Plan Review Details - Permit 18050247
Plan Review Stops For Permit 18050247
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-07-30 Cont ID  
Sent By shill Date 2018-07-30 Time 08:54 Rev Time 0.00
Received By shill Date 2018-07-30 Time 08:54 Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-06-30 Cont ID  
Sent By shill Date 2018-06-30 Time 17:08 Rev Time 0.00
Received By shill Date 2018-06-30 Time 17:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-05-27 Cont ID  
Sent By shill Date 2018-05-27 Time 19:49 Rev Time 0.00
Received By shill Date 2018-05-27 Time 19:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-05-21 Cont ID  
Sent By jpearson Date 2018-05-21 Time 12:51 Rev Time 0.00
Received By jpearson Date 2018-05-21 Time 12:08 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-07-25 Cont ID  
Sent By scaldero Date 2018-07-25 Time 10:58 Rev Time 0.00
Received By scaldero Date 2018-07-25 Time 10:58 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-06-27 Cont ID  
Sent By scaldero Date 2018-06-27 Time 10:54 Rev Time 0.00
Received By scaldero Date 2018-06-27 Time 10:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-05-11 Cont ID  
Sent By scaldero Date 2018-05-11 Time 11:30 Rev Time 0.00
Received By scaldero Date 2018-05-11 Time 11:27 Sent To  
Notes
2018-05-11 11:30:48PERMIT # 18050247
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED WITH COMMENTS:
  
 1) FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected]) OR IN WRITING
 (FAX: 561-804-4774) AND APPROVED BY THE OFFICE OF THE
 FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 2) PROVIDE 44 INCH WIDE STRIPING (DEMARCATION) IN BACK
 OF HOUSE TO ENSURE EGRESS PATH REQUIREMENTS ARE
 MAINTAINED AT ALL TIMES.
  
 3) PROVIDE A K-TYPE PORTABLE FIRE EXTINGUISHER AND
 ASSOCIATED SIGNAGE IN KITCHEN AREA.
  
 4) KITCHEN HOOD SUPPRESSION SYSTEM SHALL BE TIED INTO
 THE BUILDING FIRE ALARM SYSTEM TO INITIATE A GENERAL
 FIRE ALARM CONDITION.
  
 5) DEEP FAT FRYERS SHALL BE EQUIPPED WITH A SEPARATE
 HIGH-LIMIT CONTROL IN ADDITION TO THE ADJUSTABLE
 THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN THE FAT
 TEMPERATURE REACHES 475F DEGREES AT 1-INCH BELOW THE
 SURFACE.
  
 6) COOKING OPERATIONS PRODUCING SMOKE OR GREASE-LADEN
 VAPORS SHALL BE PROTECTED WITH A CLASS I MECHANICAL
 EXHAUST HOOD EQUIPPED WITH AN AUTOMATIC WET-CHEMICAL
 FIRE SUPPRESSION SYSTEM.
  
 7) SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO
 THE FIRE ALARM AND SPRINKLER SYSTEM.
  
  
 SUE ELLEN CALDERON
 ASST. FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2018-07-31 Cont ID  
Sent By gjohnson Date 2018-07-31 Time 17:08 Rev Time 0.00
Received By gjohnson Date 2018-07-31 Time 17:09 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-07-06 Cont ID  
Sent By gjohnson Date 2018-07-06 Time 08:25 Rev Time 0.00
Received By gjohnson Date 2018-07-06 Time 08:24 Sent To  
Notes
2018-07-06 08:28:462ND REVIEW: FBC 2017 6TH EDITION
  
 PREVIOUS GAS COMMENTS: APPEARS TO BE NO RESPONSE PLEASE
 SUBMIT RESPONSE LETTER TO EXPEDITE REVIEW.
  
 1. PLEASE PROVIDE THE DISTANCE BETWEEN THE GAS METER
 AND STEPDOWN REGULATOR 2PSI TO .5PSI SHOW DISTANCE AND
 SIZE ON RISER. PER 2017 FBC-FUEL GAS, SECS. 402.4.1,
 402.4.2.
  
 2. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 3. SHT. P2.1 THE NOTE FOR THE GAS REFERENCES NFPA 54
 BUT THE TABLE LISTED IS OUT OF THE FBC FUEL GAS THIS
 PROJECT SHALL COMPLY WITH FBC FUEL GAS PLEASE CLARIFY.
  
 4. SHT. P2.1 THE NOTE FOR THE GAS LISTS SYSTEM PRESSURE
 AT LESS THAN 2PSI WITH A .5PSI PRESSURE DROP IT ALSO
 LIST TABLE 402.4(5) WHICH IS A 2PSI SYSTEM PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 5. SHOW ALL VALVES AND DRIP LEGS ON RISER. PER FBC FUEL
 GAS 408.4 , 409.1.1 AND WPB AMEND TO FBC 107.2.1
  
  
 6. SHT. P3.0 DETAIL #5 SHOWS AND SINGLE CONCENTRIC VENT
 DETAIL #10 IS SHOWING A TWO PIPE SYSTEM PLEASE CLARIFY.
 WPB AMEND TO FBC 107.2.1
  
 7. SHOW ALL EXISTING BTU LOAD ON GAS RISER . WPB AMEND
 TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-06-06 Cont ID  
Sent By gjohnson Date 2018-06-06 Time 10:27 Rev Time 0.00
Received By gjohnson Date 2018-06-06 Time 10:27 Sent To  
Notes
2018-06-06 10:56:011ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE THE DISTANCE BETWEEN THE GAS METER
 AND STEPDOWN REGULATOR 2PSI TO .5PSI SHOW DISTANCE AND
 SIZE ON RISER. PER 2017 FBC-FUEL GAS, SECS. 402.4.1,
 402.4.2.
  
