Plan Review Details - Permit 18050255
Plan Review Stops For Permit 18050255
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-09-13 Cont ID  
Sent By cthroop Date 2018-09-13 Time 15:08 Rev Time 0.00
Received By cthroop Date 2018-09-13 Time 14:53 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-08-14 Cont ID  
Sent By cthroop Date 2018-08-14 Time 12:20 Rev Time 0.00
Received By cthroop Date 2018-08-14 Time 11:18 Sent To I
Notes
2018-08-14 12:21:12INCREASED VALUE TO $75,000.00 CT

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-05-12 Cont ID  
Sent By cthroop Date 2018-05-12 Time 10:36 Rev Time 0.00
Received By cthroop Date 2018-05-12 Time 10:34 Sent To  
Notes
2018-05-12 10:37:44BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. VALUE APPEARS LOW FOR PROPOSED SCOPE OF WORK.
 THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE.
 YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE
 OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
  
 CITY OF WPB CHPT. 1 ? VALUE
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2018-09-13 Cont ID  
Sent By jleahy Date 2018-09-13 Time 15:28 Rev Time 0.00
Received By jleahy Date 2018-09-13 Time 15:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2018-08-28 Cont ID  
Sent By jleahy Date 2018-08-28 Time 10:18 Rev Time 0.00
Received By jleahy Date 2018-08-28 Time 10:18 Sent To  
Notes
2018-08-28 10:24:31ONLY ONE COMPLETE SET OF PLANS DATED 8/23/18 NEED TYWO
 SETS AS A MINIMUM.
  
 VALUE OF WORK IS TO INCLUDE THE COST OF THE MATERIAL,
 GENERATOR AND TRANSFER SWITCH.
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-08-14 Cont ID  
Sent By jleahy Date 2018-08-14 Time 10:21 Rev Time 0.00
Received By jleahy Date 2018-08-14 Time 10:21 Sent To B
Notes
2018-08-14 10:25:37FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 COMMENT #1 PANEL "G" NOT DONE NO AIC RATING SHOWN
  
 COMMENT #2 NO CALCLUATION SHOWN ON DRAWINGS FAULT
 CURRENT CALC NO SHOWN
  
 COMMENT #9 NO SIZE ON PULL BOX
  
 COMMENT #10 NO GROUNDING DETAIL SHOWN
  
 COMMENT #11 NO CONTRACT SUBMITTED, PERMIT VALUE WILL BE
 BASED ON $75,000.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-05-10 Cont ID  
Sent By jpearson Date 2018-05-10 Time 11:27 Rev Time 0.00
Received By jpearson Date 2018-05-10 Time 11:27 Sent To FIRE
Notes
2018-05-10 11:26:57CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL.
 NEC 110.3, 110.9
 2. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 3. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 4. PROVIDE RATED VOLTAGE OF SYSTEM ON PLAN. WPB FBC
 107.2.1; NEC 110.4
 5. PROVIDE LOAD CALCULATION FOR SERVICE TO CONFIRM
 CAPACITY OF GENERATOR IS ADEQUATE. NEC 215.2, 220,
 408.30, 702.4
 6. PROVIDE SIGNS FOR GENERATOR IN COMPLIANCE WITH NEC
 702.6.
 7. PROVIDE EQUIPMENT GROUNDING CONDUCTOR IN CONDUITS
 FROM TRANSFER SWITCH TO INTERIOR PANEL. INCLUDE
 DIRECTION TO SEPARATE GROUNDS AND NEUTRALS AT THE
 ORIGINAL MAIN, WHICH WILL NOW BE A SUB-PANEL. NEC
 250.122
 8. PROVIDE PANEL SCHEDULE FOR ANY NEW CIRCUITS THAT
 WILL BE ADDED FOR GENERATOR LIGHTING, BLOCK HEATER,
 ETC. WPB FBC 107.2.1; NEC 215.2, 408.4
 9. PULL BOX MUST BE SIZED PER NEC 314.28(A)(2). PROVIDE
 CORRECTION.
 10. PROVIDE DETAIL OF GROUNDING ELECTRODE SYSTEM AND
 ATTACHMENT TO MAIN SERVICE, WHICH WILL NOW BE THE
 TRANSFER SWITCH. NEC 250.50, 250.53, 250.64
 11. VALUE SPECIFIED ON PERMIT APPLICATION APPEARS LOW.
 PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND VALUE OF
 WORK, TO INCLUDE ALL MATERIALS AND LABOR. FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-09-13 Cont ID  
Sent By skennedy Date 2018-09-13 Time 15:04 Rev Time 0.00
Received By skennedy Date 2018-09-13 Time 15:04 Sent To  
Notes
2018-09-13 15:05:04PER SCALDERON

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-07-31 Cont ID  
Sent By scaldero Date 2018-07-31 Time 13:56 Rev Time 0.00
Received By scaldero Date 2018-07-31 Time 13:56 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-05-11 Cont ID  
Sent By scaldero Date 2018-05-11 Time 10:43 Rev Time 0.00
Received By scaldero Date 2018-05-11 Time 10:40 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-09-13 Cont ID  
Sent By skennedy Date 2018-09-13 Time 15:36 Rev Time 0.00
Received By skennedy Date 2018-08-29 Time 15:06 Sent To  
Notes
2018-08-30 15:06:32RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-08-28 Cont ID  
Sent By jleahy Date 2018-08-28 Time 10:24 Rev Time 0.00
Received By jleahy Date 2018-08-23 Time 11:51 Sent To  
Notes
2018-08-27 11:51:28RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-14 Cont ID  
Sent By cthroop Date 2018-08-14 Time 12:20 Rev Time 0.00
Received By cthroop Date 2018-07-20 Time 09:39 Sent To  
Notes
2018-07-24 09:39:11RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-12 Cont ID  
Sent By cthroop Date 2018-05-12 Time 10:37 Rev Time 0.00
Received By cthroop Date 2018-05-04 Time 13:09 Sent To I
Notes
2018-05-07 13:09:27ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 3 Status P Date 2018-09-06 Cont ID  
Sent By mcruz Date 2018-09-06 Time 10:28 Rev Time 0.00
Received By mcruz Date 2018-09-06 Time 10:26 Sent To FIRE
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2018-07-27 Cont ID  
Sent By mcruz Date 2018-07-27 Time 09:05 Rev Time 0.00
Received By mcruz Date 2018-07-27 Time 09:03 Sent To FIRE
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By M. Cruz Date 2018-05-09 Time   Rev Time  
Received By   Date 2018-05-09 Time   Sent To B
Notes
***NONE***