Plan Review Details - Permit 18050248
Plan Review Stops For Permit 18050248
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-07-30 Cont ID  
Sent By shill Date 2018-07-30 Time 09:11 Rev Time 0.00
Received By shill Date 2018-07-30 Time 09:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-06-30 Cont ID  
Sent By shill Date 2018-06-30 Time 17:14 Rev Time 0.00
Received By shill Date 2018-06-30 Time 17:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-05-27 Cont ID  
Sent By shill Date 2018-05-27 Time 19:42 Rev Time 0.00
Received By shill Date 2018-05-27 Time 19:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-05-21 Cont ID  
Sent By jpearson Date 2018-05-21 Time 12:33 Rev Time 0.00
Received By jpearson Date 2018-05-21 Time 12:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-07-25 Cont ID  
Sent By scaldero Date 2018-07-25 Time 10:46 Rev Time 0.00
Received By scaldero Date 2018-07-25 Time 10:46 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-06-27 Cont ID  
Sent By scaldero Date 2018-06-27 Time 11:01 Rev Time 0.00
Received By scaldero Date 2018-06-27 Time 11:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-05-11 Cont ID  
Sent By scaldero Date 2018-05-11 Time 11:34 Rev Time 0.00
Received By scaldero Date 2018-05-11 Time 11:31 Sent To  
Notes
2018-05-11 11:34:25PERMIT # 18050248
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED WITH COMMENTS:
  
 1) FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected]) OR IN WRITING
 (FAX: 561-804-4774) AND APPROVED BY THE OFFICE OF THE
 FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 2) PROVIDE 44 INCH WIDE STRIPING (DEMARCATION) IN BACK
 OF HOUSE TO ENSURE EGRESS PATH REQUIREMENTS ARE
 MAINTAINED AT ALL TIMES.
  
 3) PROVIDE A K-TYPE PORTABLE FIRE EXTINGUISHER AND
 ASSOCIATED SIGNAGE IN KITCHEN AREA.
  
 4) KITCHEN HOOD SUPPRESSION SYSTEM SHALL BE TIED INTO
 THE BUILDING FIRE ALARM SYSTEM TO INITIATE A GENERAL
 FIRE ALARM CONDITION.
  
 5) DEEP FAT FRYERS SHALL BE EQUIPPED WITH A SEPARATE
 HIGH-LIMIT CONTROL IN ADDITION TO THE ADJUSTABLE
 THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN THE FAT
 TEMPERATURE REACHES 475F DEGREES AT 1-INCH BELOW THE
 SURFACE.
  
 6) COOKING OPERATIONS PRODUCING SMOKE OR GREASE-LADEN
 VAPORS SHALL BE PROTECTED WITH A CLASS I MECHANICAL
 EXHAUST HOOD EQUIPPED WITH AN AUTOMATIC WET-CHEMICAL
 FIRE SUPPRESSION SYSTEM.
  
 7) SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO
 THE FIRE ALARM AND SPRINKLER SYSTEM.
  
  
 SUE ELLEN CALDERON
 ASST. FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2018-08-02 Cont ID  
Sent By gjohnson Date 2018-08-02 Time 15:10 Rev Time 0.00
Received By gjohnson Date 2018-08-02 Time 15:10 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-07-06 Cont ID  
Sent By gjohnson Date 2018-07-06 Time 07:14 Rev Time 0.00
Received By gjohnson Date 2018-07-06 Time 07:14 Sent To  
Notes
2018-07-06 07:24:371ST REVIEW: FBC 2017 6TH EDITION
  
 GAS COMMENTS: IT APPEARS THAT NONE OF THE GAS COMMENTS
 WERE ADDRESSED AND NO RESPONSE LETTER A RESPONSE LETTER
 WILL HELP EXPEDITE THE REVIEW PROCESS.
  
