Plan Review Details - Permit 18041247
Plan Review Stops For Permit 18041247
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-07-05 Cont ID  
Sent By shill Date 2018-07-05 Time 09:03 Rev Time 0.00
Received By shill Date 2018-07-05 Time 09:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-06-16 Cont ID  
Sent By shill Date 2018-06-16 Time 18:58 Rev Time 0.00
Received By shill Date 2018-06-16 Time 18:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-05-23 Cont ID  
Sent By shill Date 2018-05-23 Time 07:17 Rev Time 0.00
Received By shill Date 2018-05-23 Time 06:12 Sent To  
Notes
2018-05-23 07:17:19****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC B TABLE 307.1, REVISE PLAN TO INCLUDE HAZARDOUS
 MATERIALS USED IN THE P & O MANUFACTURING PROCESS.
 PROVIDE A LIST OF MATERIALS USED AND AMOUNTS WHICH WILL
 BE STORED ON SITE.
  
 2. PROVIDE CONSTRUCTION VALUE FOR EACH SUITE; SEPARATE
 PERMITS ARE REQUIRED FOR EACH SUITE TO PROPERLY TRACK
 INSPECTIONS, FBC 107.
  
 3. THE PRODUCT APPROVAL FOR THE STOREFRONT IS
 INCOMPLETE; PROVIDE THE FLORIDA STATE PRODUCT APPROVAL
 COVER SHEET, FBC B 1609.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-06-27 Cont ID  
Sent By jpearson Date 2018-06-27 Time 14:46 Rev Time 0.00
Received By jpearson Date 2018-06-27 Time 14:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-06-18 Cont ID  
Sent By jpearson Date 2018-06-18 Time 16:10 Rev Time 0.00
Received By jpearson Date 2018-06-18 Time 16:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-05-20 Cont ID  
Sent By jpearson Date 2018-05-20 Time 11:24 Rev Time 0.00
Received By jpearson Date 2018-05-20 Time 11:24 Sent To  
Notes
2018-05-20 11:24:53PASS WITH PROVISO NOTED ON PLAN.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-07-06 Cont ID  
Sent By pleduc Date 2018-07-06 Time   Rev Time 0.00
Received By pleduc Date 2018-07-06 Time 13:47 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-06-12 Cont ID  
Sent By pleduc Date 2018-06-12 Time   Rev Time 0.00
Received By pleduc Date 2018-06-12 Time 11:52 Sent To  
Notes
2018-06-12 12:06:352ND REVIEW COMMENTS
  
 THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THERE ARE SOME EXIT SIGNS INDICATED ON THE LIFE
 SAFETY PALN AND NOT ON THE ELECTRICAL SHEETS
  
 PLEASE ENSURE EXIT SIGNS ARE INSTALLED CONSISTENT PER
 THE LIFE SAFETY PLAN.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-05-04 Cont ID  
Sent By pleduc Date 2018-05-04 Time   Rev Time 0.00
Received By pleduc Date 2018-05-04 Time 14:28 Sent To  
Notes
2018-05-04 14:34:05THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THERE ARE NO EXIT SIGNS INDICATED ON THE ELECTRICAL
 SHEETS BUT THEY ARE INDICATED ON THE LIFE SAFETY PLAN.
  
 PLEASE ENSURE EXIT SIGNS ARE INSTALLED PER THE LIFE
 SAFETY PLAN.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-07-06 Cont ID  
Sent By lmarchan Date 2018-07-06 Time 13:54 Rev Time 0.00
Received By lmarchan Date 2018-06-22 Time 12:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-06-19 Time   Rev Time 0.00
Received By lmarchan Date 2018-06-07 Time 10:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-25 Cont ID  
Sent By gjohnson Date 2018-05-25 Time 11:21 Rev Time 0.00
Received By gjohnson Date 2018-05-02 Time 15:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2018-07-03 Cont ID  
Sent By ccole Date 2018-07-03 Time 11:27 Rev Time 0.00
Received By ccole Date 2018-07-03 Time 11:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2018-06-29 Cont ID  
Sent By ccole Date 2018-06-29 Time 13:19 Rev Time 0.00
Received By ccole Date 2018-06-29 Time 12:44 Sent To  
Notes
2018-06-29 13:33:504TH REVIEW FBC-2017 MECHANICAL
 PERMIT #18041247
 6/29/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) COMMENT #6 FROM THE 3RD REVIEW HAS NOT BEEN
 COMPLETELY ADDRESSED- "LABS"ARE STILL SHOWN ON THE LIFE
 SAFETY PLAN, AND ALL OF THE ARCHITECTURAL PLANS. EITHER
 MATCH ALL ROOM ID'S ON THOSE PLAN SHEETS WITH THE MEP
 PLAN SHEETS, OR AS PREVIOUSLY REQUESTED, PROVIDE AN
 EXHAUST SYSTEM FOR THE LAB ROOM PER TABLE 403.3.1.1.
 SEE PREVIOUS COMMENT #6 BELOW.
  
