| 2018-08-20 14:44:08 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| | |
| | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| | INSPECTION. |
| | |
| | |
| | 1) SHEET FP 0 - THERE IS A NOTE INDICATING AN |
| | ELECTRICAL AUDIO ALARM BELL. |
| | |
| | THE FIRE SPRINKLER SYSTEM IS REQUIRED TO BE MONITORED |
| | PER NFPA 101, CHAPTER 30, NEW APARTMENT BUILDINGS. |
| | |
| | 30.3.4.2.3 IN BUILDINGS PROTECTED THROUGHOUT BY AN |
| | APPROVED, |
| | SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| | WITH 30.3.5, |
| | REQUIRED FIRE ALARM SYSTEMS SHALL BE INITIATED UPON |
| | OPERATION OF |
| | THE AUTOMATIC SPRINKLER SYSTEM. |
| | |
| | PLEASE ENSURE COMPLAINCE. |
| | |
| | |
| | |
| | 2) SHEET FP 02 - THERE IS AN INDICATION OF A CEILING |
| | FAN IN CLOSE PROXIMITY OF A SIDE WALL SPRINKLER HEAD. |
| | |
| | PLEASE ENSURE THAT THE CEILING FAN DOES NOT CREATE AN |
| | OBSTRUCTION PER NFPA 13 |
| | |
| | 8.7.5.2.1.6* SPRINKLERS SHALL BE PERMITTED TO BE PLACED |
| | WITHOUT |
| | REGARD TO THE BLADES OF CEILING FANS LESS THAN 60 IN. |
| | (1.5 M) IN |
| | DIAMETER, PROVIDED THE PLAN VIEW OF THE FAN IS AT LEAST |
| | 50 PERCENT |
| | OPEN. |
| | |
| | |
| | |
| | 3) SHEET FP 5 - A SPRINKLER HEAD IS INDICATED AT THE |
| | TOP OF THE ELEVATOR SHAFT. |
| | |
| | 8.15.5.3 AUTOMATIC FIRE SPRINKLERS SHALL NOT BE |
| | REQUIRED IN ELEVATOR |
| | MACHINE ROOMS, ELEVATOR MACHINERY SPACES, CONTROL |
| | SPACES, OR |
| | HOISTWAYS OF TRACTION ELEVATORS INSTALLED IN ACCORDANCE |
| | WITH THE |
| | APPLICABLE PROVISIONS IN NFPA 101, OR THE APPLICABLE |
| | BUILDING |
| | CODE, WHERE ALL OF THE FOLLOWING CONDITIONS ARE MET: |
| | (1) THE ELEVATOR MACHINE ROOM, MACHINERY SPACE, CONTROL |
| | ROOM, CONTROL SPACE, OR HOISTWAY OF TRACTION ELEVATOR |
| | IS |
| | DEDICATED TO ELEVATOR EQUIPMENT ONLY. |
| | (2) THE ELEVATOR MACHINE ROOM, MACHINE ROOM, MACHINERY |
| | SPACE, CONTROL ROOM, CONTROL SPACE, OR HOISTWAY OF |
| | TRACTION |
| | ELEVATORS ARE PROTECTED BY SMOKE DETECTORS, OR OTHER |
| | AUTOMATIC |
| | FIRE DETECTION, INSTALLED IN ACCORDANCE WITH NFPA72. |
| | (3) THE ELEVATOR MACHINERY SPACE, CONTROL ROOM, CONTROL |
| | SPACE, |
| | OR HOISTWAY OF TRACTION ELEVATORS IS SEPARATED FROM THE |
| | REMAINDER |
| | OF THE BUILDING BY WALLS AND FLOOR/CEILING OR ROOF/ |
| | CEILING ASSEMBLIES HAVING A FIRE RESISTANCE RATING OF |
| | NOT LESS |
| | THAN THAT SPECIFIED BY THE APPLICABLE BUILDING CODE. |
| | (4) NO MATERIALS UNRELATED TO ELEVATOR EQUIPMENT ARE |
| | PERMITTED |
| | TO BE STORED IN ELEVATOR MACHINE ROOMS, MACHINERY |
| | SPACES, CONTROL ROOMS, CONTROL SPACES, OR HOISTWAYS OF |
| | TRACTION |
| | ELEVATORS. |
| | (5) THE ELEVATOR MACHINERY IS NOT OF THE HYDRAULIC |
| | TYPE. |
| | |
| | 8.15.5.4* AUTOMATIC SPRINKLERS IN ELEVATOR MACHINE |
| | ROOMS OR |
| | AT THE TOPS OF HOISTWAYS SHALL BE OF ORDINARY- OR |
| | INTERMEDIATETEMPERATURE |
| | RATING. |
| | 8.15.5.5* UPRIGHT, PENDENT, OR SIDEWALL SPRAY |
| | SPRINKLERS SHALL |
| | BE INSTALLED AT THE TOP OF ELEVATOR HOISTWAYS. |
| | 8.15.5.6 THE SPRINKLER REQUIRED AT THE TOP OF THE |
| | ELEVATOR HOISTWAY |
| | BY 8.15.5.5 SHALL NOT BE REQUIRED WHERE THE HOISTWAY |
| | FOR PASSENGER |
| | ELEVATORS IS NONCOMBUSTIBLE OR LIMITED-COMBUSTIBLE AND |
| | THE CAR ENCLOSURE MATERIALS MEET THE REQUIREMENTS OF |
| | ASME |
| | A17.1, SAFETY CODE FOR ELEVATORS AND ESCALATORS. |
| | |
| | PLEASE ENSURE THAT THE SPRINKLER HEAD IS REQUIRED AT |
| | THIS LOCATION. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |