| Plan Review Stops For Permit 18041247 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2018-07-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-07-05 |
Time |
09:03 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-07-05 |
Time |
09:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2018-06-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-06-16 |
Time |
18:58 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-06-16 |
Time |
18:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-05-23 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-05-23 |
Time |
07:17 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-05-23 |
Time |
06:12 |
Sent To |
|
|
| Notes |
| 2018-05-23 07:17:19 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. FBC B TABLE 307.1, REVISE PLAN TO INCLUDE HAZARDOUS | | | MATERIALS USED IN THE P & O MANUFACTURING PROCESS. | | | PROVIDE A LIST OF MATERIALS USED AND AMOUNTS WHICH WILL | | | BE STORED ON SITE. | | | | | | 2. PROVIDE CONSTRUCTION VALUE FOR EACH SUITE; SEPARATE | | | PERMITS ARE REQUIRED FOR EACH SUITE TO PROPERLY TRACK | | | INSPECTIONS, FBC 107. | | | | | | 3. THE PRODUCT APPROVAL FOR THE STOREFRONT IS | | | INCOMPLETE; PROVIDE THE FLORIDA STATE PRODUCT APPROVAL | | | COVER SHEET, FBC B 1609. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2018-06-27 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-06-27 |
Time |
14:46 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-06-27 |
Time |
14:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2018-06-18 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-06-18 |
Time |
16:10 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-06-18 |
Time |
16:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2018-05-20 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-05-20 |
Time |
11:24 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-05-20 |
Time |
11:24 |
Sent To |
|
|
| Notes |
| 2018-05-20 11:24:53 | PASS WITH PROVISO NOTED ON PLAN. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2018-07-06 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-07-06 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-07-06 |
Time |
13:47 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2018-06-12 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-06-12 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-06-12 |
Time |
11:52 |
Sent To |
|
|
| Notes |
| 2018-06-12 12:06:35 | 2ND REVIEW COMMENTS | | | | | | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) THERE ARE SOME EXIT SIGNS INDICATED ON THE LIFE | | | SAFETY PALN AND NOT ON THE ELECTRICAL SHEETS | | | | | | PLEASE ENSURE EXIT SIGNS ARE INSTALLED CONSISTENT PER | | | THE LIFE SAFETY PLAN. | | | | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2018-05-04 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-05-04 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-05-04 |
Time |
14:28 |
Sent To |
|
|
| Notes |
| 2018-05-04 14:34:05 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) THERE ARE NO EXIT SIGNS INDICATED ON THE ELECTRICAL | | | SHEETS BUT THEY ARE INDICATED ON THE LIFE SAFETY PLAN. | | | | | | PLEASE ENSURE EXIT SIGNS ARE INSTALLED PER THE LIFE | | | SAFETY PLAN. | | | | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-07-06 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2018-07-06 |
Time |
