| 2018-04-27 16:40:33 | BUILDING PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER, PX3169 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. E-84 TEST REPORT FOR SURFACE BURNING CHARACTERISTICS |
| | OF BUILDING MATERIALS FOR THE SPECIMEN SHAW SUNDRIES |
| | GROUND WORKS STYLE 074VS IS NOT VALID WITHOUT |
| | ENGINEER'S SEAL. |
| | 2. PROVIDE CERTIFIED TEST REPORTS FOR ASTM E-90, |
| | AIRBORNE SOUND AND ASTM E-492, IMPACT SOUND FOR |
| | PROPOSED UNDERLAYMENT. |
| | |
| | PROVIDE THE FOLLOWING INFORMATION FOR FLOORING |
| | SUBMITTALS: |
| | |
| | 1. FLOOR PLAN WITH DIMENSIONS AND LOCATION OF WORK. - |
| | COMPLIED |
| | *DESIGNER TO PRINT NAME AND SIGN PLAN PER FBC 107 * |
| | 2. TOTAL SQUARE FOOTAGE OF NEW FLOORING. - COMPLIED |
| | 3. TYPE OF PROPOSED FLOORING |
| | (TILE/MARBLE/LAMINATE/WOOD/OTHER). - VINYL PLANK |
| | 4. STATED VALUE OF WORK. - VALUE SHALL BE BASED ON |
| | LABOR AND MATERIALS |
| | 5. EXISTING SITE CONDITIONS: |
| | A) THICKNESS OF SLAB. B) CEILING ASSEMBLY (OPEN |
| | CONCRETE/SUSPENDED GYPSUM/ACOUSTICAL) |
| | 6. PROPOSED UNDERLAYMENT. - STATED |
| | 7. TEST REPORTS FOR PROPOSED UNDERLAYMENT BASED ON |
| | EXISTING SITE CONDITIONS. |
| | 8. TEST REPORTS MAY BE BASED ON THE FOLLOWING ASTM?S, |
| | E-84, E-90 & E-492. |
| | 9. ALL DOCUMENTS SHALL BE SUBMITTED IN DUPLICATE. |
| | |
| | FBC 603.1 FLAME SPREAD ? ASTM E-84-09 |
| | |
| | FBC 1207.2 AIR-BORNE SOUND. ASTM E ? 90-04 |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E ? 492-09 |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC SPACE OR SERVICE |
| | AREA WITHIN THE STRUCTURE SHALL HAVE AN IMPACT |
| | INSULATION CLASS (IIC) RATING OF NOT LESS THAN 50 (45 |
| | IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E |
| | 492. |
| | |
| | |