| Plan Review Stops For Permit 18050209 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2018-08-27 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2018-08-27 |
Time |
13:05 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2018-08-27 |
Time |
11:43 |
Sent To |
I |
|
| Notes |
| 2018-08-27 13:04:52 | SEPARATE ELECTRICAL PERMIT REQUIRED FOR 120V CIRCUITS |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2018-07-28 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2018-07-28 |
Time |
09:25 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2018-07-28 |
Time |
09:23 |
Sent To |
I |
|
| Notes |
| 2018-07-28 09:25:33 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | SAME VIOLATIONS AS LAST REVIEW. | | | | | | 1. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND | | | SIGNED/SEALED BY A DESIGN PROFESSIONAL OR THE | | | ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS | | | 471.003(2)(H); 471.025; WPB FBC 107.1 | | | | | | 2. PLAN IS BLURRY AND UNREADABLE. SUBMIT CLEAR COPIES | | | OF PLANS. NOTES AND REVISION BUBBLES CANNOT BE READ ON | | | SEVERAL PAGES OF ALL PLANS. | | | | | | 3. PER FBC B1023.5 & 1023.6 (5TH EDITION 2014) | | | PENETRATIONS IN THE STAIRWELLS ARE FORBIDDEN. PLEASE | | | VERIFY RISER WILL NOT BE USING STAIRWELLS AS A RACEWAY. | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTE | | | | | | V/R, | | | | | | FRANK GIAQUINTO | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WPB | | | [email protected] | | | CELL: 561-657-1653 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-05-16 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2018-05-16 |
Time |
09:09 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2018-05-19 |
Time |
08:36 |
Sent To |
I |
|
| Notes |
| 2018-05-19 09:01:22 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND | | | SIGNED/SEALED BY A DESIGN PROFESSIONAL OR THE | | | ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS | | | 471.003(2)(H); 471.025; WPB FBC 107.1 | | | | | | 2. PLAN IS BLURRY AND UNREADABLE. SUBMIT CLEAR COPIES | | | OF PLANS. | | | | | | 3. PER FBC B1023.5 & 1023.6 (5TH EDITION 2014) | | | PENETRATIONS IN THE STAIRWELLS ARE FORBIDDEN. PLEASE | | | VERIFY RISER WILL NOT BE USING STAIRWELLS AS A RACEWAY. | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTE | | | | | | V/R, | | | | | | FRANK GIAQUINTO | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WPB | | | [email protected] | | | CELL: 561-657-1653 | | | | | 2018-05-16 08:09:51 | 5/16/18 | | | | | | EOR TESTING REQUIRED AS OUTLINED IN NFPA 72 AND ALL | | | RELATED STANDARDS IN ADDITION TO FD TESTING IN THE | | | FIELD. | | | | | | SENT TO ELECTRICAL | | | | | | SLT 7805 | | 2018-05-09 11:55:31 | 5/9/18 SENT TO FD JLEAHY |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
sathomas |
Date |
2018-08-22 |
Time |
00:00 |
Rev Time |
0.00 |
| Received By |
|
Date |
2018-08-22 |
Time |
00:00 |
Sent To |
E |
|
| Notes |
| 2018-08-22 14:47:44 | TO BE INSTALLED IN ACCORDANCE WITH NFPA 72 | | | | | | S. THOMAS | | | 561-804-4728 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2018-07-20 |
|
|
Cont ID |
|
| Sent By |
sathomas |
Date |
2018-07-20 |
Time |
00:00 |
Rev Time |
0.00 |
| Received By |
sathomas |
Date |
2018-07-20 |
Time |
00:00 |
Sent To |
E |
|
| Notes |
| 2018-07-20 14:23:33 | PROVISO: | | | | | | EOR TESTING REQUIRED AS OUTLINED IN NFPA 72 AND ALL | | | RELATED STANDARDS IN ADDITION TO FD TESTINGIN THE | | | FIELD. | | | | | | SENT TO: ELECTRICAL | | | | | | S. THOMAS | | | 561-804-4728 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2018-05-21 |
|
|
Cont ID |
|
| Sent By |
sathomas |
Date |
2018-05-21 |
Time |
|
Rev Time |
0.00 |
| Received By |
sathomas |
Date |
2018-05-21 |
Time |
|
Sent To |
|
|
| Notes |
| 2018-05-21 07:25:40 | 5/16/18 | | | | | | EOR TESTING REQUIRED AS OUTLINED IN NFPA 72 AND ALL | | | RELATED STANDARDS IN ADDITION TO FD TESTING IN THE | | | FIELD. | | | | | | SENT TO ELECTRICAL | | | | | | SLT 7805 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-08-27 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2018-08-27 |
Time |
13:05 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2018-08-15 |
Time |
16:09 |
Sent To |
|
|
| Notes |
| 2018-08-16 16:09:29 | RESUB ROUTED TO FIRE INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-07-28 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2018-07-28 |
Time |
09:25 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2018-07-17 |
Time |
15:40 |
Sent To |
|
|
| Notes |
| 2018-07-18 15:40:44 | RESUB ROUTED TO FIRE INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-05-21 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2018-05-21 |
Time |
10:23 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2018-05-04 |
Time |
14:19 |
Sent To |
|
|
| Notes |
| 2018-05-07 14:19:56 | ROUTED TO ELECTRICAL INBOX |
|
|