Plan Review Details - Permit 18041299
Plan Review Stops For Permit 18041299
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-07-02 Cont ID  
Sent By jgomez Date 2018-07-02 Time 09:45 Rev Time 0.00
Received By jgomez Date 2018-07-02 Time 09:14 Sent To  
Notes
2018-07-02 09:45:14SHELL ONLY,

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-06-05 Cont ID  
Sent By jgomez Date 2018-06-05 Time 09:38 Rev Time 0.00
Received By jgomez Date 2018-06-05 Time 08:42 Sent To  
Notes
2018-06-05 08:51:07SHELL ONLY,

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-05-21 Cont ID  
Sent By jgomez Date 2018-05-18 Time 19:23 Rev Time 0.00
Received By jgomez Date 2018-05-18 Time 19:14 Sent To  
Notes
2018-05-18 19:14:58SHELL ONLY, BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- PROVIDE ALL THE WIND DESIGN DATA AS REQUIRED BY SEC.
 1603.1.4 FBC.
  
 SEC. 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
 1.ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 2.RISK CATEGORY.
 3.WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE THAN
 ONE WIND EXPOSURE IS UTILIZED.
 4.APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5.DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF
 (KN/M2).
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR THE NEW EXTERIOR DOOR #1.
  
 3- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-06-28 Cont ID  
Sent By ppetty Date 2018-06-28 Time 09:12 Rev Time 0.00
Received By ppetty Date 2018-06-28 Time 09:10 Sent To  
Notes
2018-06-28 09:12:00CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: OK SEE NOTE AND STAMP, SEE
 COMMENTS BELOW.
  
 1. OK
 2. OK
 3. PROVIDE AIC RATING OF NEW PANEL. NEC 110.3, 110.9
 4. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 5.
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER, CHIEF ELECTRICAL INSPECTOR
 561-805-6742
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-06-06 Cont ID  
Sent By ppetty Date 2018-06-06 Time 09:19 Rev Time 0.00
Received By ppetty Date 2018-06-05 Time 15:01 Sent To P
Notes
2018-06-06 09:19:22CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. OK
 2. RISER DIAGRAM SHOWS A NEW PANEL B, BUT THIS PANEL IS
 NOT SHOWN ON THE PLAN. SHOW LOCATION OF ALL ELECTRICAL
 PANELS ON PLAN. ALSO, PROVIDE PANEL SCHEDULE FOR PANEL
 B WITH A LOAD CALCULATION. WPB FBC 107.2.1; NEC 215.5,
 220, 408.4
 3. PROVIDE AIC RATING OF NEW PANEL. NEC 110.3, 110.9
 4. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 5. PROVIDE GFCI PROTECTION FOR DRINKING FOUNTAIN. NEC
 422.52
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER, CHIEF ELECTRICAL INSPECTOR
 561-805-6742
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-05-09 Cont ID  
Sent By jpearson Date 2018-05-09 Time 13:44 Rev Time 0.00
Received By jpearson Date 2018-05-09 Time 10:29 Sent To  
Notes
2018-05-09 13:44:31CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLANS MUST BE SUBMITTED AS 2 COMPLETE SETS ONE SET
 IS MISSING THE MECHANICAL DRAWING BUT HAS 2 OF THE SAME
 ELECTRICAL SHEETS IN THE SAME SET. PROVIDE CORRECTION.
 WPB FBC 107.2.1
 2. RISER DIAGRAM SHOWS A NEW PANEL B, BUT THIS PANEL IS
 NOT SHOWN ON THE PLAN. SHOW LOCATION OF ALL ELECTRICAL
 PANELS ON PLAN. ALSO, PROVIDE PANEL SCHEDULE FOR PANEL
 B WITH A LOAD CALCULATION. WPB FBC 107.2.1; NEC 215.5,
 220, 408.4
 3. PROVIDE AIC RATING OF NEW PANEL. NEC 110.3, 110.9
 4. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 5. PROVIDE GFCI PROTECTION FOR DRINKING FOUNTAIN. NEC
 422.52
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-06-27 Cont ID  
Sent By scaldero Date 2018-06-27 Time 10:50 Rev Time 0.00
Received By scaldero Date 2018-06-27 Time 10:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-06-04 Cont ID  
Sent By scaldero Date 2018-06-04 Time 12:37 Rev Time 0.00
Received By scaldero Date 2018-06-04 Time 12:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-05-01 Cont ID  
Sent By scaldero Date 2018-05-01 Time 11:52 Rev Time 0.00
Received By scaldero Date 2018-05-01 Time 11:49 Sent To  
Notes
2018-05-01 11:52:36PERMIT # 18041299
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED WITH COMMENTS:
  
