Plan Review Details - Permit 18050017
Plan Review Stops For Permit 18050017
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-07-26 Cont ID  
Sent By spalmer Date 2018-07-26 Time 15:12 Rev Time 0.00
Received By spalmer Date 2018-07-26 Time 15:12 Sent To  
Notes
2018-07-26 15:13:04PASSED PER 18050016

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-06-03 Cont ID  
Sent By tklarge Date 2018-06-03 Time 08:49 Rev Time 0.00
Received By tklarge Date 2018-06-03 Time 07:57 Sent To  
Notes
2018-06-03 08:49:021) THE EXISTING PLANS ON FILE WITH THE CITY SHOW A BBQ
 GRILL AND ALSO A POOL HEATER. THE BTU LOADS OF THESE
 APPLIANCES MUST BE ADDED INTO THE TOTAL BTU LOAD FOR
 THIS SYSTEM. 2017 FBCR SEC. G2412.3, 2412.4 G2412.8. IF
 UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO
 ENSURE A SAFE OPERATING SYSTEM.
 2) THE SHUTOFF VALVE ON THE LINE TO THE INTERIOR OF THE
 STRUCTURE SHALL BE LOCATED IMMEDIATELY AHEAD OF THE
 REGULATOR, NOT AFTER THE REGULATOR. 2017 FBCR SEC.
 G2420.4.
 3) SHOW THE DISTANCE FROM THE MP REGULATOR FOR THE
 EXISTING LOAD INTO THE STRUCTURE TO THE FURTHEST OUTLET
 ON THAT SECTION OF THE SYSTEM. COMPLY WITH 2017 FBCR
 SEC. G2413.4.1.
 4) INDICATE ON THE PLANS WHICH GAS SIZING TABLE IS USED
 FOR THE LOW PRESSURE SYSTEM.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-26 Cont ID  
Sent By tklarge Date 2018-07-26 Time 15:17 Rev Time 0.00
Received By tklarge Date 2018-07-26 Time 15:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-03 Cont ID  
Sent By tklarge Date 2018-06-03 Time 08:49 Rev Time 0.00
Received By tklarge Date 2018-06-03 Time 07:57 Sent To  
Notes
***NONE***