Plan Review Stops For Permit 18041245
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-05-26 Cont ID  
Sent By jleahy Date 2022-05-26 Time 11:42 Rev Time 0.00
Received By jleahy Date 2022-05-26 Time 11:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-05-04 Cont ID  
Sent By fgiaquin Date 2018-05-04 Time 06:18 Rev Time 0.00
Received By fgiaquin Date 2018-05-04 Time 06:06 Sent To M
Notes
2018-05-04 06:10:18CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND
 SIGNED/SEALED BY A DESIGN PROFESSIONAL OR THE
 ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1
  
 2. VALUE HAS BEEN ADJUSTED TO 1500$ IF YOU DISAGREE
 WITH THIS ADJUSTMENT PLEASE PROVIDE COPY OF SIGNED
 (SIGNED BY BOTH OWNER AND YOUR COMPANY) CONTRACT WITH
 SCOPE AND VALUE OF WORK, TO INCLUDE ALL MATERIALS AND
 LABOR. FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-05-12 Cont ID  
Sent By cwalker Date 2022-05-12 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-05-01 Cont ID  
Sent By pleduc Date 2018-05-01 Time   Rev Time 0.00
Received By pleduc Date 2018-04-30 Time 12:01 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-05-26 Cont ID  
Sent By jleahy Date 2022-05-26 Time 11:42 Rev Time 0.00
Received By jleahy Date 2022-05-11 Time 11:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-10 Cont ID  
Sent By hmoser Date 2018-05-10 Time 09:49 Rev Time 0.00
Received By hmoser Date 2018-04-26 Time 11:44 Sent To  
Notes
2018-04-27 11:44:36ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2018-05-10 Cont ID  
Sent By hmoser Date 2018-05-10 Time 09:49 Rev Time 0.00
Received By hmoser Date 2018-05-10 Time 09:49 Sent To I
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-06-15 Cont ID  
Sent By mpeterso Date 2022-06-15 Time 15:00 Rev Time 0.00
Received By mpeterso Date 2022-06-15 Time 15:00 Sent To  
Notes
2022-06-15 15:08:146/15/22 SIGNATURE REVIEW OF PAPER PLANS/DOCUMENTS
 PASSED AND ROUTED TO STORAGE.MP

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-05-26 Cont ID  
Sent By jleahy Date 2022-05-26 Time 11:33 Rev Time 0.00
Received By jleahy Date 2022-05-26 Time 11:33 Sent To  
Notes
2022-05-26 11:42:09FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLAN IS NOT SIGNED AND SEALED BY ENGINEER OF RECORD.
  
 ELECTRICAL PLAN IS REQUIRED TO BE SIGNED/SEALED BY THE
 DESIGN PROFESSIONAL . PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB