Plan Review Details - Permit 18050274
Plan Review Stops For Permit 18050274
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-05-27 Cont ID  
Sent By shill Date 2018-05-27 Time 13:24 Rev Time 0.00
Received By shill Date 2018-05-27 Time 13:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-05-10 Cont ID  
Sent By shill Date 2018-05-10 Time 07:22 Rev Time 0.00
Received By shill Date 2018-05-10 Time 07:22 Sent To  
Notes
2018-05-10 07:35:05****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC B 1609, ENGINEERING INDICATES OPENING 1 AS ZONE
 4, BUT THE FLOOR PLAN SHOWS THIS AS ZONE 5. PLEASE
 CORRELATE, AND IF IN ZONE 4, PROVIDE THE DIMENSION OF
 OPENING FROM THE CORNERS, AS WELL AS ZONE 5 DIMENSION.
 PRODUCT PROPOSED APPEARS COMPLIANT FOR ZONE 5, BUT NOT
 ENTIRELY CLEAR AS ZONE 5 PRESSURES WERE NOT PROVIDED.
  
 2. SHEET 4, THANK YOU FOR INDICATING FASTENING OPTIONS
 PROPOSED. HOWEVER, THE POSITIVE DESIGN PRESSURES WERE
 CROSSED OFF; THEY APPEAR TO COMPLY, NOT CLEAR WHY THEY
 WERE CROSSED OFF, PLEASE PROVIDE EXPLANATION.
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-05-27 Cont ID  
Sent By shill Date 2018-05-27 Time 13:24 Rev Time 0.00
Received By shill Date 2018-05-16 Time 11:14 Sent To  
Notes
2018-05-16 11:14:35RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-10 Cont ID  
Sent By shill Date 2018-05-10 Time 07:35 Rev Time 0.00
Received By shill Date 2018-05-07 Time 09:47 Sent To  
Notes
2018-05-08 09:47:25BLDG MISC 1