 6) THE LIFE SAFETY PLAN ALS1.1, AND ARCHITECTURAL,
 PLUMBING AND ELECTRICAL PLANS ARE IDENTIFYING THE LARGE
 WORK AREA AS A "LAB" WHICH CONFLICTS WITH THE
 ARCHITECT'S ASSERTION THAT THIS IS A WORK AREA. REFER
 TO SECTIONS 510.1 AND 510.2 FBC M AND PROVIDE A LIST OF
 ALL CHEMICALS AND THEIR QUANTITIES TO BE USED AND
 STORED AT THE FACILITY AND PROVIDE MSDS SHEETS FOR
 EACH. PLEASE NOTE A HAZARDOUS EXHAUST SYSTEM MAY BE
 REQUIRED PER SECTION 510.2. IF THE WORK AREA IS NOT
 CONSIDERED A "LAB" PLEASE CORRECTLY IDENTIFY THE ROOM
 ON ALL PLAN SHEETS AND PROVIDE A NARRATIVE THAT
 CLARIFIES WHAT PROCESSES TAKE PLACE IN THE ROOM, AND
 WHAT, IF ANY CHEMICALS AND THEIR QUANTITIES ARE USED IN
 THE PROCESSES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2018-06-14 Cont ID  
Sent By ccole Date 2018-06-14 Time 11:26 Rev Time 0.00
Received By ccole Date 2018-06-14 Time 10:09 Sent To  
Notes
2018-06-14 11:28:503RD REVIEW FBC-2017 MECHANICAL
 PERMIT #18041247
 6/14/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M6.1: REFER TO SECTION 403.3.1.1 AND TABLE
 403.3.1 AND REVISE THE O/A CALCULATIONS TO INCLUDE THE
 WORK AREA, THE MACHINE AND PLASTER ROOMS. THE MOST
 SIMILAR OCCUPANCY IN THE TABLE WOULD BE WOOD/METAL
 SHOPS WHICH REQUIRES O/A RATES BASED ON (20 PERSONS PER
 1000 SQ. FT.) AT (10 CFMS PER PERSON) AND (0.18 CFMS
 PER SQ. FT.). PLEASE SEE FOOTNOTE G WHICH PROHIBITS
 RECIRCULATION OF AIR FROM THOSE ROOMS AND SPACES.
 UPDATE THE 2014 CODE REFERENCE LISTED UNDER THE TABLE
 TO THE 2017 EDITION OF THE MECHANICAL CODE.
  
 2) SHEET M2.1 & M6.1: PLEASE LABEL OR IDENTIFY ALL OF
 THE WORK ROOMS SO THEY MATCH THE IDENTIFICATIONS LISTED
 IN THE AIR BALANCE SCHEDULE.
  
 3) M6.1: PROVIDE EXHAUST VENTILATION CALCULATION PER
 TABLE 403.3.1 FBC M WHICH REQUIRES A RATE OF 0.50 CFMS
 PER SQ. FT. FOR THE WORK AND MACHINE ROOMS.
  
 4) M2.1: AS NOTED IN COMMENT #1 ABOVE, RECIRCULATION OF
 AIR FROM THE WORK ROOM, MACHINE ROOM ETC. IS PROHIBITED
 EXCEPT THAT RECIRCULATION SHALL BE PERMITTED WHERE THE
 RESULTING SUPPLY AIRSTREAM CONSISTS OF NOT MORE THAN 10
 PERCENT AIR RECIRCULATED FROM THESE SPACES. PLEASE
 REVISE THE LAYOUT PLAN ACCORDINGLY.
  