 1. PLEASE SHOW THE 1" BRANCH FOR NEW TANKLESS WATER
 HEATER ON THE RISER DIAGRAM WITH THE BTU LOAD. PER WPB
 AMEND TO FBC (9)
  
 2. DRIP LEGS REQUIRED PLEASE SHOW THEM ON THE RISER .
 PER FBC FG 408.4
  
 3. PLEASE SHOW THE LENGTH OF EACH CUT SECTION OF PIPE.
 PER WPB AMEND TO FBC 107.2.1
  
 4. PROVIDE THE TOTAL LENGTH FROM THE METER TO THE STEP
 DOWN REGULATOR 2PSI TO .5PSI SHOW ON THE RISER ALSO.
 PER WPB AMEND TO FBC 107.2.1
  
 5. SHT. P2.1 THE NOTE FOR THE GAS IS STATING A SYSTEM
 OF LESS THAN 2PSI .5 PRESSURE DROP BUT IT LIST TABLE
 402.4(5) WHICH IS 2PSI PLEASE CLARIFY. PER WPB AMEND TO
 FBC 107.2.1
  
 6. SHOW SIZE ON PIPING FROM METER TO FIRST REGULATOR.
 PER WPB AMEND TO FBC 107.2.1
  
 7. SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 8. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC-FUEL GAS CODE SEC.304.1, 614.6 (CLOTHES DRYERS) OR
 2017 FBC-RES. SEC. G 2407.1 AND G2439.4 (CLOTHES
 DRYERS).
  
 NEW COMMENT
  
 1. SHT. P2.1 UNDER WATER PLAN KEYED NOTES #4 THE
 CONTRACTOR SHALL RUN A NEW GAS LINE TO A HVAC EQUIPMENT
 ON THE ROOF PLEASE SHOW ON THE GAS ISOMETRIC DRAWING
 AND INCLUDE IN TOTAL BTU LOAD. PER WPB AMEND TO FBC
 107.2.1
  
 2. PROVIDE ANY EXISTING BTU LOAD ON EXISTING GAS SYSTEM
 SHOW ON GAS ISO. PER WPB AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-06-05 Cont ID  
Sent By gjohnson Date 2018-06-05 Time 14:53 Rev Time 0.00
Received By gjohnson Date 2018-06-05 Time 14:52 Sent To  
Notes
2018-06-05 16:20:451ST REVIEW: FBC 2017 6TH EDITION
  
 GAS COMMENTS:
  
 1. PLEASE SHOW THE 1" BRANCH FOR NEW TANKLESS WATER
 HEATER ON THE RISER DIAGRAM WITH THE BTU LOAD. PER WPB
 AMEND TO FBC (9)
  
 2. DRIP LEGS REQUIRED PLEASE SHOW THEM ON THE RISER .
 PER FBC FG 408.4
  
 3. PLEASE SHOW THE LENGTH OF EACH CUT SECTION OF PIPE.
 PER WPB AMEND TO FBC 107.2.1
  
 4. PROVIDE THE TOTAL LENGTH FROM THE METER TO THE STEP
 DOWN REGULATOR 2PSI TO .5PSI SHOW ON THE RISER ALSO.
 PER WPB AMEND TO FBC 107.2.1
  
 5. SHT. P2.1 THE NOTE FOR THE GAS IS STATING A SYSTEM
 OF LESS THAN 2PSI .5 PRESSURE DROPBUT IT LIST TABLE
 402.4(5) WHICH IS 2PSI PLEASE CLARIFY. PER WPB AMEND TO
 FBC 107.2.1
  
 6. SHOW SIZE ON PIPING FROM METER TO FIRST REGULATOR.
 PER WPB AMEND TO FBC 107.2.1
  
 7. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 8. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC-FUEL GAS CODE SEC.304.1, 614.6 (CLOTHES DRYERS) OR
 2017 FBC-RES. SEC. G 2407.1 AND G2439.4 (CLOTHES
 DRYERS).
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-08-02 Cont ID  
Sent By gjohnson Date 2018-08-02 Time 15:10 Rev Time 0.00
Received By gjohnson Date 2018-07-18 Time 15:10 Sent To  
Notes
2018-07-30 09:11:597/30 TO GJ DESK
  
2018-07-26 18:37:107/26 ON SH DESK
  
2018-07-19 15:10:52RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-16 Cont ID  
Sent By lmarchan Date 2018-07-16 Time 15:03 Rev Time 0.00
Received By lmarchan Date 2018-06-14 Time 09:22 Sent To  
Notes
2018-06-18 09:22:57B05

