| Plan Review Stops For Permit 18041240 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2018-06-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-06-20 |
Time |
17:52 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-06-20 |
Time |
17:52 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-05-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-05-14 |
Time |
17:50 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-05-14 |
Time |
17:31 |
Sent To |
FIRE |
|
| Notes |
| 2018-05-14 17:47:20 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SPECIFY THE WIND LOAD DATA ON THE PLANS. FBC | | | 1603.1.4 | | | | | | 2) SUBMIT TWO SETS OF STRUCTURAL DETAILS FOR THE | | | CONCRETE SLAB THAT WILL SUPPORT THE NEW GENERATOR. FBC | | | 107.2.1 & 1604.1 | | | | | | 2) SPECIFY THE FASTENERS (TYPE, SIZE, EMBED DEPTH, | | | ETC.) THAT WILL BE USED TO ANCHOR THE GENERATOR TO TO | | | THE SLAB TO PREVENT SLIDING AND OVERTURN FROM | | | WINDLOADING. FBC 107.2.1 & 1604.1 | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2018-07-26 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-07-26 |
Time |
14:40 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-07-26 |
Time |
14:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2018-07-23 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-07-23 |
Time |
16:45 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-07-23 |
Time |
16:45 |
Sent To |
I |
|
| Notes |
| 2018-07-23 16:44:48 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS | | | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY | | | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW | | | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. | | | | | | 1. CORRECTED. | | | 2. VOIDED SHEETS MUST BE REMOVED FROM THE ORIGINAL SET | | | AND NEW SHEETS INSERTED INTO EACH PLAN SET. PROVIDE TWO | | | COMPLETE SETS OF PLANS. WPB FBC 107.1, 107.2.1 (ONLY | | | ONE SHEET, E-1 HAS BEEN PROVIDED. SHEET E-2 FROM THE | | | ORIGINAL SUBMISSION IS MISSING. THIS SHEET INCLUDES THE | | | RISER DIAGRAM AND MUST BE INCLUDED FOR A COMPLETE SET | | | OF PLANS.) | | | | | | NEW COMMENT: | | | | | | 3. PLEASE BE ADVISED THAT THIS COMMENT HAS NOT BEEN | | | ADDRESSED FOR TWO REVIEWS. IF UPON THE THIRD REVIEW, IF | | | IT IS NECESSARY TO REJECT THE SUBMITTED PLAN A THIRD | | | TIME FOR THE SAME REASONS, AN ADDITIONAL PLAN REVIEW IS | | | REQUIRED. FLORIDA STATUTES STATE: ?WITH RESPECT TO | | | EVALUATION OF DESIGN PROFESSIONALS? DOCUMENTS, IF A | | | LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO | | | ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND | | | ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY | | | THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A | | | CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN | | | EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS, | | | FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, | | | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, | | | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER | | | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING | | | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL | | | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH | | | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, | | | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE | | | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)? | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2018-06-20 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-06-20 |
Time |
12:36 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-06-20 |
Time |
12:36 |
Sent To |
P |
|
| Notes |
| 2018-06-20 12:36:39 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS | | | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY | | | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW | | | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. | | | | | | 1. CORRECTED. | | | | | | NEW COMMENT: | | | | | | 2. VOIDED SHEETS MUST BE REMOVED FROM THE ORIGINAL SET | | | AND NEW SHEETS INSERTED INTO EACH PLAN SET. PROVIDE TWO | | | COMPLETE SETS OF PLANS. WPB FBC 107.1, 107.2.1 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-05-10 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-05-10 |
Time |
14:41 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-05-10 |
Time |
14:41 |
Sent To |
|
|
| Notes |
| 2018-05-10 14:41:43 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS | | | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND | | | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. FBC | | | 109.3 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2018-06-07 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-06-07 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-06-06 |