 5) M6.1: REFER TO SECTION 501.4 FBC M AS IT APPLIES TO
 THE MACHINE ROOM WHICH APPEARS NOT TO BE AT NEUTRAL OR
 NEGATIVE PRESSURE. PLEASE NOTE THAT THE AIR BALANCE
 TABLE IS ALSO NOT SHOWING ANY TRANSFER AIR CFMS.
  
 6) THE LIFE SAFETY PLAN ALS1.1, AND ARCHITECTURAL,
 PLUMBING AND ELECTRICAL PLANS ARE IDENTIFYING THE LARGE
 WORK AREA AS A "LAB" WHICH CONFLICTS WITH THE
 ARCHITECT'S ASSERTION THAT THIS IS A WORK AREA. REFER
 TO SECTIONS 510.1 AND 510.2 FBC M AND PROVIDE A LIST OF
 ALL CHEMICALS AND THEIR QUANTITIES TO BE USED AND
 STORED AT THE FACILITY AND PROVIDE MSDS SHEETS FOR
 EACH. PLEASE NOTE A HAZARDOUS EXHAUST SYSTEM MAY BE
 REQUIRED PER SECTION 510.2. IF THE WORK AREA IS NOT
 CONSIDERED A "LAB" PLEASE CORRECTLY IDENTIFY THE ROOM
 ON ALL PLAN SHEETS AND PROVIDE A NARRATIVE THAT
 CLARIFIES WHAT PROCESSES TAKE PLACE IN THE ROOM, AND
 WHAT, IF ANY CHEMICALS AND THEIR QUANTITIES ARE USED IN
 THE PROCESSES.
  
 7) PLEASE CLARIFY THE PURPOSE OF THE NEW FIRE DAMPERS
 TO BE INSTALLED WHERE THE EXISTING DUCT IS PENETRATING
 THE OFFICE 122 WALLS. THE ARCHITECTURAL PLANS ARE NOT
 SHOWING THESE WALLS TO BE FIRE-RATED.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-06-13 Cont ID  
Sent By ccole Date 2018-06-13 Time 10:58 Rev Time 0.00
Received By ccole Date 2018-06-13 Time 10:58 Sent To  
Notes
2018-06-13 11:20:062ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18041247
 6/12/18
  
 CODES IN EFFECT:
 FBC BC- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC MC- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC RE- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC-SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) NO MECHANICAL PLANS WERE UPLOADED FOR REVIEW AS
 REQUESTED IN THE 1ST REVIEW. COPIED AND PRINTED BELOW
 ARE THE ARCHITECT'S RESPONSE TO THE 1ST REVIEW
 COMMENTS.
  
 MECHANICAL- CHRISTOPHER COLE
  
 COMMENT 1 PROVIDE MECHANICAL PLANS INCLUDING MINIMUM
 VENTILATION CALCULATIONS FOR ALL ROOMS AND SPACES, A
 DUCT LAYOUT PLAN SHOWING ALL NEW AND RELOCATED DUCTS
 AND DIFFUSERS, AND AN AIR DISTRIBUTION SCHEDULE FOR ALL
 NEW DUCTS, DIFFUSERS, AND RETURN GRILLS TO BE
 INSTALLED.
  
 RESPONSE: SEE ATTACHED MECHANICAL PLANS.
  
