Plan Review Details - Permit 18050094
Plan Review Stops For Permit 18050094
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-06-20 Cont ID  
Sent By cthroop Date 2018-06-20 Time 15:26 Rev Time 0.00
Received By cthroop Date 2018-06-20 Time 15:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-06-20 Cont ID  
Sent By cthroop Date 2018-06-20 Time 09:13 Rev Time 0.00
Received By cthroop Date 2018-06-15 Time 13:36 Sent To  
Notes
2018-06-20 09:20:20BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 FLORIDA BUILDING CODE, 6TH EDITION, EXISTING
 BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ITEM #3 FROM 1ST REVIEW HAS NOT BEEN ADDRESSED. SEE
 PLAN PAGE RF1.6, REVISE CHPT 7 LEVEL 1 SECTION 708 AND
 708.1 TO SECTION 706.
  
 2. PROVIDE TITLE BLOCK WITH GOVERNING CODES AND
 STATEMENT OF THRESHOLD BUILDING AS FOLLOWS:
  
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 FLORIDA BUILDING CODE, 6TH EDITION, EXISTING
 BUILDING
  
 THRESHOLD BUILDING
 CONFORMING TO CHAPTER 553 FLORIDA STATUTES,
 CHAPTER 468, PART XII, FLORIDA STATUTES
 AND THE FLORIDA BUILDING CODE AS AMENDED BY CITY OF
 WEST PALM BEACH
  
 3. PROVIDE SPECIAL INSPECTOR AGREEMENT. SEE THRESHOLD
 REVIEW COMMENTS.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-05-09 Cont ID  
Sent By cthroop Date 2018-05-09 Time 17:10 Rev Time 0.00
Received By cthroop Date 2018-05-08 Time 17:17 Sent To P
Notes
2018-05-09 17:22:55BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 FLORIDA BUILDING CODE, EXISTING BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE EVALUATION REPORT FROM DESIGN PROFESSIONAL
 PER FBC EXISTING BUILDING CHPT. 6.
 ?[BS]606.2.2.1EVALUATION.
 THE BUILDING SHALL BE EVALUATED BY A REGISTERED DESIGN
 PROFESSIONAL, AND THE EVALUATION FINDINGS SHALL BE
 SUBMITTED TO THE CODE OFFICIAL. THE EVALUATION SHALL
 ESTABLISH WHETHER THE DAMAGED BUILDING, IF REPAIRED TO
 ITS PREDAMAGE STATE, WOULD COMPLY WITH THE PROVISIONS
 OF THE FLORIDA BUILDING CODE, BUILDING FOR LOAD
 COMBINATIONS THAT INCLUDE WIND OR EARTHQUAKE EFFECTS,
 EXCEPT THAT THE SEISMIC FORCES SHALL BE THE REDUCED
 FLORIDA BUILDING CODE, BUILDING-LEVEL SEISMIC FORCES.
 [BS]606.2.2.2EXTENT OF REPAIR FOR COMPLIANT BUILDINGS.
 IF THE EVALUATION ESTABLISHES THAT THE BUILDING IN ITS
 PREDAMAGE CONDITION COMPLIES WITH THE PROVISIONS OF
 SECTION 606.2.2.1, THEN THE DAMAGED ELEMENTS SHALL BE
 PERMITTED TO BE RESTORED TO THEIR PREDAMAGE CONDITION.
  
 2. PROVIDE DEMENSIONS OF STRUCTURAL ELEMENTS.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 3. CHANGE CODE REFERENCE ON PLAN PAGE RF1.6, CHPT. 7 -
 LEVEL 1 SECTION 708 AND 708.1 REROOFING TO SECTION 706.
 SECTION 708 IS FOR ENERGY CONSERVATION.
  
 4. ROOFING PERMIT REQUIRED. PROVIDE PRODUCT APPROVALS
 FOR ROOFING SYSTEM COMPONENTS.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
 DEFERRED SUBMITTALS OPTION -
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 5. PROVIDE CONNECTOR DETAIL AND SPECIFICATIONS FOR WOOD
 TIMBER PURLIN REPLACEMENT.
  
