Plan Review Details - Permit 18041240
Plan Review Stops For Permit 18041240
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-06-20 Cont ID  
Sent By rmcdouga Date 2018-06-20 Time 17:52 Rev Time 0.00
Received By rmcdouga Date 2018-06-20 Time 17:52 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-05-14 Cont ID  
Sent By rmcdouga Date 2018-05-14 Time 17:50 Rev Time 0.00
Received By rmcdouga Date 2018-05-14 Time 17:31 Sent To FIRE
Notes
2018-05-14 17:47:20PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SPECIFY THE WIND LOAD DATA ON THE PLANS. FBC
 1603.1.4
  
 2) SUBMIT TWO SETS OF STRUCTURAL DETAILS FOR THE
 CONCRETE SLAB THAT WILL SUPPORT THE NEW GENERATOR. FBC
 107.2.1 & 1604.1
  
 2) SPECIFY THE FASTENERS (TYPE, SIZE, EMBED DEPTH,
 ETC.) THAT WILL BE USED TO ANCHOR THE GENERATOR TO TO
 THE SLAB TO PREVENT SLIDING AND OVERTURN FROM
 WINDLOADING. FBC 107.2.1 & 1604.1
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2018-07-26 Cont ID  
Sent By jpearson Date 2018-07-26 Time 14:40 Rev Time 0.00
Received By jpearson Date 2018-07-26 Time 14:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2018-07-23 Cont ID  
Sent By jpearson Date 2018-07-23 Time 16:45 Rev Time 0.00
Received By jpearson Date 2018-07-23 Time 16:45 Sent To I
Notes
2018-07-23 16:44:48CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. VOIDED SHEETS MUST BE REMOVED FROM THE ORIGINAL SET
 AND NEW SHEETS INSERTED INTO EACH PLAN SET. PROVIDE TWO
 COMPLETE SETS OF PLANS. WPB FBC 107.1, 107.2.1 (ONLY
 ONE SHEET, E-1 HAS BEEN PROVIDED. SHEET E-2 FROM THE
 ORIGINAL SUBMISSION IS MISSING. THIS SHEET INCLUDES THE
 RISER DIAGRAM AND MUST BE INCLUDED FOR A COMPLETE SET
 OF PLANS.)
  
 NEW COMMENT:
  
 3. PLEASE BE ADVISED THAT THIS COMMENT HAS NOT BEEN
 ADDRESSED FOR TWO REVIEWS. IF UPON THE THIRD REVIEW, IF
 IT IS NECESSARY TO REJECT THE SUBMITTED PLAN A THIRD
 TIME FOR THE SAME REASONS, AN ADDITIONAL PLAN REVIEW IS
 REQUIRED. FLORIDA STATUTES STATE: ?WITH RESPECT TO
 EVALUATION OF DESIGN PROFESSIONALS? DOCUMENTS, IF A
 LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO
 ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND
 ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY
 THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A
 CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN
 EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS,
 FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)?
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-06-20 Cont ID  
Sent By jpearson Date 2018-06-20 Time 12:36 Rev Time 0.00
Received By jpearson Date 2018-06-20 Time 12:36 Sent To P
Notes
2018-06-20 12:36:39CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
  
 NEW COMMENT:
  
 2. VOIDED SHEETS MUST BE REMOVED FROM THE ORIGINAL SET
 AND NEW SHEETS INSERTED INTO EACH PLAN SET. PROVIDE TWO
 COMPLETE SETS OF PLANS. WPB FBC 107.1, 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-05-10 Cont ID  
Sent By jpearson Date 2018-05-10 Time 14:41 Rev Time 0.00
Received By jpearson Date 2018-05-10 Time 14:41 Sent To  
Notes
2018-05-10 14:41:43CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. FBC
 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-06-07 Cont ID  
Sent By pleduc Date 2018-06-07 Time   Rev Time 0.00
Received By pleduc Date 2018-06-06 Time 15:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-05-15 Cont ID  
Sent By pleduc Date 2018-05-15 Time   Rev Time 0.00
Received By pleduc Date 2018-05-15 Time 15:25 Sent To I
Notes
2018-05-15 15:31:42THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS NO INDICATION OF COMPLIANCE WITH ANY FIRE
 CODE.
  
 THE INSTALLATION SHALL COMPLY WITH NFPA? 110 STANDARD
 FOR EMERGENCY AND STANDBY POWER SYSTEMS
 2013 EDITION
  
 PLEASE REVIEW TO ENSURE COMPLIANCE AND PROVIDE AN
 APPLICABLE NOTE.
  