13:54 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2018-06-22 |
Time |
12:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2018-06-19 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2018-06-07 |
Time |
10:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-05-25 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-05-25 |
Time |
11:21 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-05-02 |
Time |
15:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2018-07-03 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-07-03 |
Time |
11:27 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-07-03 |
Time |
11:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2018-06-29 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-06-29 |
Time |
13:19 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-06-29 |
Time |
12:44 |
Sent To |
|
|
| Notes |
| 2018-06-29 13:33:50 | 4TH REVIEW FBC-2017 MECHANICAL | | | PERMIT #18041247 | | | 6/29/18 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) COMMENT #6 FROM THE 3RD REVIEW HAS NOT BEEN | | | COMPLETELY ADDRESSED- "LABS"ARE STILL SHOWN ON THE LIFE | | | SAFETY PLAN, AND ALL OF THE ARCHITECTURAL PLANS. EITHER | | | MATCH ALL ROOM ID'S ON THOSE PLAN SHEETS WITH THE MEP | | | PLAN SHEETS, OR AS PREVIOUSLY REQUESTED, PROVIDE AN | | | EXHAUST SYSTEM FOR THE LAB ROOM PER TABLE 403.3.1.1. | | | SEE PREVIOUS COMMENT #6 BELOW. | | | | | | 6) THE LIFE SAFETY PLAN ALS1.1, AND ARCHITECTURAL, | | | PLUMBING AND ELECTRICAL PLANS ARE IDENTIFYING THE LARGE | | | WORK AREA AS A "LAB" WHICH CONFLICTS WITH THE | | | ARCHITECT'S ASSERTION THAT THIS IS A WORK AREA. REFER | | | TO SECTIONS 510.1 AND 510.2 FBC M AND PROVIDE A LIST OF | | | ALL CHEMICALS AND THEIR QUANTITIES TO BE USED AND | | | STORED AT THE FACILITY AND PROVIDE MSDS SHEETS FOR | | | EACH. PLEASE NOTE A HAZARDOUS EXHAUST SYSTEM MAY BE | | | REQUIRED PER SECTION 510.2. IF THE WORK AREA IS NOT | | | CONSIDERED A "LAB" PLEASE CORRECTLY IDENTIFY THE ROOM | | | ON ALL PLAN SHEETS AND PROVIDE A NARRATIVE THAT | | | CLARIFIES WHAT PROCESSES TAKE PLACE IN THE ROOM, AND | | | WHAT, IF ANY CHEMICALS AND THEIR QUANTITIES ARE USED IN | | | THE PROCESSES. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2018-06-14 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-06-14 |
Time |
11:26 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-06-14 |
Time |
10:09 |
Sent To |
|
|
| Notes |
| 2018-06-14 11:28:50 | 3RD REVIEW FBC-2017 MECHANICAL | | | PERMIT #18041247 | | | 6/14/18 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M6.1: REFER TO SECTION 403.3.1.1 AND TABLE | | | 403.3.1 AND REVISE THE O/A CALCULATIONS TO INCLUDE THE | | | WORK AREA, THE MACHINE AND PLASTER ROOMS. THE MOST | | | SIMILAR OCCUPANCY IN THE TABLE WOULD BE WOOD/METAL | | | SHOPS WHICH REQUIRES O/A RATES BASED ON (20 PERSONS PER | | | 1000 SQ. FT.) AT (10 CFMS PER PERSON) AND (0.18 CFMS | | | PER SQ. FT.). PLEASE SEE FOOTNOTE G WHICH PROHIBITS | | | RECIRCULATION OF AIR FROM THOSE ROOMS AND SPACES. | | | UPDATE THE 2014 CODE REFERENCE LISTED UNDER THE TABLE | | | TO THE 2017 EDITION OF THE MECHANICAL CODE. | | | | | | 2) SHEET M2.1 & M6.1: PLEASE LABEL OR IDENTIFY ALL OF | | | THE WORK ROOMS SO THEY MATCH THE IDENTIFICATIONS LISTED | | | IN THE AIR BALANCE SCHEDULE. | | | | | | 3) M6.1: PROVIDE EXHAUST VENTILATION CALCULATION PER | | | TABLE 403.3.1 FBC M WHICH REQUIRES A