 6. RESIDENT INSPECTOR REQUIRED.
 110.3.9 OTHER INSPECTIONS SERVICES. THE BUILDING
 OFFICIAL MAY MAKE, OR CAUSE TO BE MADE BY OTHERS, THE
 INSPECTIONS REQUIRED BY SECTION 109. HE/SHE MAY ACCEPT
 REPORTS OF INSPECTORS OF RECOGNIZED INSPECTION
 SERVICES, PROVIDED THAT AFTER INVESTIGATION HE/SHE IS
 SATISFIED AS TO THEIR QUALIFICATIONS AND RELIABILITY. A
 CERTIFICATE CALLED FOR BY ANY PROVISION OF THE
 TECHNICAL CODES SHALL NOT BE BASED ON SUCH REPORTS
 UNLESS THE SAME ARE IN WRITING AND CERTIFIED BY A
 RESPONSIBLE OFFICER OF SUCH SERVICE. THE BUILDING
 OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY AN INSPECTION
 SERVICE IN THE FOLLOWING INSTANCES:
  
 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS
 3. WHERE THE CONCRETE DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F ?C) IN EXCESS OF 3000 POUNDS PER SQUARE
 INCH
 4. FOR PILE DRIVING
 5. FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE
 FOOT
 6. FOR BUILDINGS MORE THAN 2 STORIES IN HEIGHT
 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR
 METHODS OF CONSTRUCTION
  
 SUCH INSPECTORS SHALL BE ADEQUATELY PRESENT AT TIMES
 WORK IS UNDERWAY ON THE STRUCTURAL ELEMENTS OF THE
 BUILDING. SUCH INSPECTORS SHALL BE A REGISTERED
 ARCHITECT, OR ENGINEER, OR A PERSON LICENSED UNDER
 CHAPTER 468, PART XII, FLORIDA STATUTES.
 SUCH INSPECTORS SHALL SUBMIT WEEKLY PROGRESS REPORTS
 INCLUDING THE DAILY INSPECTIONS TO THE BUILDING
 OFFICIAL, AND INCLUDING A CODE COMPLIANCE OPINION OF
 THE RESIDENT INSPECTOR.
 AT THE COMPLETION OF THE CONSTRUCTION WORK OR PROJECT,
 SUCH INSPECTORS SHALL SUBMIT A CERTIFICATE OF
 COMPLIANCE TO THE BUILDING OFFICIAL, STATING THAT THE
 WORK WAS DONE IN COMPLIANCE WITH THIS CODE AND IN
 ACCORDANCE WITH THE PERMITTED DRAWING. FINAL INSPECTION
 SHALL BE MADE BY THE BUILDING OFFICIAL BEFORE A
 CERTIFICATE OF OCCUPANCY OR CERTIFICATE OF COMPLETION
 IS ISSUED; AND CONFIRMATION INSPECTIONS MAY BE MADE AT
 ANY TIME TO MONITOR ACTIVITIES AND RESIDENT INSPECTORS.
 1. RESIDENT INSPECTOR AGREEMENT SHALL BE COMPLETED AND
 SUBMITTED IN TRIPLICATE.
 2. PROVIDE RESUME OF RESIDENT INSPECTOR.
 3. PROVIDE RESUME OF JOB INSPECTOR IF DIFFERENT FROM
 RESIDENT INSPECTOR ? (P.E., ARCH. OR 468 INSPECTOR).
 4. PROVIDE LIST OF SIMILAR PROJECTS COMPLETED BY
 CONTRACTOR.
 5. PROVIDE STRUCTURAL INSPECTION PLAN.
  
 A COPY OF THE CITY OF WEST PALM BEACH RESIDENT
 INSPECTOR HAS BEEN INCLUDED IN THIS SUBMITTAL FOR YOUR
 REVIEW AND USE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  
  
  
  
