Plan Review Details - Permit 18050070
Plan Review Stops For Permit 18050070
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-06-07 Cont ID  
Sent By jleahy Date 2018-06-07 Time 10:52 Rev Time 0.00
Received By jleahy Date 2018-06-07 Time 10:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-05-29 Cont ID  
Sent By jleahy Date 2018-05-29 Time 08:01 Rev Time 0.00
Received By jleahy Date 2018-05-29 Time 08:01 Sent To  
Notes
2018-05-29 08:07:17FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED TO SHOW LOCATION OF THE CONTROLLER FOR LIGHTING,
 AND PANEL FOR CIRCUITS.
  
 NEED CUT SHEETS ON CONTROLER
  
 LIGHTING FIXTURES DO NOT APPEAR TO BE LISTED.
  
 VALUE OF THE WORK IS LOW SHOULD INCLUDE ALL LABOR AND
 MATERIALS PER FBC 109.3
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC,
 PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE
 WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION
 REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF
 NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 PROVIDE LIGHTING CONTROL PER FBC ENERGY CODE. FBC CE
 405.2.2.2
  
 EXTERIOR LIGHTING CONTROLS. LIGHTING NOT DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY EITHER A
 COMBINATION OF A PHOTOSENSOR AND A TIME SWITCH, OR AN
 ASTRONOMICAL TIME SWITCH. LIGHTING DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY AN
 ASTRONOMICAL TIME SWITCH OR PHOTOSENSOR. ALL TIME
 SWITCHES
 SHALL BE CAPABLE OF RETAINING PROGRAMMING AND THE TIME
 SETTING DURING LOSS OF POWER FOR A PERIOD OF AT LEAST
 10 HOURS. FBC CE 405.2.4

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-29 Cont ID  
Sent By jleahy Date 2018-05-29 Time 08:07 Rev Time 0.00
Received By jleahy Date 2018-05-01 Time 09:37 Sent To  
Notes
2018-05-02 09:37:34ELEC <5K

Review Stop Z ZONING
Rev No 1 Status N Date   Cont ID  
Sent By M. Cruz Date 2018-05-08 Time   Rev Time 0.00
Received By   Date 2018-05-08 Time   Sent To E
Notes
2018-05-08 13:30:53ZONING REVIEW N/A.
 M. CRUZ
 ASSOCIATE PLANNER
 561-822-1442
 [email protected]