 COMMENT 2 THE PLANS INDICATE A NEW LAB TO BE INSTALLED
 WHICH WILL REQUIRE INSTALLATION OF AN EXHAUST
 VENTILATION SYSTEM WITH AN EXHAUST AIRFLOW RATE OF 1.0
 CFMS PER SF. RECIRCULATION OF AIR FROM THE SPACE IS
 PROHIBITED WITH AN EXCEPTION OF NOT MORE THAN 10% OF
 THE AIRFLOW STREAM FROM THE LAB- SEE FOOTNOTE G. PLEASE
 NOTE THAT EXHAUST VENTILATION SYSTEMS MAY BE REQUIRED
 FOR ALL OTHER ROOMS STORING OR PROCESSING CHEMICALS OR
 MATERIALS THAT GIVE OFF DUSTS OR FUMES- PLEASE REFER TO
 SECTION 414 FBC BC, AND SECTION 502.1 FBC MCL:
 502.1 GENERAL AND EXHAUST SYSTEM SHALL BE PROVIDED
 MAINTAINED AND OPERATED AS SPECIFICALLY REQUIRED BY
 THIS SECTION AND FOR ALL OCCUPIED AREAS WHERE MACHINES,
 VATS, TANKS, FURNACES, FORGES, SALAMANDERS AND OTHER
 APPLIANCES, EQUIPMENT AND PROCESSES IN SUCH AREAS
 PRODUCE OR THROW OFF DUST OR PARTICLES SUFFICIENTLY
 LIGHT TO FLOAT IN THE AIR, OR WHICH EMIT HEAT, ORDERS,
 FUMES SPRAY, GAS R SMOKE, IN SUCH QUANTITIES SO AS TO
 BE IRRITATING OR INJURIOUS TO HEALTH OR SAFETY. THE
 MECHANICAL REVIEW IS STOPPED AT THIS POINT PENDING
 SUBMITTAL OF COMPLETE PLANS AND SPECIFICATIONS.
  
 RESPONSE: AREA HAS BEEN RE-DESIGNATED AT WORK AREA.
 MACHINE ROOM HAS BEEN PROVIDED WITH AN EXHAUST FAN TO
 INSURE NO RETURN AIR FROM THIS AREA. (THIS IS BEYOND
 CODE REQUIREMENTS). ALSO, A SOURCE POINT DUST
 COLLECTION SYSTEM IS BEING PROVIDED BY THE TENANT. SEE
 ATTACHED CUT SHEET.
  
 VERY TRULY YOURS,
  
 KEITH M. SPINA
 SENIOR PARTNER
 P:\17\FLORIDA O&P PROSTHETICS-17288\PERMIT\2018-05-25
 BLDG DEPT COMMENTS\FLORIDA O&P RESPONSE LETTER.DOCX
  
  
 2) PLEASE NOTE THAT THE THE LIFE SAFETY PLAN- SHEET
 ALS1.1 AND THE ELECTRICAL AND PLUMBING PLANS ARE STILL
 IDENTIFYING THE ROOM IN QUESTION AS "LAB" WHICH IS NOT
 CONSISTENT WITH THE ARCHITECT'S CLAIM THAT THE ROOM HAS
 BEEN REDESIGNATED AS "WORK AREA".
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-05-24 Cont ID  
Sent By ccole Date 2018-05-24 Time 16:37 Rev Time 0.00
Received By ccole Date 2018-05-24 Time 16:37 Sent To  
Notes
2018-05-24 16:54:331ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18041247
 5/24/18
  
 CODES IN EFFECT:
 FBC BC- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC MC- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC RE- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC-SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE MECHANICAL PLANS INCLUDING MINIMUM
 VENTILATION CALCULATIONS FOR ALL ROOMS AND SPACES, A
 DUCT LAYOUT PLAN SHOWING ALL NEW AND RELOCATED DUCTS
 AND DIFFUSERS, AND AN AIR DISTRIBUTION SCHEDULE FOR ALL
 NEW DUCTS, DIFFUSERS, AND RETURN GRILLS TO BE
 INSTALLED.
  
 2) THE PLANS INDICATE A NEW LAB TO BE INSTALLED WHICH
 WILL REQUIRE INSTALLATION OF AN EXHAUST VENTILATION
 SYSTEM WITH AN EXHAUST AIRFLOW RATE OF 1.0 CFMS PER SF.
 RECIRCULARION OF AIR FROM THE SPACE IS PROHIBITED WITH
 AN EXCEPTION OF NOT MORE THAN 10% OF THE AIRFLOW STREAM
 FROM THE LAB- SEE FOOTNOTE G. PLEASE NOTE THAT EXHAUST
 VENTILATION SYSTEMS MAY BE REQUIRED FOR ALL OTHER ROOMS
  
 STORING OR PROCESSING CHEMICALS OR MATERIALS THAT GIVE
 OFF DUSTS OR FUMES- PLEASE REFER TO SECTION 414 FBC BC,
 AND SECTION 502.1 FBC MC:
  