RATE OF 0.50 CFMS | | | PER SQ. FT. FOR THE WORK AND MACHINE ROOMS. | | | | | | 4) M2.1: AS NOTED IN COMMENT #1 ABOVE, RECIRCULATION OF | | | AIR FROM THE WORK ROOM, MACHINE ROOM ETC. IS PROHIBITED | | | EXCEPT THAT RECIRCULATION SHALL BE PERMITTED WHERE THE | | | RESULTING SUPPLY AIRSTREAM CONSISTS OF NOT MORE THAN 10 | | | PERCENT AIR RECIRCULATED FROM THESE SPACES. PLEASE | | | REVISE THE LAYOUT PLAN ACCORDINGLY. | | | | | | 5) M6.1: REFER TO SECTION 501.4 FBC M AS IT APPLIES TO | | | THE MACHINE ROOM WHICH APPEARS NOT TO BE AT NEUTRAL OR | | | NEGATIVE PRESSURE. PLEASE NOTE THAT THE AIR BALANCE | | | TABLE IS ALSO NOT SHOWING ANY TRANSFER AIR CFMS. | | | | | | 6) THE LIFE SAFETY PLAN ALS1.1, AND ARCHITECTURAL, | | | PLUMBING AND ELECTRICAL PLANS ARE IDENTIFYING THE LARGE | | | WORK AREA AS A "LAB" WHICH CONFLICTS WITH THE | | | ARCHITECT'S ASSERTION THAT THIS IS A WORK AREA. REFER | | | TO SECTIONS 510.1 AND 510.2 FBC M AND PROVIDE A LIST OF | | | ALL CHEMICALS AND THEIR QUANTITIES TO BE USED AND | | | STORED AT THE FACILITY AND PROVIDE MSDS SHEETS FOR | | | EACH. PLEASE NOTE A HAZARDOUS EXHAUST SYSTEM MAY BE | | | REQUIRED PER SECTION 510.2. IF THE WORK AREA IS NOT | | | CONSIDERED A "LAB" PLEASE CORRECTLY IDENTIFY THE ROOM | | | ON ALL PLAN SHEETS AND PROVIDE A NARRATIVE THAT | | | CLARIFIES WHAT PROCESSES TAKE PLACE IN THE ROOM, AND | | | WHAT, IF ANY CHEMICALS AND THEIR QUANTITIES ARE USED IN | | | THE PROCESSES. | | | | | | 7) PLEASE CLARIFY THE PURPOSE OF THE NEW FIRE DAMPERS | | | TO BE INSTALLED WHERE THE EXISTING DUCT IS PENETRATING | | | THE OFFICE 122 WALLS. THE ARCHITECTURAL PLANS ARE NOT | | | SHOWING THESE WALLS TO BE FIRE-RATED. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2018-06-13 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-06-13 |
Time |
10:58 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-06-13 |
Time |
10:58 |
Sent To |
|
|
| Notes |
| 2018-06-13 11:20:06 | 2ND REVIEW FBC-2017 MECHANICAL | | | PERMIT #18041247 | | | 6/12/18 | | | | | | CODES IN EFFECT: | | | FBC BC- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC MC- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC RE- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC-SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) NO MECHANICAL PLANS WERE UPLOADED FOR REVIEW AS | | | REQUESTED IN THE 1ST REVIEW. COPIED AND PRINTED BELOW | | | ARE THE ARCHITECT'S RESPONSE TO THE 1ST REVIEW | | | COMMENTS. | | | | | | MECHANICAL- CHRISTOPHER COLE | | | | | | COMMENT 1 PROVIDE MECHANICAL PLANS INCLUDING MINIMUM | | | VENTILATION CALCULATIONS FOR ALL ROOMS AND SPACES, A | | | DUCT LAYOUT PLAN SHOWING ALL NEW AND RELOCATED DUCTS | | | AND DIFFUSERS, AND AN AIR DISTRIBUTION SCHEDULE FOR ALL | | | NEW DUCTS, DIFFUSERS, AND RETURN GRILLS TO BE | | | INSTALLED. | | | | | | RESPONSE: SEE ATTACHED MECHANICAL PLANS. | | | | | | COMMENT 2 THE PLANS INDICATE A NEW LAB TO BE INSTALLED | | | WHICH WILL REQUIRE INSTALLATION OF AN EXHAUST | | | VENTILATION SYSTEM WITH AN EXHAUST AIRFLOW RATE OF 1.0 | | | CFMS PER SF. RECIRCULATION OF AIR FROM THE SPACE IS | | | PROHIBITED WITH AN EXCEPTION OF NOT MORE THAN 10% OF | | | THE AIRFLOW STREAM FROM THE LAB- SEE FOOTNOTE G. PLEASE | | | NOTE THAT EXHAUST VENTILATION SYSTEMS MAY BE REQUIRED | | | FOR ALL OTHER ROOMS STORING OR PROCESSING CHEMICALS OR | | | MATERIALS THAT GIVE OFF DUSTS OR FUMES- PLEASE