| 2018-06-05 17:19:37 | BUILDING PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER, PX3169 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. CORRECT ADDRESS ON PLANS. | | | 2. PROVIDE 2ND COPY OF WINDOW PRODUCT APPROVALS. | | | 3. PROVIDE PRODUCT APPROVALS FOR WINDOW MULLIONS. | | | 4. PALM BEACH COUNTY IMPACT FEES REQUIRED. | | | 5. SUBMIT ENERGY SUBMITTAL. | | | | | | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | SPECIFICALLY, PROVIDE WINDOW SUBMITTALS. | | | | | | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT | | | FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID. | | | UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE | | | SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN | | | IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP | | | AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE | | | CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN | | | BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY | | | IMPACT FEES AT (561) 233-5025. | | | | | | FBC 107.3.5.1.6 ENERGY CALCULATIONS ? PROVIDE AN ENERGY | | | SUBMITTAL COMPLIANT WITH FBC-E 103. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | | REVIEWED SHEETS DETACHED AND MARK VOID. | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2018-08-01 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-08-01 |
Time |
14:43 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-08-01 |
Time |
14:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-05-23 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-05-23 |
Time |
08:56 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-05-23 |
Time |
07:55 |
Sent To |
|
|
| Notes |
| 2018-05-23 08:56:56 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE CORRECT ADDRESS ON PLAN. WPB FBC 107.2.1 | | | 2. PROVIDE FLOOR PLAN OF ENTIRE RESIDENCE, SHOWING | | | SMOKE/CO ALARMS IN EACH LOCATION REQUIRED PER CODE. | | | SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE EXISTING | | | OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC RE | | | R314.3, R315.1; WPB FBC 107.2.1 | | | 3. NOTE 18 DOES NOT MATCH THE CURRENT CODE FOR AFCI | | | PROTECTION. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, | | | SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN | | | KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, | | | PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS, | | | RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND | | | SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. PROVIDE | | | CORRECTION. NEC 210.12; FBC RE E3902.16 | | | 4. NOTE 19 STATES THAT RECEPTACLES SHALL BE TAMPER | | | RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT | | | APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE | | | CORRECTION. NEC 406.12; FBC RE E4002.14 | | | 5. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE | | | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE | | | IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2 | | | 6. PLAN IS SHOWING AN OPTIONAL WP GFI RECEPTACLE. A | | | GFCI PROTECTED OUTLET FOR SERVICING OF A/C EQUIPMENT IS | | | REQUIRED PER CODE. PROVIDE CORRECTION. NEC 210.63; FBC | | | RE E3901.12 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-08-01 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-08-01 |
Time |
15:35 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-08-01 |
Time |
14:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-06-05 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-06-05 |
Time |
17:19 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-05-01 |
Time |
10:01 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2018-08-14 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-08-14 |
Time |
16:09 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-08-14 |
Time |
16:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2018-06-05 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-06-05 |
Time |
17:11 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-06-05 |
Time |
17:01 |
Sent To |
|
|
| Notes |
| 2018-06-05 17:12:01 | BUILDING PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER, PX3169 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT | | | FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID. | | | UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE | | | SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN | | | IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP | | | AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE | | | CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN | | | BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY | | | IMPACT FEES AT (561) 233-5025. | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2018-08-14 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-08-14 |
Time |