  
  
  
 2) THERE IS NO INDICATION OF THE SEPARATION DISTANCE
 FROM AND NEARBY BUILDINGS TO ENSURE NO EXPSOURE TO
 EXHAUST FUUMES.
  
 PLEASE PROVIDE DISTANCES AS APPLICABLE ON THE SITE
 PLAN.
  
 PER NFPA 110
  
 7.10 EXHAUST SYSTEM.
 7.10.1 THE EXHAUST SYSTEM EQUIPMENT AND INSTALLATION,
 INCLUDING
 PIPING, MUFFLER, AND RELATED ACCESSORIES, SHALL BE IN
 ACCORDANCE WITH NFPA37, STANDARD FOR THE INSTALLATION
 AND USE OF
 STATIONARY COMBUSTION ENGINES AND GAS TURBINES, AND
 OTHER APPLICABLE
 STANDARDS.
  
  
  
 3) THERE IS NO INDICATION IF YOUR BUILDING IS PROVIDED
 WITH ANY FIRE ALARM OR FIRE SPRINKLER SYSTEMS THAT MAY
 NEED TO BE TIED INTO THIS GENERATOR.
  
 PLEASE PROVIDE AN APPLICABLE NOTE AS THE TIE HAS TO BE
 DONE BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
  
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-06-20 Cont ID  
Sent By tklarge Date 2018-06-20 Time 13:51 Rev Time 0.00
Received By tklarge Date 2018-06-20 Time 13:41 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-05-13 Cont ID  
Sent By tklarge Date 2018-05-13 Time 13:05 Rev Time 0.00
Received By tklarge Date 2018-05-13 Time 12:54 Sent To  
Notes
2018-05-13 13:05:07THE GENERATOR IS SHOWN LOCATED IN A PARKING AREA.
 SUBMIT DETAILS AS TO HOW THE GENERATOR WILL BE
 PROTECTED FROM VEHICLE IMPACT IN ACCORDANCE WITH 2017
 FBC-FUEL GAS SEC. 303.4.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2018-07-23 Time   Rev Time 0.00
Received By lmarchan Date 2018-07-13 Time 13:32 Sent To  
Notes
2018-07-16 13:32:12RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-06-20 Cont ID  
Sent By rmcdouga Date 2018-06-20 Time 17:52 Rev Time 0.00
Received By rmcdouga Date 2018-05-25 Time 09:56 Sent To  
Notes
2018-06-16 11:51:466/16 TO JP DESK
  
2018-05-30 09:56:50RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-15 Cont ID  
Sent By cpuell Date 2018-05-15 Time 16:08 Rev Time 0.00
Received By cpuell Date 2018-04-26 Time 11:40 Sent To  
Notes
2018-04-27 11:41:00ROTUED TO ZONING INBOX

Review Stop Z ZONING
Rev No 3 Status P Date 2018-07-19 Cont ID  
Sent By mcruz Date 2018-07-19 Time 11:07 Rev Time 0.00
Received By mcruz Date 2018-07-19 Time 10:56 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2018-06-01 Cont ID  
Sent By mcruz Date 2018-06-01 Time 16:31 Rev Time 0.00
Received By mcruz Date 2018-05-31 Time 10:29 Sent To FIRE
Notes
2018-06-01 16:31:49ZONING REVIEW FAILED, DUE TO THE FOLLOWING:
  
 1) RESPOND TO COMMENTS IN WRITING.
 2) INDICATE ON PLAN THE DISTANCE OF PARKING SPACE TO
 GENERATOR TO ENSURE VEHICLES ARE ABLE TO MANUEVER OUT
 OF PARKING SPACE SAFELY.
 3) ADVISE WHERE IS THE DUMPSTER GOING TO BE LOCATED? I
 SEE DUMPSTER IS CURRENTLY IN LOCATION WHERE GENERATOR
 IS BEING PROPOSED.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 561-822-1442
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2018-05-04 Cont ID  
Sent By ajones Date 2018-05-04 Time 15:39 Rev Time 0.00
Received By ajones Date 2018-05-04 Time 15:39 Sent To B
Notes
2018-05-04 15:48:44FAILED- PLEASE PROVIDE A BETTER LOCATION OF THE
 GENERATOR AS IT RELATES TO THE EXISTING PARKING AND THE
 LANDSCAPING.
  
 ANGELLA VANN
 561-822-1441
 [email protected]