  
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2018-06-11 Cont ID  
Sent By destabro Date 2018-06-11 Time 15:16 Rev Time 0.00
Received By destabro Date 2018-06-11 Time 15:16 Sent To P
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2018-05-08 Cont ID  
Sent By destabro Date 2018-05-08 Time 13:08 Rev Time 0.00
Received By destabro Date 2018-05-08 Time 13:08 Sent To B
Notes
2018-05-08 13:09:535/8/2018 - RETENTION OF HISTORIC MATERIAL IS A PRIORITY
 - ROOF DECKING REPAIR AND REPLACEMENT IN-KIND MEETS
 GRANT REQUIREMENTS. DLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-06-20 Cont ID  
Sent By cthroop Date 2018-06-20 Time 09:20 Rev Time 0.00
Received By cthroop Date 2018-06-06 Time 11:45 Sent To I
Notes
2018-06-07 11:45:52RESUB ROUTED TO HISTORIC INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-17 Cont ID  
Sent By tklarge Date 2018-05-17 Time 13:09 Rev Time 0.00
Received By tklarge Date 2018-05-02 Time 16:17 Sent To  
Notes
2018-05-02 16:17:26ROUTED TO HISTORIC INBOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-06-14 Cont ID  
Sent By thunt Date 2018-06-14 Time 17:00 Rev Time 0.00
Received By thunt Date 2018-06-14 Time 17:00 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-05-17 Cont ID  
Sent By tklarge Date 2018-05-17 Time 13:09 Rev Time 0.00
Received By tklarge Date 2018-05-17 Time 11:49 Sent To I
Notes
2018-05-17 13:08:311) SHT. RF1.1 - SUBMIT CALCULATIONS FOR THE SIZING OF
 THE GUTTER SYSTEM FOR THE RAINWATER.HOW DID YOU ARRIVE
 AT THE 106 GPM REQUIRED NUMBER?/
 2) SHT. RF1.1 - SUBMIT CALCULATIONS FOR THE SIZING OF
 THE DOWNSPOUTS. HOW DID YOU REACH THE REQUIRED CAPACITY
 NUMBER OF 192 GPM?
 3) SHT. RF.1.1 - ROOF STORM DRAIN SCHEDULE --SUBMIT
 ADDITIONAL INFORMATION AS TO HOW YOU ARRIVED AT THE
 NUMBER OF DOWNSPUTS REQD. (2) 3" DOWNSPOUTS DO NOT
 EQUAL THE SQUARE INCH AREA OF A 6" DOWNSPOUT NOR DO (3)
 3" DOWNSPOUTS EQUAL THE SQUARE INCH AREA OF A
 9"DOWNSPOUT.
 4) SUBMIT A SITE PLAN SHOWING WHERE AND HOW THE STORM
 DRAINS CONNECT TO THE STORM SEWER.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2018-06-20 Cont ID  
Sent By cthroop Date 2018-06-20 Time 09:08 Rev Time 0.00
Received By cthroop Date 2018-06-20 Time 09:08 Sent To  
Notes
2018-06-20 09:10:40BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 FLORIDA BUILDING CODE, 6TH EDITION, EXISTING
 BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1. PRODUCT APPROVALS FOR PROPOSED ROOFING SYSTEM WILL
 BE DEFERRED.
  
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON
 THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING
 OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2018-06-15 Cont ID  
Sent By cthroop Date 2018-06-15 Time 14:18 Rev Time 0.00
Received By cthroop Date 2018-06-15 Time 13:37 Sent To  
Notes
2018-06-15 14:19:20ROOFING SUBMITTALS TO BE DEFERRED. CT

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2018-05-09 Cont ID  
Sent By cthroop Date 2018-05-09 Time 15:28 Rev Time 0.00
Received By cthroop Date 2018-05-09 Time 15:03 Sent To  
Notes
2018-05-09 15:53:32BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 FLORIDA BUILDING CODE, EXISTING BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE PRODUCT APPROVALS FOR PROPOSED ROOFING
 SYSTEM COMPONENTS.
  
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
  
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status P Date 2018-06-29 Cont ID  
Sent By cthroop Date 2018-06-29 Time 13:14 Rev Time 0.00
Received By cthroop Date 2018-06-29 Time 13:14 Sent To I
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2018-06-15 Cont ID  
Sent By cthroop Date 2018-06-15 Time 14:18 Rev Time 0.00
Received By cthroop Date 2018-06-15 Time 14:18 Sent To  
Notes
2018-06-15 14:26:43BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 THRESHOLD BUILDINGS
  
