| 2018-05-22 15:30:55 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A |
| | DISCONNECTING MEANS AT THE BUILDING OR SEPARATE |
| | STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR |
| | MAIN BREAKER AT THE PANEL FOR PANEL LA. NEC 225.31, |
| | 225.32 |
| | 2. PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A |
| | BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH |
| | CIRCUIT. NEC 250.32; FBC RE3607.3 |
| | 3. NOTE 1 ON SHEETS E-2 AND E-3 DOES NOT ADDRESS THE |
| | AFCI REQUIREMENTS PER THE 2014 NEC. ALL BRANCH CIRCUITS |
| | THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE |
| | OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS, DINING |
| | ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, |
| | BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, |
| | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS |
| | SHALL BE AFCI PROTECTED. PROVIDE CORRECTION. NEC |
| | 210.12; FBC RE E3902.16 |
| | 4. NOTE 2 ON SHEETS E-2 AND E-3 STATES THAT RECEPTACLES |
| | SHALL BE TR PER THE 2011 NEC, WHICH IS NOT THE CURRENT |
| | CODE. PROVIDE CORRECTION. FBC PREFACE. |
| | 5. RISER DIAGRAM SHOWS THE PANELS AS 10K AIC RATED, |
| | WHILE THE PANEL SCHEDULES SHOWS THEM AS 22K AIC RATED. |
| | CORRECT DISCREPANCY. WPB FBC 107.2.1 |
| | 6. GFCI PROTECTION IS REQUIRED FOR ALL OUTLETS IN |
| | GARAGE INCLUDING THE GARAGE DOOR OPENER. PROVIDE |
| | CORRECTION. NEC 210.8; FBC RE E3902.2 |
| | 7. GFCI RECEPTACLES IN GARAGE ARE SHOWN ON THE SAME |
| | CIRCUIT AS ITEMS LOCATED OUTSIDE OF GARAGE. PROVIDE |
| | CORRECTION. NEC 210.52(G)(1); FBC RE E3901.9 |
| | 8. PROVIDE GFCI PROTECTION FOR DISHWASHERS. NEC |
| | 210.8(D); FBC RE E3902.10 |
| | 9. LIGHTING OVER TUB/SHOWERS APPEARS TO BE A STANDARD |
| | RECESS LIGHT. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL |
| | BE SUITABLE FOR DAMP LOCATIONS. PROVIDE CORRECTION. NEC |
| | 410.10(D); FBC RE E4003.11 |
| | 10. PROVIDE GFCI WEATHER PROOF RECEPTACLE ON BALCONY |
| | AND TERRARE AREAS. NEC 210.52(E); FBC RE E3901.7 |
| | 11. BREAKER FOR POOL PUMP REQUIRED TO BE GFCI |
| | PROTECTED. PROVIDE CORRECTION. NEC 680.21(C); FBC RE |
| | E4203.1.3 |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |