Plan Review Details - Permit 18041222
Plan Review Stops For Permit 18041222
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-08-27 Cont ID  
Sent By shill Date 2018-08-27 Time 18:50 Rev Time 0.00
Received By shill Date 2018-08-27 Time 18:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-05-22 Cont ID  
Sent By shill Date 2018-05-22 Time 13:26 Rev Time 0.00
Received By shill Date 2018-05-22 Time 13:26 Sent To  
Notes
2018-05-22 13:31:12****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. SHEET S1-101 REFERS TO A SOILS REPORT, PLEASE
 PROVIDE, FBC 107.
  
 2. A RESIDENT INSPECTOR IS REQUIRED FOR THE BOLTS AND
 WELDS, FBC 110.
  
 3. WHO WILL MONITOR THE AUGERCAST PILE INSTALLATION?
 PROVIDE A LETTER, FBC 110.
  
 4. REVISE PLAN TO INCLUDE COMPONENT & CLADDING
 PRESSURES, FBC B 1603.1.4.
  
 5. THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING
 PROVISO: STANDING SEAM PRODUCT APPROVAL IS REQUIRED TO
 BE REVIEWED BY DESIGNER OF RECORD, SUBMITTED TO THE
 BUILDING DIVISION, REVIEWED AND ISSUED PRIOR TO
 INSTALLATION.
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2018-11-26 Cont ID  
Sent By jpearson Date 2018-11-26 Time 07:29 Rev Time 0.00
Received By jpearson Date 2018-11-26 Time 07:29 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-10-11 Cont ID  
Sent By jpearson Date 2018-10-11 Time 08:22 Rev Time 0.00
Received By jpearson Date 2018-10-11 Time 08:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-08-20 Cont ID  
Sent By jpearson Date 2018-08-20 Time 09:04 Rev Time 0.00
Received By jpearson Date 2018-08-20 Time 09:03 Sent To  
Notes
2018-08-20 09:03:55ELECTRICAL SHEETS E0.101B, E3.101, AND E3.101B ARE NOT
 DIGITALLY SIGNED PER FS 471, 481. PROVIDE CORRECTION.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-05-20 Cont ID  
Sent By jpearson Date 2018-05-20 Time 11:03 Rev Time 0.00
Received By jpearson Date 2018-05-20 Time 11:03 Sent To  
Notes
2018-05-20 11:03:53CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL SHEET INDEX INDICATES THAT THERE ARE 8
 SHEETS INCLUDED FOR ELECTRICAL REVIEW, BUT ONLY 4
 SHEETS WERE SUBMITTED. PROVIDE CORRECTION. WPB FBC
 107.2.1
 2. PROVIDE LIGHTING CONTROLS AS SPECIFIED IN THE FBC
 ENERGY CONSERVATION. FBC EC C405.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2018-10-16 Cont ID  
Sent By rrossano Date 2018-10-16 Time   Rev Time 0.00
Received By rrossano Date 2018-10-16 Time   Sent To I
Notes
2018-10-16 13:08:12PLANS HAVE BEEN PASSED THROUGH FORMAL ENGINEERING
 REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2018-09-07 Cont ID  
Sent By RRossano Date 2018-09-07 Time   Rev Time 0.00
Received By rrossano Date 2018-09-06 Time   Sent To I
Notes
2018-09-07 14:22:07NO CONFLICT WITH CITY OF WPB UTILITIES.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2018-05-22 Cont ID  
Sent By shill Date 2018-05-22 Time 17:10 Rev Time 0.00
Received By shill Date 2018-05-22 Time 17:10 Sent To  
Notes
2018-05-22 17:10:25CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2018-11-26 Time   Rev Time 0.00
Received By cpuell Date 2018-11-06 Time 12:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-10-31 Cont ID  
Sent By gjohnson Date 2018-10-31 Time 16:33 Rev Time 0.00
Received By gjohnson Date 2018-10-03 Time 10:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-09-07 Cont ID  
Sent By cpuell Date 2018-09-07 Time 14:42 Rev Time 0.00
Received By cpuell Date 2018-07-31 Time 13:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-08 Cont ID  
Sent By cpuell Date 2018-06-08 Time 15:57 Rev Time 0.00