 1. SPECIAL INSPECTOR AGREEMENT SHALL BE COMPLETED AND
 SUBMITTED IN TRIPLICATE.
 YOU MAY OBTAIN A COPY OF THE CURRENT S.I. FORM @
 ONESTOPSHOP.WPBGOV.COM.
 2. PROVIDE RESUME OF JOB INSPECTOR (P.E., ARCH. OR 468
 INSPECTOR).
 3. PROVIDE LIST OF SIMILAR PROJECTS COMPLETED BY
 CONTRACTOR.
 4. PROVIDE STRUCTURAL INSPECTION PLAN.
 5. THIS BUILDING MEETS THE DEFINITION OF: THRESHOLD
 BUILDING F.S. 553.71 (12)
 ?THRESHOLD BUILDING? ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND HAS AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
 5A) THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS PURSUANT TO
 A STRUCTURAL INSPECTION PLAN PREPARED BY THE ENGINEER
 OF RECORD. THE STRUCTURAL INSPECTION PLAN MUST BE
 SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE ISSUANCE
 OF A BUILDING PERMIT.
 5B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUESTS FOR THRESHOLD
 BUILDINGS, A SPECIAL INSPECTOR IS REQUIRED BY F.S.
 553.79 (5) TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED TO BE
 FILLED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED AND
 RETURNED TO THIS OFFICE AND REVIEWED AND APPROVED
 BEFORE PERMIT ISSUANCE WILL TAKE PLACE. CONTACT KEN
 CONRAD, MANAGER OF SPECIAL INSPECTOR PROGRAM AT (561)
 805-6666 FOR FURTHER INFORMATION BEFORE THE PERMIT MAY
 BE ISSUED.
 5C) THRESHOLD BUILDING, REQUIRED. W.P.B. AMENDMENT
 110.3.7.4.4. ALL PLANS FOR THE BUILDING WHICH ARE
 REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT OR
 ENGINEER OF RECORD CONTAIN A STATEMENT THAT, ?TO THE
 BEST OF THE ARCHITECT?S OR ENGINEER?S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 F.S.?
 5D) FOR THE SPECIAL INSPECTOR & DESIGNATED JOB
 INSPECTORS ? PLEASE PROVIDE A RESUME? OF INSPECTION
 EXPERIENCE ON PREVIOUS PROJECTS. THE RESUME? MUST BE
 ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED HEREIN.
 THE BUILDING OFFICIAL OR HIS DESIGNEE WILL REVIEW THE
 RESUME?. AFTER THE RESUME? IS REVIEWED, AN INTERVIEW
 MAY BE SCHEDULED.
 5E) JOB INSPECTOR ? FBC 110.3.7.6 THE BUILDING
 DEPARTMENT MAY ALLOW A SPECIAL INSPECTOR TO CONDUCT THE
 MINIMUM STRUCTURAL INSPECTION OF THRESHOLD BUILDINGS
 REQUIRED BY THIS CODE, SECTION 553.73,FLORIDA STATUTES,
 WITHOUT DUPLICATIVE INSPECTION BY THE BUILDING
 DEPARTMENT. THE BUILDING OFFICIAL IS RESPONSIBLE FOR
 ENSURING THAT ANY PERSON CONDUCTING INSPECTIONS IS
 QUALIFIED AS A BUILDING INSPECTOR UNDER PART XII OF
 CHAPTER 468, FLORIDA STATUTES, OR CERTIFIED AS A
 SPECIAL INSPECTOR UNDER CHAPTER 471 OR 481, FLORIDA
 STATUTES. INSPECTIONS OF THRESHOLD BUILDINGS REQUIRED
 BY SECTION 553.79(5), FLORIDA STATUTES, ARE IN ADDITION
 TO THE MINIMUM INSPECTIONS REQUIRED BY THIS CODE.
 5F) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
 5G) NOTE FOR PAPER PLANS, 3 SETS OF DOCUMENTS ARE
 REQUIRED.
 5H) 110.3.7.4.1 THE SPECIAL INSPECTOR, UPON COMPLETION
 OF THE BUILDING AND PRIOR TO THE ISSUANCE OF A
 CERTIFICATE OF OCCUPANCY OR COMPLETION, FILE A SIGNED
 AND SEALED STATEMENT WITH THE ENFORCEMENT AGENCY IN
 SUBSTANTIALLY THE FOLLOWING FORM: ?TO THE BEST OF MY
 KNOWLEDGE AND BELIEF, THE CONSTRUCTION OF ALL
 STRUCTURAL LOAD-BEARING COMPONENTS DESCRIBED IN THE
 THRESHOLD INSPECTION PLAN COMPLIES WITH THE PERMITTED
 DOCUMENTS AND THE SPECIALTY SHORING DESIGN PROFESSIONAL