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-05 Cont ID  
Sent By gjohnson Date 2018-06-05 Time 16:20 Rev Time 0.00
Received By gjohnson Date 2018-05-04 Time 14:22 Sent To  
Notes
2018-05-07 14:22:17B02

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2018-07-12 Cont ID  
Sent By cmontell Date 2018-07-12 Time 12:48 Rev Time 0.00
Received By cmontell Date 2018-07-12 Time 12:48 Sent To  
Notes
2018-07-12 12:49:17HOOD PERMIT NEEDED
  
 CHRIS MONTELLO
 561-805-6733

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-05-17 Cont ID  
Sent By cmontell Date 2018-05-17 Time 14:15 Rev Time 0.00
Received By cmontell Date 2018-05-17 Time 13:27 Sent To  
Notes
2018-05-17 13:29:37NEED SEPRATE PERMIT, SEALED DRAWING AND PERMIT FOR HOOD
 PLAN NOT REVIEWED
  
 CHRIS MONTELLO
 561-805-6733

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-08-02 Cont ID  
Sent By gjohnson Date 2018-08-02 Time 15:10 Rev Time 0.00
Received By gjohnson Date 2018-08-02 Time 15:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-07-06 Cont ID  
Sent By gjohnson Date 2018-07-06 Time 07:08 Rev Time 0.00
Received By gjohnson Date 2018-07-05 Time 16:03 Sent To  
Notes
2018-07-06 07:13:252ND REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS: DOES NOT APPEAR THAT ANY OF THE
 PLUMBING COMMENTS WERE ADDRESSED AND THERE WAS NO
 RESPONSE LETTER, A RESPONSE LETTER WILL HELP EXPEDITE
 REVIEW PROCESS.
  
 1. PLEASE PROVIDE WATER ISOMETRIC FOR ALL NEW WATER
 PIPING. PER WPB AMEND TO FBC 107.3.5.1.3(13)
  
 2. PROVIDE MANUFACTURE SPECIFICATIONS FOR THE WATER
 FILTER AND CARBONATOR. PER WPB AMEND TO FBC 107.2.1
  
 3. A BACK FLOW IS REQUIRED FOR ICE MACHINE, WATER
 FILTER AND CARBINATOR, DRINK MACHINES AND COFFEE
 MAKERS. PER FBC PL 608.3 , 608.16.1 , 608.16.10
  
 4. TRAP PRIMERS ARE REQUIRED AT ALL NEW FLOOR DRAINS.
 PER FBC PL 1002.4.1
  
 NEW COMMENT:
  
 1. PROVIDE SANITARY ISOMETRIC FOR THE DROP IN HAND SINK
 4.55. PER WPB AMEND TO FBC 107.3.5.1.3(13)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-06-05 Cont ID  
Sent By gjohnson Date 2018-06-05 Time 14:36 Rev Time 0.00
Received By gjohnson Date 2018-06-04 Time 16:54 Sent To  
Notes
2018-06-05 14:52:471ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE WATER ISOMETRIC FOR ALL NEW WATER
 PIPING. PER WPB AMEND TO FBC 107.3.5.1.3(13)
  
 2. PROVIDE MANUFACTURE SPECIFICATIONS FOR THE WATER
 FILTER AND CARBONATOR. PER WPB AMEND TO FBC 107.2.1
  
 3. A BACK FLOW IS REQUIRED FOR ICE MACHINE, WATER
 FILTER AND CARBINATOR, DRINK MACHINES AND COFFEE
 MAKERS. PER FBC PL 608.3 , 608.16.1 , 608.16.10
  
 4. TRAP PRIMERS ARE REQUIRED AT ALL NEW FLOOR DRAINS.
 PER FBC PL 1002.4.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2018-05-15 Cont ID  
Sent By eschneid Date 2018-05-15 Time 12:09 Rev Time 0.25
Received By eschneid Date 2018-05-15 Time 12:09 Sent To  
Notes
***NONE***