Plan Review Details - Permit 18050020
| Plan Review Stops For Permit 18050020 |
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2018-07-26 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-07-26 |
Time |
11:47 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-07-26 |
Time |
11:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2018-06-04 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-06-04 |
Time |
05:06 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-06-04 |
Time |
05:06 |
Sent To |
|
|
| Notes |
| 2018-06-04 05:06:47 | 1) SHOW THE DISTANCE FROM THE EXISTING GAS METER TO THE | | | MOST REMOTE GAS OUTLET ON THE SYSTEM. THE EXISTING GAS | | | DRAWING ON FILE IN CITY RECORDS SHOWS THE FURTHEST | | | DISTANCE AS 67 FT. THIS IS THE DISTANCE THAT IS TO BE | | | USE FOR THE SIZING OF THIS SYTEM.2017 FBC-FUEL GAS | | | SEC.402.4.1. | | | 2) THE MINIMUM SIZE OF THE SCH. 40 METALLIC PIPE AT THE | | | METER OUTLET SHALL BE 2 INCHES BASED ON THE TOTAL BTU | | | LOAD AND THE EXISTING DISTANCE OF THE MOST REMOTE GAS | | | OUTLET ON THIS SYSTEM. 2017 FBC-FUEL GAS SEC. 402.4.1, | | | 401.3, 401. | | | 3) THE EXISTING GAS PLAN ON FILE IN CITY RECORDS FOR | | | THIS ADDRESS SHOWS THE SIZE OF THE PIPE ENTERING THE | | | STRUCTURE AS 1 INCH AND YOUR PLAN SHOWSS 3/4 INCH. | | | CLARIFY. | | | 4) THE SUBMITTED GAS PLAN NOTES A 3/4 INCH LINE | | | SUPPLYING AN EXISTING 1 1/4 INCH PE LINE TO THE POOL | | | HEATER AND A NEW 1 1/4 SCH. 40 METALLIC LINE FOR THE | | | GENERATOR. SUBMIT CALCULATIONS/DOCUMENTATION AS TO HOW | | | YOU ARE GOING TO ACCOMPLISH THIS FEAT. WPBAMEND. TO FBC | | | SEC. 107.2.1, 2017 FBC-FUEL GAS SEC.401.8, 402.2 | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-07-26 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-07-26 |
Time |
11:47 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-07-26 |
Time |
11:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-06-04 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-06-04 |
Time |
05:06 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-06-04 |
Time |
04:05 |
Sent To |
|
|
| Notes |
|
|
|