Time |
15:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2018-05-15 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-05-15 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-05-15 |
Time |
15:25 |
Sent To |
I |
|
| Notes |
| 2018-05-15 15:31:42 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THERE IS NO INDICATION OF COMPLIANCE WITH ANY FIRE | | | CODE. | | | | | | THE INSTALLATION SHALL COMPLY WITH NFPA? 110 STANDARD | | | FOR EMERGENCY AND STANDBY POWER SYSTEMS | | | 2013 EDITION | | | | | | PLEASE REVIEW TO ENSURE COMPLIANCE AND PROVIDE AN | | | APPLICABLE NOTE. | | | | | | | | | | | | | | | 2) THERE IS NO INDICATION OF THE SEPARATION DISTANCE | | | FROM AND NEARBY BUILDINGS TO ENSURE NO EXPSOURE TO | | | EXHAUST FUUMES. | | | | | | PLEASE PROVIDE DISTANCES AS APPLICABLE ON THE SITE | | | PLAN. | | | | | | PER NFPA 110 | | | | | | 7.10 EXHAUST SYSTEM. | | | 7.10.1 THE EXHAUST SYSTEM EQUIPMENT AND INSTALLATION, | | | INCLUDING | | | PIPING, MUFFLER, AND RELATED ACCESSORIES, SHALL BE IN | | | ACCORDANCE WITH NFPA37, STANDARD FOR THE INSTALLATION | | | AND USE OF | | | STATIONARY COMBUSTION ENGINES AND GAS TURBINES, AND | | | OTHER APPLICABLE | | | STANDARDS. | | | | | | | | | | | | 3) THERE IS NO INDICATION IF YOUR BUILDING IS PROVIDED | | | WITH ANY FIRE ALARM OR FIRE SPRINKLER SYSTEMS THAT MAY | | | NEED TO BE TIED INTO THIS GENERATOR. | | | | | | PLEASE PROVIDE AN APPLICABLE NOTE AS THE TIE HAS TO BE | | | DONE BY CERTIFIED LIFE SAFETY CONTRACTORS. | | | | | | | | | | | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2018-06-20 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-06-20 |
Time |
13:51 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-06-20 |
Time |
13:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2018-05-13 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-05-13 |
Time |
13:05 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-05-13 |
Time |
12:54 |
Sent To |
|
|
| Notes |
| 2018-05-13 13:05:07 | THE GENERATOR IS SHOWN LOCATED IN A PARKING AREA. | | | SUBMIT DETAILS AS TO HOW THE GENERATOR WILL BE | | | PROTECTED FROM VEHICLE IMPACT IN ACCORDANCE WITH 2017 | | | FBC-FUEL GAS SEC. 303.4. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2018-07-23 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2018-07-13 |
Time |
13:32 |
Sent To |
|
|
| Notes |
| 2018-07-16 13:32:12 | RESUB ROUTED TO ZONING INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-06-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-06-20 |
Time |
17:52 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-05-25 |
Time |
09:56 |
Sent To |
|
|
| Notes |
| 2018-06-16 11:51:46 | 6/16 TO JP DESK | | | | | 2018-05-30 09:56:50 | RESUB ROUTED TO ZONING INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-05-15 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2018-05-15 |
Time |
16:08 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2018-04-26 |
Time |
11:40 |
Sent To |
|
|
| Notes |
| 2018-04-27 11:41:00 | ROTUED TO ZONING INBOX |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2018-07-19 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2018-07-19 |
Time |
11:07 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2018-07-19 |
Time |
10:56 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2018-06-01 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2018-06-01 |
Time |
16:31 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2018-05-31 |
Time |
10:29 |
Sent To |
FIRE |
|
| Notes |
| 2018-06-01 16:31:49 | ZONING REVIEW FAILED, DUE TO THE FOLLOWING: | | | | | | 1) RESPOND TO COMMENTS IN WRITING. | | | 2) INDICATE ON PLAN THE DISTANCE OF PARKING SPACE TO | | | GENERATOR TO ENSURE VEHICLES ARE ABLE TO MANUEVER OUT | | | OF PARKING SPACE SAFELY. | | | 3) ADVISE WHERE IS THE DUMPSTER GOING TO BE LOCATED? I | | | SEE DUMPSTER IS CURRENTLY IN LOCATION WHERE GENERATOR | | | IS BEING PROPOSED. | | | | | | FOR ADDITIONAL INFORMATION, THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT | | | WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH | | | PLANNING DEPARTMENT WEBSITE AT | | | WWW.CITYOFWPB.COM/PLAN/INDEX.HTM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | | CONTACT ME. | | | | | | MAGGIE CRUZ | | | ASSOCIATE PLANNER | | | 561-822-1442 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2018-05-04 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2018-05-04 |
Time |
15:39 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2018-05-04 |
Time |
15:39 |
Sent To |
B |
|
| Notes |
| 2018-05-04 15:48:44 | FAILED- PLEASE PROVIDE A BETTER LOCATION OF THE | | | GENERATOR AS IT RELATES TO THE EXISTING PARKING AND THE | | | LANDSCAPING. | | | | | | ANGELLA VANN | | | 561-822-1441 | | | [email protected] |
|
|