REFER TO | | | SECTION 414 FBC BC, AND SECTION 502.1 FBC MCL: | | | 502.1 GENERAL AND EXHAUST SYSTEM SHALL BE PROVIDED | | | MAINTAINED AND OPERATED AS SPECIFICALLY REQUIRED BY | | | THIS SECTION AND FOR ALL OCCUPIED AREAS WHERE MACHINES, | | | VATS, TANKS, FURNACES, FORGES, SALAMANDERS AND OTHER | | | APPLIANCES, EQUIPMENT AND PROCESSES IN SUCH AREAS | | | PRODUCE OR THROW OFF DUST OR PARTICLES SUFFICIENTLY | | | LIGHT TO FLOAT IN THE AIR, OR WHICH EMIT HEAT, ORDERS, | | | FUMES SPRAY, GAS R SMOKE, IN SUCH QUANTITIES SO AS TO | | | BE IRRITATING OR INJURIOUS TO HEALTH OR SAFETY. THE | | | MECHANICAL REVIEW IS STOPPED AT THIS POINT PENDING | | | SUBMITTAL OF COMPLETE PLANS AND SPECIFICATIONS. | | | | | | RESPONSE: AREA HAS BEEN RE-DESIGNATED AT WORK AREA. | | | MACHINE ROOM HAS BEEN PROVIDED WITH AN EXHAUST FAN TO | | | INSURE NO RETURN AIR FROM THIS AREA. (THIS IS BEYOND | | | CODE REQUIREMENTS). ALSO, A SOURCE POINT DUST | | | COLLECTION SYSTEM IS BEING PROVIDED BY THE TENANT. SEE | | | ATTACHED CUT SHEET. | | | | | | VERY TRULY YOURS, | | | | | | KEITH M. SPINA | | | SENIOR PARTNER | | | P:\17\FLORIDA O&P PROSTHETICS-17288\PERMIT\2018-05-25 | | | BLDG DEPT COMMENTS\FLORIDA O&P RESPONSE LETTER.DOCX | | | | | | | | | 2) PLEASE NOTE THAT THE THE LIFE SAFETY PLAN- SHEET | | | ALS1.1 AND THE ELECTRICAL AND PLUMBING PLANS ARE STILL | | | IDENTIFYING THE ROOM IN QUESTION AS "LAB" WHICH IS NOT | | | CONSISTENT WITH THE ARCHITECT'S CLAIM THAT THE ROOM HAS | | | BEEN REDESIGNATED AS "WORK AREA". | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2018-05-24 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-05-24 |
Time |
16:37 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-05-24 |
Time |
16:37 |
Sent To |
|
|
| Notes |
| 2018-05-24 16:54:33 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #18041247 | | | 5/24/18 | | | | | | CODES IN EFFECT: | | | FBC BC- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC MC- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC RE- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC-SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE MECHANICAL PLANS INCLUDING MINIMUM | | | VENTILATION CALCULATIONS FOR ALL ROOMS AND SPACES, A | | | DUCT LAYOUT PLAN SHOWING ALL NEW AND RELOCATED DUCTS | | | AND DIFFUSERS, AND AN AIR DISTRIBUTION SCHEDULE FOR ALL | | | NEW DUCTS, DIFFUSERS, AND RETURN GRILLS TO BE | | | INSTALLED. | | | | | | 2) THE PLANS INDICATE A NEW LAB TO BE INSTALLED WHICH | | | WILL REQUIRE INSTALLATION OF AN EXHAUST VENTILATION | | | SYSTEM WITH AN EXHAUST AIRFLOW RATE OF 1.0 CFMS PER SF. | | | RECIRCULARION OF AIR FROM THE SPACE IS PROHIBITED WITH | | | AN EXCEPTION OF NOT MORE THAN 10% OF THE AIRFLOW STREAM | | | FROM THE LAB- SEE FOOTNOTE G. PLEASE NOTE THAT EXHAUST | | | VENTILATION SYSTEMS MAY BE REQUIRED FOR ALL OTHER ROOMS | | | | | | STORING OR PROCESSING CHEMICALS OR MATERIALS THAT GIVE | | | OFF DUSTS OR FUMES- PLEASE REFER TO SECTION 414 FBC BC, | | | AND SECTION 502.1 FBC MC: | | | | | | 502.1 GENERAL.AN EXHAUST SYSTEM SHALL BE PROVIDED, | | | MAINTAINED AND OPERATED AS SPECIFICALLY REQUIRED BY | | | THIS SECTION AND FOR ALL OCCUPIED AREAS WHERE MACHINES, | | | VATS, TANKS, FURNACES, FORGES, SALAMANDERS AND OTHER | | | APPLIANCES, EQUIPMENT AND PROCESSES IN SUCH AREAS | | | PRODUCE OR THROW OFF DUST OR PARTICLES SUFFICIENTLY | | | LIGHT TO FLOAT IN THE AIR, OR WHICH EMIT HEAT, ODORS, | | | FUMES, SPRAY, | | | | | | GAS OR SMOKE, IN SUCH QUANTITIES SO AS TO BE IRRITATING | | | OR INJURIOUS TO HEALTH OR SAFETY. | | | | | | THE MECHANICAL REVIEW IS STOPPED AT THIS POINT PENDING | | | SUBMITTAL OF COMPLETE PLANS AND SPECIFICATIONS. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2018-07-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-07-05 |
