| Plan Review Stops For Permit 18041239 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2018-07-16 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-07-16 |
Time |
17:52 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-07-16 |
Time |
17:52 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2018-06-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-06-14 |
Time |
17:37 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-06-14 |
Time |
17:37 |
Sent To |
I |
|
| Notes |
| 2018-06-14 17:07:11 | PLAN | | | REVIEW COMMENTS | | | | | | 3RD REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | GENERATOR PAD AND ANCHORING | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | COMMENTS FROM THE PREVIOUS REVIEWS HAVE NOT BEEN | | | ADDRESSED. | | | | | | 1) FBC 107.2.1 & R301.1 SUBMIT TWO SETS OF GENERATOR | | | ANCHORING AND PAD PLANS. ( THE GENERATOR PAD DOCUMENTS | | | THAT WERE SUBMITTED INDICATE THAT THE 4 INCH THICK PADS | | | HAVE A WIND RATING OF 175 MPH. HOWEVER, THE ONE THAT IS | | | HIGHLIGHTED ON THE SECOND PAGE IS THE 3 INCH PAD | | | WITHOUT A WIND RATING. YOU WILL BE REQUIRED TO SUBMIT | | | THE TESTING FROM AN APPROVED TESTING AGENCY OR A | | | FLORIDA LICENSED ENGINEER'S SIGNED AND SEALED | | | CALCULATIONS WHICH SHOW THAT THE 4 INCH PAD IS RATED | | | FOR 175 MPH.) | | | | | | 2) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. | | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2018-06-11 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-06-11 |
Time |
16:36 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-06-11 |
Time |
16:36 |
Sent To |
I |
|
| Notes |
| 2018-06-11 16:38:17 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | GENERATOR PAD AND ANCHORING | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | COMMENTS FROM THE FIRST REVIEW HAVE NOT BEEN ADDRESSED. | | | | | | 1) FBC 107.2.1 SUBMIT TWO SETS OF GENERATOR ANCHORING | | | AND PAD PLANS. | | | | | | 2) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. | | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-05-25 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-05-25 |
Time |
08:29 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-05-25 |
Time |
08:26 |
Sent To |
I |
|
| Notes |
| 2018-05-25 08:29:53 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | GENERATOR PAD AND ANCHORING | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC 107.2.1 SUBMIT TWO SETS OF GENERATOR ANCHORING | | | AND PAD PLANS. | | | | | | 2) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. | | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN. | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2018-06-05 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-06-05 |
Time |
17:09 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-06-05 |
Time |
17:09 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-05-22 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-05-22 |
Time |
09:04 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-05-22 |
Time |
09:03 |
Sent To |
B |
|
| Notes |
| 2018-05-22 09:20:00 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | NEW PANEL WILL BE WHAT TYPE? | | | | | | VALUE FOR WORK SHOWN IS LOW, PLEASE SUBMIT A SIGNED | | | CONTRACT FOR THE WORK. | | | | | | GAS PERMIT VALUE IS TO BE INCLUDED WITH THIS PERMIT, | | | GAS SUB PERMIT CAME IN AS A SUB. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2018-05-15 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-05-15 |
Time |
06:33 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-05-15 |
Time |
06:24 |
Sent To |
|
|
| Notes |
| 2018-05-15 06:36:06 | A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL | | | PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT | | | THIS TIME. A SEPARATE GAS PERMIT IS REQUIRED FOR A | | | CONTRACTOR TO PERFORM THE RELATED WORK. PROVIDE | | | COMPLETE PLANS THAT REFLECT THE ENTIRE SCOPE OF GAS | | | WORK TO BE DONE. WPB AMEND. TO FBC SEC.107.2.1. | | | | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2018-07-16 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-07-16 |
Time |
17:52 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-07-13 |
Time |
13:30 |
Sent To |
|
|
| Notes |
| 2018-07-16 13:30:50 | RESUB ROUTED TO RMCDOUGAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-06-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-06-14 |
Time |
17:37 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-06-13 |
Time |
10:30 |
Sent To |
|
|
| Notes |
| 2018-06-14 10:30:43 | RESUB ROUTED TO RMCDOUGAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-06-11 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-06-11 |
Time |
16:38 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-05-25 |
Time |
09:48 |
Sent To |
|
|
| Notes |
| 2018-05-30 09:48:53 | ROUTED TO JLEAHY |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-05-25 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-05-25 |
Time |
08:31 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-04-26 |
Time |
11:43 |
Sent To |
|
|
| Notes |
| 2018-04-27 11:43:43 | ROUTED TO ZONING INBOX |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2018-05-04 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2018-05-04 |
Time |
15:30 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2018-05-04 |
Time |
15:30 |
Sent To |
G |
|
| Notes |
|
|