 ENGINEER HAS ASCERTAINED THAT THE SHORING AND RESHORING
 CONFORMS WITH THE SHORING AND RESHORING PLANS SUBMITTED
 TO THE ENFORCEMENT AGENCY?.
 5I) 110.3.7.4.2 ANY PROPOSAL TO INSTALL AN ALTERNATE
 STRUCTURAL PRODUCT OR SYSTEM TO WHICH BUILDING CODES
 APPLY SHALL BE SUBMITTED TO THE ENFORCEMENT AGENCY FOR
 REVIEW FOR COMPLIANCE WITH THE CODES AND MADE PART OF
 THE ENFORCEMENT AGENCY?S RECORDED SET OF PERMIT
 DOCUMENTS. 110.3.7.4.3 ALL SHORING AND RESHORING
 PROCEDURES, PLANS AND DETAILS SHALL BE SUBMITTED TO THE
 ENFORCEMENT AGENCY FOR RECORDKEEPING. EACH SHORING AND
 RESHORING INSTALLATION SHALL BE SUPERVISED, INSPECTED
 AND CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
 5J) NOTICE ONLY. PLEASE CALL THE CITY OF WEST PALM
 BEACH?S AUTOMATED TELEPHONE INSPECTION LINE @ (561)
 805-6700 FOR ALL BUILDING INSPECTIONS FOR AUDITING OF
 JOBSITE INSPECTIONS. WITHOUT THIS, THE PERMIT EXPIRES
 IN 6 MONTHS WHICH WILL RESULT IN ?ABANDONMENT OF JOB,
 NO INSPECTION ACTIVITY?. THE PERMIT WILL BECOME
 EXPIRED.
 6) PLEASE PROVIDE A SITE PLAN SHOWING THE PROPERTY
 LINES, CONSTRUCTION AREAS, STAGING AREAS, HOW THE
 OCCUPANTS OF THE BUILDING WILL BE SAFE GUARDED DURING
 THEIR ENTRY AND EXIT OF THE BUILDING. SHOW COMPLIANCE
 WITH 2014 FBC 3306.7 ? COVERED WALKWAYS, INCLUDING
 LIGHTING FOR THE EXIT DISCHARGE. 2014 FBC 3310.2 ?
 MAINTENANCE OF MEANS OF EGRESS. REQUIRED MEANS OF
 EGRESS SHALL BE MAINTAINED AT ALL TIMES DURING
 CONSTRUCTION, DEMOLITION, REMODELING OR ALTERATIONS AND
 ADDITIONS TO ANY BUILDING.
 7) IF SCAFFOLDING EXTENDS BEYOND THE PRIVATE PROPERTY
 AND ONTO CITY RIGHT OF WAY, ENGINEERING WILL REQUIRE
 RIGHT OF WAY PERMITS. PLEASE CONTACT MANNY GONZALEZ AT
 THE ENGINEERING DEPARTMENT ? (561) 494-1085.
 7A) IF SCAFFOLDING IS TO BE USED FOR THE HEIGHT OF THE
 BUILDING, PLEASE PROVIDE HOW THE SCAFFOLDING WILL BE
 BUILT AS WELL AS HOW THE SCAFFOLDING WILL BE ANCHORED
 TO RESIST LATERAL WIND LOADING. THERE APPEARS SAND
 BLASTING WILL ALSO BE AN ELEMENT OF THE OPERATION, HOW
 WILL THE SANDBLASTING BE CONTAINED, WILL THERE BE WIND
 SCREENS, IF SO PLEASE PROVIDE WHAT ELEMENTS WILL BE
 INTRODUCED TO KEEP THE SCAFFOLDING FROM MOVING WITH THE
 LATERAL EFFECT OF WIND ON THE WIND SCREENS. AT WHAT
 SAFETY FACTOR ARE THESE ELEMENTS FACTORED? 107.2.1.3
 ADDITIONAL INFORMATION. 2014 FBC 3302.1 & 3306.1.
 FBC 3309 FIRE EXTINGUISHERS
 [F] 3309.1 WHERE REQUIRED.
 ALL STRUCTURES UNDER CONSTRUCTION, ALTERATION OR
 DEMOLITION SHALL BE PROVIDED WITH NO FEWER THAN ONE
 APPROVED PORTABLE FIRE EXTINGUISHER IN ACCORDANCE WITH
 SECTION 906 AND SIZED FOR NOT LESS THAN ORDINARY HAZARD
 AS FOLLOWS:
 8) PROVIDE COMPLIANCE WITH FBC 3309.1 WHERE REQUIRED.
 ALL STRUCTURES UNDER CONSTRUCTION, ALTERATION OR
 DEMOLITION SHALL BE PROVIDED WITH NO FEWER THAN ONE
 APPROVED PORTABLE FIRE EXTINGUISHER IN ACCORDANCE WITH
 SECTION 906 AND SIZED FOR NOT LESS THAN ORDINARY HAZARD
 AS FOLLOWS:
 8A) AT EACH STAIRWAY ON ALL FLOOR LEVELS WHERE
 COMBUSTIBLE MATERIALS HAVE ACCUMULATED.
 8B) IN EVERY STORAGE AND CONSTRUCTION SHED.
 8C) ADDITIONAL PORTABLE FIRE EXTINGUISHERS SHALL BE
 PROVIDED WHERE SPECIAL HAZARDS EXIST, SUCH AS THE
 STORAGE AND USE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS.
  
  