 1) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 2) PERMIT IS FOR SHELL ONLY.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-07-13 Cont ID  
Sent By gjohnson Date 2018-07-13 Time 14:31 Rev Time 0.00
Received By gjohnson Date 2018-06-25 Time 15:27 Sent To  
Notes
2018-06-26 15:27:53B17

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-06-12 Cont ID  
Sent By gjohnson Date 2018-06-12 Time 14:48 Rev Time 0.00
Received By gjohnson Date 2018-05-24 Time 13:34 Sent To  
Notes
2018-05-25 13:34:35B12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-21 Cont ID  
Sent By jgomez Date 2018-05-18 Time 19:24 Rev Time 0.00
Received By jgomez Date 2018-04-27 Time 14:30 Sent To I
Notes
2018-04-30 14:30:37B11

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2018-05-18 Cont ID  
Sent By jgomez Date 2018-05-18 Time 19:23 Rev Time 0.00
Received By jgomez Date 2018-05-17 Time 15:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-06-28 Cont ID  
Sent By ccole Date 2018-06-28 Time 12:13 Rev Time 0.00
Received By ccole Date 2018-06-28 Time 11:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-05-29 Cont ID  
Sent By ccole Date 2018-05-29 Time 11:44 Rev Time 0.00
Received By ccole Date 2018-05-29 Time 11:44 Sent To  
Notes
2018-05-29 11:46:082ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18041299
 5/29/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) WIND LOAD ENGINEERING IS REQUIRED FOR INSTALLATION
 OF THE NEW 5-TON RTU- SECTION 301.15. PLEASE PROVIDE
 THE DESIGN CRITERIA AND INSTALLATION DETAILS ON THE
 PLAN.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-05-09 Cont ID  
Sent By ccole Date 2018-05-09 Time 16:56 Rev Time 0.00
Received By ccole Date 2018-05-09 Time 16:56 Sent To  
Notes
2018-05-09 17:14:431ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18041299
 5/9/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS C-1 & 4.0M: MECHANICAL NOTES #1 & #5 ON C-1
 SEEM TO INDICATE (3) 5-TON AC SYSTEMS WILL BE
 INSTALLED, HOWEVER THE PLAN SHOWS (2).
  
 2) REPLACEMENT OF THE AC SYSTEMS ARE NOT EXACT SAME
 SIZE REPLACEMENTS SO COOLING AND HEATING CALCULATIONS
 ARE REQUIRED TO VERIFY ACCURATE SIZING- SECTION
 C403.2.1 FBC-14 ENERGY CONSERVATION.
  
 3) 4.0M: PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION
 OF THE NEW ROOFTOP UNITS ON THE EXISTING CURBS. IF
 USING CURB ADAPTERS PLEASE INCLDUE THEM IN THE DETAILS
 AND SUBMIT SPECS- SECTION 301.15 FBC-17 MECHANICAL.
  
 4) SHEET C-1, NOTE 3 & SHEET 4.0M: SHOW THE LOCATIONS
 OF THE ROOFTOP HOODS AND PROVIDE CAPPING DETAILS.
  
 5) 4.0M: DUCT SMOKE DETECTORS ARE REQUIRED IN THE
 SUPPLY SYSTEMS OF THE NEW 5-TON RTU'S , UNLESS
 MANUFACTURER'S SPECIFICATIONS INDICATE THE SYSTEMS
 CANNOT PRODUCE OVER 2000 CFMS OF SUPPLY AIR- SECTION
 606.2.1.
  