16:10 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-08-14 |
Time |
16:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2018-08-01 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-08-01 |
Time |
15:24 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-08-01 |
Time |
15:24 |
Sent To |
|
|
| Notes |
| 2018-08-01 15:34:57 | 2ND REVIEW: FBC 2017 6TH ED. RESIDENTIAL | | | 2ND REVIEW FBC 2017 EXISTING BUILDING | | | | | | FBC 107 - PROVIDE AN HVAC EQUIPMENT SCHDULE OR | | | EQUPIMENT SPECIFICATIONS. | | | | | | PROVIDE AN EQUIPMENT SIZING CALCULATION: | | | R403.6.1 EQUIPMENT SIZING. | | | HEATING AND COOLING EQUIPMENT SHALL BE SIZED IN | | | ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT | | | LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR | | | OTHER APPROVED HEATING AND COOLING CALCULATION | | | METHODOLOGIES, BASED ON BUILDING LOADS FOR THE | | | DIRECTIONAL ORIENTATION OF THE BUILDING. THE | | | MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR | | | UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH | | | THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN | | | CONDITIONS DESCRIBED IN SECTION R302.1. THIS CODE DOES | | | NOT ALLOW DESIGNER SAFETY FACTORS, PROVISIONS FOR | | | FUTURE EXPANSION OR OTHER FACTORS WHICH AFFECT | | | EQUIPMENT SIZING. SYSTEM SIZING CALCULATIONS SHALL NOT | | | INCLUDE LOADS CREATED BY LOCAL INTERMITTENT MECHANICAL | | | VENTILATION SUCH AS STANDARD KITCHEN AND BATHROOM | | | EXHAUST SYSTEMS. | | | | | | R403.6.1.1 COOLING EQUIPMENT CAPACITY. | | | COOLING ONLY EQUIPMENT SHALL BE SELECTED SO THAT ITS | | | TOTAL CAPACITY IS NOT LESS THAN THE CALCULATED TOTAL | | | LOAD, BUT NOT MORE THAN 1.15 TIMES GREATER THAN THE | | | TOTAL LOAD CALCULATED ACCORDING TO THE PROCEDURE | | | SELECTED IN SECTION 403.6, OR THE CLOSEST AVAILABLE | | | SIZE PROVIDED BY THE MANUFACTURER?S PRODUCT LINES. THE | | | CORRESPONDING LATENT CAPACITY OF THE EQUIPMENT SHALL | | | NOT BE LESS THAN THE CALCULATED LATENT LOAD. | | | | | | STEVEN KENNEDY, CBO | | | ASSISTANT BUILDING OFFICIAL | | | (561) 805-6710 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2018-05-17 |
|
|
Cont ID |
|
| Sent By |
cmontell |
Date |
2018-05-17 |
Time |
14:38 |
Rev Time |
0.00 |
| Received By |
cmontell |
Date |
2018-05-17 |
Time |
14:37 |
Sent To |
|
|
| Notes |
| 2018-05-17 14:38:15 | NEED CORRECT ADDRESS ON PLANS | | | | | | CHRIS MONTELLO | | | 561-805-6733 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2018-10-18 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-10-18 |
Time |
10:30 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-10-18 |
Time |
10:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
N |
Date |
2018-08-01 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-08-01 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-08-01 |
Time |
14:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2018-06-05 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2018-06-05 |
Time |
16:51 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2018-06-05 |
Time |
16:51 |
Sent To |
|
|
| Notes |
| 2018-06-05 16:56:36 | 06/05/2018 1ST PLUMBING REVIEW**DENIED** | | | | | | 1) ADDRESS ON PLAN 361 COLONY ROAD IS INCORRECT. ACTUAL | | | CORRECT ADDRESS AND PER PERMIT APPLICATION IS 361 | | | COLONIAL RD. FBC 107.2.1 | | | | | | 2) VALUE SEEMS LOW. PROVIDED SIGNED BONA FIDE CONTRACT. | | | 109.3BUILDING PERMIT VALUATIONS. | | | THE APPLICANT FOR A PERMIT SHALL PROVIDE AN ESTIMATED | | | PERMIT VALUE AT TIME OF APPLICATION. PERMIT VALUATIONS | | | SHALL INCLUDE TOTAL VALUE OF WORK, INCLUDING MATERIALS | | | AND LABOR, FOR WHICH THE PERMIT IS BEING ISSUED, SUCH | | | AS ELECTRICAL, GAS, MECHANICAL, PLUMBING EQUIPMENT AND | | | PERMANENT SYSTEMS. IF, IN THE OPINION OF THE BUILDING | | | OFFICIAL, THE VALUATION IS UNDERESTIMATED ON THE | | | APPLICATION, THE PERMIT SHALL BE DENIED, UNLESS THE | | | APPLICANT CAN SHOW DETAILED ESTIMATES TO MEET THE | | | APPROVAL OF THE BUILDING OFFICIAL. FINAL BUILDING | | | PERMIT VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. | | | | | | 3) ACCESS TO WASHING MACHINE SHUT OFF VALVE SHALL | | | REMAIN. FBC R P2903.9.3 | | | | | | | | | TIM HUNT | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | 561-805-6695 | | | [email protected] | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
N |
Date |
2018-08-01 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-08-01 |
Time |
14:44 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-08-01 |
Time |
14:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
PG |
Date |
2018-05-14 |
Time |
|
Rev Time |
0.00 |
| Received By |
pgreilic |
Date |
2018-05-11 |
Time |
14:25 |
Sent To |
|
|
| Notes |
| 2018-05-14 16:18:43 | 1.) PLEASE CORRECT PROJECT ADDRESS ON ALL PLANS | | | | | | PAUL GREILICH, SENIOR PLANNER | | | 561-822-1443 | | | [email protected] |
|
|