 502.1 GENERAL.AN EXHAUST SYSTEM SHALL BE PROVIDED,
 MAINTAINED AND OPERATED AS SPECIFICALLY REQUIRED BY
 THIS SECTION AND FOR ALL OCCUPIED AREAS WHERE MACHINES,
 VATS, TANKS, FURNACES, FORGES, SALAMANDERS AND OTHER
 APPLIANCES, EQUIPMENT AND PROCESSES IN SUCH AREAS
 PRODUCE OR THROW OFF DUST OR PARTICLES SUFFICIENTLY
 LIGHT TO FLOAT IN THE AIR, OR WHICH EMIT HEAT, ODORS,
 FUMES, SPRAY,
  
 GAS OR SMOKE, IN SUCH QUANTITIES SO AS TO BE IRRITATING
 OR INJURIOUS TO HEALTH OR SAFETY.
  
 THE MECHANICAL REVIEW IS STOPPED AT THIS POINT PENDING
 SUBMITTAL OF COMPLETE PLANS AND SPECIFICATIONS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-07-05 Cont ID  
Sent By shill Date 2018-07-05 Time 15:19 Rev Time 0.00
Received By gjohnson Date 2018-07-05 Time 15:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-06-19 Cont ID  
Sent By gjohnson Date 2018-06-19 Time 14:01 Rev Time 0.00
Received By gjohnson Date 2018-06-19 Time 14:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-05-25 Cont ID  
Sent By gjohnson Date 2018-05-25 Time 11:21 Rev Time 0.00
Received By gjohnson Date 2018-05-25 Time 10:03 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2018-07-05 Cont ID  
Sent By shill Date 2018-07-05 Time 13:00 Rev Time 0.00
Received By shill Date 2018-07-05 Time 13:00 Sent To  
Notes
2018-07-05 13:00:38RECEIVED THE FOLLOWING S&S PAGES VIA EMAIL:
  
 AD1.0
 A2.1.1
 A3.1.1
 A4.1.1
 P0.1
 P5.1
 E0.1
 E5.1
  
 ALL OTHER PAGES ARE DIGITALLY SIGNED AND SEALED IN
 ACCORDANCE WITH FS471, FS481
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2018-07-05 Cont ID  
Sent By shill Date 2018-07-05 Time 09:08 Rev Time 0.00
Received By shill Date 2018-07-05 Time 09:08 Sent To  
Notes
2018-07-05 09:10:01SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 THE FOLLOWING PAGES ARE NOT SIGNED AND SEALED IN
 ACCORDANCE WITH FS471, FS481. PLEASE SEND SIGNED &
 SEALED PAGES DIRECTLY TO ME VIA EMAIL, [email protected]:
  
 AD1.0
 A2.1.1
 A3.1.1
 A4.1.1
 P0.1
 P5.1
 E0.1
 E5.1
  
  
2018-07-03 11:28:01MECH DIG/SIGS OK
 CCOLE- 7/3/18

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2018-06-16 Cont ID  
Sent By shill Date 2018-06-16 Time 19:01 Rev Time 0.00
Received By shill Date 2018-06-16 Time 19:01 Sent To  
Notes
2018-06-16 19:05:03****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 ALL PAGES WERE REPLACED, EVEN THE ONES WHICH DID NOT
 CHANGE. IN THE FUTURE PLEASE SUBMIT ONLY PAGES WHICH
 CHANGE AS SUBMITTING ALL NEW PAGES REQUIRES REVIEW OF
 ALL PAGES BY ALL TRADES. THIS SIGNIFICANTLY INCREASES
 PLAN REVIEW TIME.
  
 THE NEW A, P, E PAGES ARE NOT DIGITALLY SIGNED AND
 SEALED, FS471, FS481. IF B, FIRE, PLUMBING, ELECTRICAL
 PASS THIS REVIEW CYCLE, **DO NOT RESUBMIT NEW SHEETS**,
 CONTACT ME FOR INFORMATION ON HOW TO RESOLVE THIS
 ISSUE.
  
  
  
  
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-05-23 Cont ID  
Sent By shill Date 2018-05-23 Time 07:20 Rev Time 0.00
Received By shill Date 2018-05-23 Time 07:18 Sent To  
Notes
2018-05-23 07:21:15****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 ALL DIGITAL SIGNATURE/SEALS ARE IN ACCORDANCE WITH
 FS471, FS481, BUT NEW SHEETS SUBMITTED NEXT REVIEW
 CYCLE NEED REVIEW.
  
  