Received By cpuell Date 2018-04-27 Time 10:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-10-31 Cont ID  
Sent By gjohnson Date 2018-10-31 Time 16:33 Rev Time 0.00
Received By gjohnson Date 2018-10-31 Time 16:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-08-28 Cont ID  
Sent By gjohnson Date 2018-08-28 Time 11:19 Rev Time 0.00
Received By gjohnson Date 2018-08-28 Time 11:19 Sent To  
Notes
2018-08-28 12:02:111ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. A4.100 REFERS TO PLUMBING DRAWING NONE WHERE
 PROVIDED WITH THIS SUBMITTAL PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 2. PLEASE PROVIDE A STORM DRAIN ISOMETRIC DRAWING AND
 SIZING CALCULATIONS. PER WPB AMEND TO 107.3.5.1.3(13)
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2018-08-27 Cont ID  
Sent By shill Date 2018-08-27 Time 18:50 Rev Time 0.00
Received By shill Date 2018-08-27 Time 18:50 Sent To  
Notes
2018-08-27 18:51:05PRODUCT APPROVALS RECEIVED, BUT METHOD OF INSTALLATION
 WILL BE SUBMITTED BY ROOFING CONTRACTOR
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2018-11-06 Cont ID  
Sent By jpearson Date 2018-11-06 Time 10:59 Rev Time 0.00
Received By jpearson Date 2018-11-06 Time 10:59 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2018-10-11 Cont ID  
Sent By jpearson Date 2018-10-11 Time 08:21 Rev Time 0.00
Received By jpearson Date 2018-10-11 Time 08:21 Sent To  
Notes
2018-10-11 08:21:46ELECTRICAL SHEETS E0.101A, E0.101B, E3.101, AND E3.101B
 ARE NOT DIGITALLY SIGNED PER FS 471, 481. PROVIDE
 CORRECTION.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2018-08-20 Cont ID  
Sent By jpearson Date 2018-08-20 Time 09:02 Rev Time 0.00
Received By jpearson Date 2018-08-20 Time 09:02 Sent To  
Notes
2018-08-20 09:01:55ELECTRICAL SHEETS E0.101B, E3.101, AND E3.101B ARE NOT
 DIGITALLY SIGNED PER FS 471, 481. PROVIDE CORRECTION.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-05-22 Cont ID  
Sent By shill Date 2018-05-22 Time 13:32 Rev Time 0.00
Received By shill Date 2018-05-22 Time 13:31 Sent To  
Notes
2018-05-22 13:33:02ALL SIGNATURE/SEALS ARE IN ACCORDANCE WITH FS471,
 FS481. NEW SHEETS SUBMITTED NEXT REVIEW CYCLE NEED
 VERIFICATION.
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 3 Status P Date 2018-11-06 Cont ID  
Sent By shill Date 2018-11-06 Time 12:58 Rev Time 0.00
Received By shill Date 2018-11-06 Time 12:58 Sent To  
Notes
2018-11-06 12:58:35PROVISO: SUBMIT 3 ORIGINAL SI AGREEMENTS
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status F Date 2018-11-06 Cont ID  
Sent By shill Date 2018-11-06 Time 11:12 Rev Time 0.00
Received By shill Date 2018-11-06 Time 11:06 Sent To  
Notes
2018-11-06 11:16:15****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 PER SI AGREEMENT, THREE ORIGINALS ARE REQUIRED. PLEASE
 SUBMIT AT THE BUILDING DIVISION WITH A "PLAN REVIEW
 REQUEST FORM".
  
 INSPECTORS PREVIOUSLY APPROVED:
  
 ONMJ
 JOE MINCUZZI
 ERIC HERNANDEZ
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2018-08-27 Cont ID  
Sent By shill Date 2018-08-27 Time 18:41 Rev Time 0.00
Received By shill Date 2018-08-27 Time 18:41 Sent To  
Notes
2018-08-27 18:42:20SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 PROVIDE RESIDENT INSPECTOR AGREEMENT SIGNED BY ALL
 PARTIES
 PROVIDE RESUMES AND COPIES OF THE ENGINEER'S AND
 INSPECTORS' LICENSES
 THIS MAY BE SENT TO [email protected] FOR PRELIMINARY
 REVIEW
 3 ORIGINALS REQUIRED
  

Review Stop Z ZONING
Rev No 1 Status P Date 2018-06-01 Cont ID  
Sent By AA Date 2018-06-01 Time 16:22 Rev Time 0.00
Received By aaponte Date 2018-06-01 Time 16:22 Sent To  
Notes
***NONE***