Time |
15:19 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-07-05 |
Time |
15:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2018-06-19 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-06-19 |
Time |
14:01 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-06-19 |
Time |
14:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2018-05-25 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-05-25 |
Time |
11:21 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-05-25 |
Time |
10:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2018-07-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-07-05 |
Time |
13:00 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-07-05 |
Time |
13:00 |
Sent To |
|
|
| Notes |
| 2018-07-05 13:00:38 | RECEIVED THE FOLLOWING S&S PAGES VIA EMAIL: | | | | | | AD1.0 | | | A2.1.1 | | | A3.1.1 | | | A4.1.1 | | | P0.1 | | | P5.1 | | | E0.1 | | | E5.1 | | | | | | ALL OTHER PAGES ARE DIGITALLY SIGNED AND SEALED IN | | | ACCORDANCE WITH FS471, FS481 | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
F |
Date |
2018-07-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-07-05 |
Time |
09:08 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-07-05 |
Time |
09:08 |
Sent To |
|
|
| Notes |
| 2018-07-05 09:10:01 | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | THE FOLLOWING PAGES ARE NOT SIGNED AND SEALED IN | | | ACCORDANCE WITH FS471, FS481. PLEASE SEND SIGNED & | | | SEALED PAGES DIRECTLY TO ME VIA EMAIL, [email protected]: | | | | | | AD1.0 | | | A2.1.1 | | | A3.1.1 | | | A4.1.1 | | | P0.1 | | | P5.1 | | | E0.1 | | | E5.1 | | | | | | | | 2018-07-03 11:28:01 | MECH DIG/SIGS OK | | | CCOLE- 7/3/18 |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2018-06-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-06-16 |
Time |
19:01 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-06-16 |
Time |
19:01 |
Sent To |
|
|
| Notes |
| 2018-06-16 19:05:03 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | ALL PAGES WERE REPLACED, EVEN THE ONES WHICH DID NOT | | | CHANGE. IN THE FUTURE PLEASE SUBMIT ONLY PAGES WHICH | | | CHANGE AS SUBMITTING ALL NEW PAGES REQUIRES REVIEW OF | | | ALL PAGES BY ALL TRADES. THIS SIGNIFICANTLY INCREASES | | | PLAN REVIEW TIME. | | | | | | THE NEW A, P, E PAGES ARE NOT DIGITALLY SIGNED AND | | | SEALED, FS471, FS481. IF B, FIRE, PLUMBING, ELECTRICAL | | | PASS THIS REVIEW CYCLE, **DO NOT RESUBMIT NEW SHEETS**, | | | CONTACT ME FOR INFORMATION ON HOW TO RESOLVE THIS | | | ISSUE. | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2018-05-23 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-05-23 |
Time |
07:20 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-05-23 |
Time |
07:18 |
Sent To |
|
|
| Notes |
| 2018-05-23 07:21:15 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | ALL DIGITAL SIGNATURE/SEALS ARE IN ACCORDANCE WITH | | | FS471, FS481, BUT NEW SHEETS SUBMITTED NEXT REVIEW | | | CYCLE NEED REVIEW. | | | | | | |
|
|