:24 Sent To  
Notes
2018-07-30 14:25:05****CORRECTIONS****
 W.P.B. PERMIT: 18050313
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC EB = FBC EXISTING BUILDING
 FBC R = FBC RESIDENTIAL
  
 1. OK.
  
 2. WHEN COMPLETING THE INSTALLATION SCHEDULE, PLEASE
 NOTE PAGE 13 OF 20, FACTORS APPLY DEPENDING ON
 SUBSTRATE, EDGE DISTANCE AND FASTENER. FOR FASTENER, IF
 USING TAPCON, BE SPECIFIC AS TO WHICH TAPCON (TAPCON
 W/ADVANCED THREADFORM TECHNOLOGY REQUIRES A .9 FACTOR).
 2.1. THE EDGE DISTANCE DOESN'T MEET THE TABLE ON PAGE
 13 OF 20.
 IF YOU USE ALL POINT ANCHORS AS SPECIFIED THAN YOUR
 MINIMUM EDGE DISTANCE WOULD BE 3.5" AND YOU WOULD USE
 FACTOR .78*10(ANCHOR SPACING) FOR A NEW ANCHOR SPACING
 OF 7.8".
 PLEASE LOOK AT THIS TABLE EDGE DISTANCE VS. SPACING
 SCHEDULE FOR ANCHORS AND CHOOSE THE ANCHOR AND SPACING
 THAT WORKS BEST FOR YOUR PROJECT.
 CALL IF ANY QUESTIONS ABOUT THE EDGE SPACING.
 DYLAN BATTLES 561-805-6718.
  
 ALSO, THE I.D. NO. 4&5 FROM SALES SHEET DON'T MATCH THE
 SUBMITTAL SHEET OPENING 4&5. I HAVE NO COMMENT ON THAT
 BECAUSE IT WON'T CHANGE SPACING VALUES, BUT YOU MAY
 WANT TO VERIFY THE SIZE BEFORE FABRICATION.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-06-06 Cont ID  
Sent By shill Date 2018-06-06 Time 18:05 Rev Time 0.00
Received By shill Date 2018-06-06 Time 18:05 Sent To  
Notes
2018-06-06 18:16:14****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 SEE COMMENT FROM PREVIOUS LIST. THE DOCUMENT PROVIDED
 DOES NOT INCLUDE ALL OF THE INFORMATION REQUIRED TO
 DETERMINE COMPLIANCE.
  
 1. FBC R 301, COMPLETE THE "SCHEDULE FOR INSTALLATION
 OF OPENING PROTECTIVE DEVICES" OR PROVIDE ALL
 INFORMATION REQUIRED IN ANOTHER FORMAT (SUCH AS EXCEL
 SPREADSHEET):
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS?PAGE=2
  
 2. WHEN COMPLETING THE INSTALLATION SCHEDULE, PLEASE
 NOTE PAGE 13 OF 20, FACTORS APPLY DEPENDING ON
 SUBSTRATE, EDGE DISTANCE AND FASTENER. PLEASE CONTACT
 ME IF YOU NEED ASSISTANCE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-05-09 Cont ID  
Sent By shill Date 2018-05-09 Time 17:57 Rev Time 0.00
Received By shill Date 2018-05-09 Time 17:57 Sent To  
Notes
2018-05-09 17:58:21****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC R 301, COMPLETE THE "SCHEDULE FOR INSTALLATION
 OF OPENING PROTECTIVE DEVICES" OR PROVIDE ALL
 INFORMATION REQUIRED IN ANOTHER FORMAT (SUCH AS EXCEL
 SPREADSHEET):
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS?PAGE=2
  
 2. WHEN COMPLETING THE INSTALLATION SCHEDULE, PLEASE
 NOTE PAGE 13 OF 20, FACTORS APPLY DEPENDING ON
 SUBSTRATE, EDGE DISTANCE AND FASTENER. PLEASE CONTACT
 ME IF YOU NEED ASSISTANCE.
  
 3. REVISE PLAN TO SHOW MEANS OF ESCAPE REQUIRED BY FBC
 R 310.4; INCLUDE ROOM DESIGNATION.
  
 PLAN APPEARS TO SHOW FRONT DOOR AS EGRESS, COVERED WITH
 A SHUTTER. IS THIS DOOR INSWING?

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-08-30 Cont ID  
Sent By dbattles Date 2018-08-30 Time 11:39 Rev Time 0.00
Received By dbattles Date 2018-08-28 Time 14:41 Sent To  
Notes
2018-08-29 14:42:08RESUB ROUTED TO DBATTLES

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-07-30 Cont ID  
Sent By dbattles Date 2018-07-30 Time 14:26 Rev Time 0.00
Received By dbattles Date 2018-07-18 Time 15:05 Sent To  
Notes
2018-07-30 10:42:597/30 TO DB DESK
  
2018-07-19 15:05:13RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-06-06 Cont ID  
Sent By shill Date 2018-06-06 Time 18:16 Rev Time 0.00
Received By shill Date 2018-05-29 Time 15:37 Sent To  
Notes
2018-05-30 15:37:17RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-09 Cont ID  
Sent By shill Date 2018-05-09 Time 17:58 Rev Time 0.00
Received By shill Date 2018-05-07 Time 10:06 Sent To  
Notes
2018-05-08 10:07:01BLDG <5K