Plan Review Details - Permit 18050209
Plan Review Stops For Permit 18050209
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-08-27 Cont ID  
Sent By fgiaquin Date 2018-08-27 Time 13:05 Rev Time 0.00
Received By fgiaquin Date 2018-08-27 Time 11:43 Sent To I
Notes
2018-08-27 13:04:52SEPARATE ELECTRICAL PERMIT REQUIRED FOR 120V CIRCUITS

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-07-28 Cont ID  
Sent By fgiaquin Date 2018-07-28 Time 09:25 Rev Time 0.00
Received By fgiaquin Date 2018-07-28 Time 09:23 Sent To I
Notes
2018-07-28 09:25:33ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 SAME VIOLATIONS AS LAST REVIEW.
  
 1. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND
 SIGNED/SEALED BY A DESIGN PROFESSIONAL OR THE
 ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1
  
 2. PLAN IS BLURRY AND UNREADABLE. SUBMIT CLEAR COPIES
 OF PLANS. NOTES AND REVISION BUBBLES CANNOT BE READ ON
 SEVERAL PAGES OF ALL PLANS.
  
 3. PER FBC B1023.5 & 1023.6 (5TH EDITION 2014)
 PENETRATIONS IN THE STAIRWELLS ARE FORBIDDEN. PLEASE
 VERIFY RISER WILL NOT BE USING STAIRWELLS AS A RACEWAY.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTE
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-05-16 Cont ID  
Sent By fgiaquin Date 2018-05-16 Time 09:09 Rev Time 0.00
Received By fgiaquin Date 2018-05-19 Time 08:36 Sent To I
Notes
2018-05-19 09:01:22ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND
 SIGNED/SEALED BY A DESIGN PROFESSIONAL OR THE
 ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1
  
 2. PLAN IS BLURRY AND UNREADABLE. SUBMIT CLEAR COPIES
 OF PLANS.
  
 3. PER FBC B1023.5 & 1023.6 (5TH EDITION 2014)
 PENETRATIONS IN THE STAIRWELLS ARE FORBIDDEN. PLEASE
 VERIFY RISER WILL NOT BE USING STAIRWELLS AS A RACEWAY.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTE
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  
2018-05-16 08:09:515/16/18
  
 EOR TESTING REQUIRED AS OUTLINED IN NFPA 72 AND ALL
 RELATED STANDARDS IN ADDITION TO FD TESTING IN THE
 FIELD.
  
 SENT TO ELECTRICAL
  
 SLT 7805
2018-05-09 11:55:315/9/18 SENT TO FD JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date   Cont ID  
Sent By sathomas Date 2018-08-22 Time 00:00 Rev Time 0.00
Received By   Date 2018-08-22 Time 00:00 Sent To E
Notes
2018-08-22 14:47:44TO BE INSTALLED IN ACCORDANCE WITH NFPA 72
  
 S. THOMAS
 561-804-4728

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-07-20 Cont ID  
Sent By sathomas Date 2018-07-20 Time 00:00 Rev Time 0.00
Received By sathomas Date 2018-07-20 Time 00:00 Sent To E
Notes
2018-07-20 14:23:33PROVISO:
  
 EOR TESTING REQUIRED AS OUTLINED IN NFPA 72 AND ALL
 RELATED STANDARDS IN ADDITION TO FD TESTINGIN THE
 FIELD.
  
 SENT TO: ELECTRICAL
  
 S. THOMAS
 561-804-4728

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-05-21 Cont ID  
Sent By sathomas Date 2018-05-21 Time   Rev Time 0.00
Received By sathomas Date 2018-05-21 Time   Sent To  
Notes
2018-05-21 07:25:405/16/18
  
 EOR TESTING REQUIRED AS OUTLINED IN NFPA 72 AND ALL
 RELATED STANDARDS IN ADDITION TO FD TESTING IN THE
 FIELD.
  
 SENT TO ELECTRICAL
  
 SLT 7805

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-08-27 Cont ID  
Sent By fgiaquin Date 2018-08-27 Time 13:05 Rev Time 0.00
Received By fgiaquin Date 2018-08-15 Time 16:09 Sent To  
Notes
2018-08-16 16:09:29RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-28 Cont ID  
Sent By fgiaquin Date 2018-07-28 Time 09:25 Rev Time 0.00
Received By fgiaquin Date 2018-07-17 Time 15:40 Sent To  
Notes
2018-07-18 15:40:44RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-21 Cont ID  
Sent By lmarchan Date 2018-05-21 Time 10:23 Rev Time 0.00
Received By lmarchan Date 2018-05-04 Time 14:19 Sent To  
Notes
2018-05-07 14:19:56ROUTED TO ELECTRICAL INBOX