 6) ONE SET OF PLANS IS MISSING THE 4.0M SHEET.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-07-13 Cont ID  
Sent By gjohnson Date 2018-07-13 Time 14:30 Rev Time 0.00
Received By gjohnson Date 2018-07-13 Time 14:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-06-12 Cont ID  
Sent By gjohnson Date 2018-06-12 Time 14:44 Rev Time 0.00
Received By gjohnson Date 2018-06-12 Time 14:44 Sent To  
Notes
2018-06-12 14:48:442ND REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED WITH
  
 1. PLEASE PROVIDE WATER ISOMETRIC DRAWING. AMEND TO FBC
 107.3.5.1.3(3)(13)
  
 2. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA PER FBC PL 416.5
  
 3. IS THE WATER HEATER EXISTING IF NEW PROVIDE
 MANUFACTURE SPECS. PER AMEND TO FBC 107.2.1
  
 NEW COMMENT THE NEW WATER FOUNTAIN SHALL CONNECT DOWN
 STREAM OF THE BATHROOM GROUP. PER FBC PL 912.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-05-17 Cont ID  
Sent By gjohnson Date 2018-05-17 Time 13:32 Rev Time 0.00
Received By gjohnson Date 2018-05-17 Time 11:40 Sent To  
Notes
2018-05-17 13:46:361ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE WATER ISOMETRIC DRAWING. AMEND TO FBC
 107.3.5.1.3(3)(13)
  
 2. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA PER FBC PL 416.5
  
 3. IS THE WATER HEATER EXISTING IF NEW PROVIDE
 MANUFACTURE SPECS. PER AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2018-07-12 Cont ID  
Sent By eschneid Date 2018-07-12 Time 09:58 Rev Time 0.25
Received By eschneid Date 2018-07-02 Time 10:28 Sent To P
Notes
2018-07-12 09:58:48PROPOSED REPLACEMENT A/C IS SMALLER THAN EXISTING UNIT,
 SO IT IS A LOWER PROFILE, REDUCING THE NON-CONFORMITY.
 PAINT UNIT WITH SKY PATTERN AS SCREENING.

Review Stop Z ZONING
Rev No 2 Status F Date 2018-05-31 Cont ID  
Sent By eschneid Date 2018-05-31 Time 15:24 Rev Time 0.25
Received By eschneid Date 2018-05-31 Time 15:20 Sent To  
Notes
2018-05-31 15:27:12FAILED
  
 1) REPEAT COMMENT: RESOLUTION NO. 358-16 REQUIRES THAT
 WITHIN VILLAGE COMMONS, ALL NEW MECHANICAL EQUIPMENT,
 WHETHER GROUND OR ROOF MOUNTED, MUST BE SCREENED FROM
 VIEW OF THE PUBLIC. PLEASE PROVIDE VERIFICATION THAT
 THE NEW 5 TON ROOF MOUNTED RTU MEETS THIS REQUIREMENT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2018-05-15 Cont ID  
Sent By eschneid Date 2018-05-15 Time 10:50 Rev Time 0.25
Received By eschneid Date 2018-05-15 Time 10:50 Sent To  
Notes
2018-05-15 10:50:11FAILED
  
 1) RESOLUTION NO. 358-16 REQUIRES THAT WITHIN VILLAGE
 COMMONS, ALL NEW MECHANICAL EQUIPMENT, WHETHER GROUND
 OR ROOF MOUNTED, MUST BE SCREENED FROM VIEW OF THE
 PUBLIC. PLEASE PROVIDE VERIFICATION THAT THE TWO NEW
 ROOF MOUNTED RTU(S) MEET THIS REQUIREMENT.
  
 2) SHEET 4.0M (ONLY ONE PROVIDED) DOES NOT SHOW THE
 TENANT BAY THAT IS PART OF THIS PERMIT, BUT RATHER THE
 ADJACENT TENANT BAY (PERMIT 18041305). ALL PERMITS MUST
 SHOW ACCURATE LOCATION.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]