Plan Review Details - Permit 18050220
Plan Review Stops For Permit 18050220
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-07-03 Cont ID  
Sent By cthroop Date 2018-07-03 Time 13:31 Rev Time 0.00
Received By cthroop Date 2018-07-03 Time 13:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-06-14 Cont ID  
Sent By cthroop Date 2018-06-14 Time 15:04 Rev Time 0.00
Received By cthroop Date 2018-06-13 Time 17:27 Sent To  
Notes
2018-06-14 15:06:20BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. NOA'S SUBMITTED DO NOT MATCH THE NOA'S LISTED ON THE
 PLANS. PLEASE CLARIFY.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-06-28 Cont ID  
Sent By jleahy Date 2018-06-28 Time 08:18 Rev Time 0.00
Received By jleahy Date 2018-06-28 Time 08:18 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-05-31 Cont ID  
Sent By jleahy Date 2018-05-31 Time 15:30 Rev Time 0.00
Received By jleahy Date 2018-05-31 Time 15:29 Sent To  
Notes
2018-05-31 15:37:02FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO ELECTRIC SHOWN
  
 E3903.3 ADDITIONAL LOCATIONS. AT LEAST ONE
 WALL-SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE
 INSTALLED IN HALLWAYS, STAIRWAYS,
 ATTACHED GARAGES, AND DETACHED GARAGES WITH ELECTRIC
 POWER. AT LEAST ONE WALL-SWITCH-CONTROLLED LIGHTING
 OUTLET SHALL BE
 INSTALLED TO PROVIDE ILLUMINATION ON THE EXTERIOR SIDE
 OF EACH OUTDOOR EGRESS DOOR HAVING GRADE LEVEL ACCESS,
 INCLUDING
 OUTDOOR EGRESS DOORS FOR ATTACHED GARAGES AND DETACHED
 GARAGES WITH ELECTRIC POWER. A VEHICLE DOOR IN A GARAGE
 SHALL
 NOT BE CONSIDERED AS AN OUTDOOR EGRESS DOOR. WHERE ONE
 OR MORE LIGHTING OUTLETS ARE INSTALLED FOR INTERIOR
 STAIRWAYS, THERE
 SHALL BE A WALL SWITCH AT EACH FLOOR LEVEL AND LANDING
 LEVEL THAT INCLUDES AN ENTRYWAY TO CONTROL THE LIGHTING
 OUTLETS WHERE
 THE STAIRWAY BETWEEN FLOOR LEVELS HAS SIX OR MORE
 RISERS. [210.70(A)(2)]
  
 E3901.2.1 SPACING.
 RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL
 SPACE IS MORE THAN
 6 FEET (1829 MM), FROM A RECEPTACLE OUTLET.
 [210.52(A)(1)]
  
 E3901.2.2 WALL SPACE.
 AS USED IN THIS SECTION, A WALL SPACE SHALL INCLUDE THE
 FOLLOWING: [210.52(A)(2)]
  
 1.ANY SPACE THAT IS 2 FEET (610 MM) OR MORE IN WIDTH,
 INCLUDING SPACE MEASURED AROUND CORNERS, AND THAT IS
 UNBROKEN ALONG THE FLOOR LINE BY DOORWAYS AND SIMILAR
 OPENINGS, FIREPLACES, AND FIXED CABINETS.
  
 2.THE SPACE OCCUPIED BY FIXED PANELS IN EXTERIOR WALLS,
 EXCLUDING SLIDING PANELS.
  
 3.THE SPACE CREATED BY FIXED ROOM DIVIDERS SUCH AS
 RAILINGS AND FREESTANDING BAR-TYPE COUNTERS.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-03 Cont ID  
Sent By cthroop Date 2018-07-03 Time 13:31 Rev Time 0.00
Received By cthroop Date 2018-06-18 Time 14:06 Sent To I
Notes
2018-06-19 14:06:21RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-14 Cont ID  
Sent By cthroop Date 2018-06-14 Time 15:06 Rev Time 0.00
Received By cthroop Date 2018-05-04 Time 09:31 Sent To I
Notes
2018-05-08 09:31:28R05

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2018-06-14 Cont ID  
Sent By cthroop Date 2018-06-14 Time 15:00 Rev Time 0.00
Received By cthroop Date 2018-06-13 Time 17:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2018-06-04 Cont ID  
Sent By cmontell Date 2018-05-23 Time 12:57 Rev Time 0.00
Received By cmontell Date 2018-06-04 Time 14:21 Sent To  
Notes
2018-05-23 12:57:26NO MECHANICAL WORK TO BE DONE
  
 CHRIS MONTELLO
 561-805-6733
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2018-05-10 Cont ID  
Sent By AW Date 2018-05-10 Time   Rev Time  
Received By awooten Date 2018-05-10 Time   Sent To  
Notes
***NONE***