 2. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 3. SHT. P2.1 THE NOTE FOR THE GAS REFERENCES NFPA 54
 BUT THE TABLE LISTED IS OUT OF THE FBC FUEL GAS THIS
 PROJECT SHALL COMPLY WITH FBC FUEL GAS PLEASE CLARIFY.
  
 4. SHT. P2.1 THE NOTE FOR THE GAS LISTS SYSTEM PRESSURE
 AT LESS THAN 2PSI WITH A .5PSI PRESSURE DROP IT ALSO
 LIST TABLE 402.4(5) WHICH IS A 2PSI SYSTEM PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 5. SHOW ALL VALVES AND DRIP LEGS ON RISER. PER FBC FUEL
 GAS 408.4 , 409.1.1 AND WPB AMEND TO FBC 107.2.1
  
 6. SHT. P3.0 DETAIL #5 SHOWS AND SINGLE CONCENTRIC VENT
 DETAIL #10 IS SHOWING A TWO PIPE SYSTEM PLEASE CLARIFY.
 WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-07-31 Cont ID  
Sent By gjohnson Date 2018-07-31 Time 17:09 Rev Time 0.00
Received By gjohnson Date 2018-07-18 Time 15:07 Sent To  
Notes
2018-07-30 08:55:237/30 TO GJ DESK
  
  
2018-07-27 06:41:397/27 ON SH DESK
  
2018-07-19 15:09:43RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-06 Cont ID  
Sent By gjohnson Date 2018-07-06 Time 08:29 Rev Time 0.00
Received By gjohnson Date 2018-06-14 Time 09:19 Sent To  
Notes
2018-06-18 09:19:59B01

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-07 Cont ID  
Sent By gjohnson Date 2018-06-07 Time 09:16 Rev Time 0.00
Received By gjohnson Date 2018-05-04 Time 14:38 Sent To  
Notes
2018-05-07 14:38:43B08

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-05-17 Cont ID  
Sent By cmontell Date 2018-05-17 Time 13:04 Rev Time 0.00
Received By cmontell Date 2018-05-17 Time 11:28 Sent To  
Notes
2018-05-17 11:29:49MECHANICAL PLAN REVIEW PASS
  
 NEED SEPARATE HOOD PERMIT
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-07-31 Cont ID  
Sent By gjohnson Date 2018-07-31 Time 17:08 Rev Time 0.00
Received By gjohnson Date 2018-07-31 Time 16:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-07-06 Cont ID  
Sent By gjohnson Date 2018-07-06 Time 08:21 Rev Time 0.00
Received By gjohnson Date 2018-07-05 Time 16:00 Sent To  
Notes
2018-07-06 08:23:512ND REVIEW: FBC 2017 6TH EDITION
  
 PREVIOUS PLUMBING COMMENTS: APPEARS TO BE NO RESPONSE
 TO PLUMBING COMMENTS PLEASE SUBMIT RESPONSE LETTER TO
 EXPEDITE REVIEW.
  
 1. PLEASE PROVIDE WATER RISER FOR ALL NEW WATER PIPING.
 PER WPB AMEND TO FBC 107.3.5.1.3(13)
  
 2. A BACKFLOW IS REQUIRED FOR THE ICE MACHINE, WATER
 FILTER, DRINK MACHINE, COFFEE AND TEA MAKERS SHOW ON
 WATER RISER. PER FBC PL 608.3 , 608.16.1 , 608.16.10
  
 3. PROVIDE MANUFACTURE SPECIFICATIONS FOR THE BOOSTER
 PUMP AND WATER FILTER. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-06-06 Cont ID  
Sent By gjohnson Date 2018-06-06 Time 10:10 Rev Time 0.00
Received By gjohnson Date 2018-06-06 Time 10:10 Sent To  
Notes
2018-06-06 10:26:511ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE WATER RISER FOR ALL NEW WATER PIPING.
 PER WPB AMEND TO FBC 107.3.5.1.3(13)
  
 2. A BACKFLOW IS REQUIRED FOR THE ICE MACHINE, WATER
 FILTER, DRINK MACHINE, COFFEE AND TEA MAKERS SHOW ON
 WATER RISER. PER FBC PL 608.3 , 608.16.1 , 608.16.10
  
 3. PROVIDE MANUFACTURE SPECIFICATIONS FOR THE BOOSTER
 PUMP AND WATER FILTER. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2018-05-15 Cont ID  
Sent By eschneid Date 2018-05-15 Time 11:56 Rev Time 0.25
Received By eschneid Date 2018-05-15 Time 11:55 Sent To  
Notes
***NONE***