Plan Review Details - Permit 18041175
Plan Review Stops For Permit 18041175
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2018-05-14 Cont ID  
Sent By cthroop Date 2018-05-14 Time 16:13 Rev Time 0.00
Received By cthroop Date 2018-05-14 Time 07:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-08-06 Cont ID  
Sent By cthroop Date 2018-08-06 Time 16:01 Rev Time 0.00
Received By cthroop Date 2018-08-06 Time 16:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-07-20 Cont ID  
Sent By dbattles Date 2018-07-20 Time 15:52 Rev Time 0.00
Received By dbattles Date 2018-07-20 Time 15:52 Sent To  
Notes
2018-07-20 15:53:52SEE COMMENTS FROM 18041063 (MAIN HOUSE)

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-06-22 Cont ID  
Sent By cthroop Date 2018-06-22 Time 09:57 Rev Time 0.00
Received By cthroop Date 2018-06-22 Time 09:56 Sent To I
Notes
2018-06-22 12:55:37SEE REVIEW COMMENTS UNDER 18041063. CT

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-05-14 Cont ID  
Sent By cthroop Date 2018-05-14 Time 16:11 Rev Time 0.00
Received By cthroop Date 2018-05-14 Time 07:38 Sent To  
Notes
2018-05-14 16:13:12BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE SOILS REPORT WITH ORIGINAL SIGNATURE AND
 SEAL OF FLORIDA LICENSED PROFESSIONAL ENGINEER.
 PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE,
 DATE AND SEAL OF THE ENGINEER PER FL ADMIN. CODE RULE
 61G15-23.001.
  
 2. PROVIDE SITE DRAINAGE PLAN.
 FBC R401.3 SITE DRAINAGE
 PROVIDE TWO SETS OF A SITE DRAINAGE PLAN SHOWING
 COMPLIANCE WITH FBC R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD.
 LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES WITHIN THE FIRST 10 FEET.
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES OF FALL WITHIN 10
 FEET, DRAINS OR SWALES SHALL BE CONSTRUCTED TO ENSURE
 DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET OF THE BUILDING
 FOUNDATION SHALL BE SLOPED A MINIMUM OF
 2 PERCENT AWAY FROM THE BUILDING.
  
 3. PROVIDE ICC-ES REPORT FOR ICYNENE INSULATION. SELECT
 PRODUCT TO BE INSTALLED TO OBTAIN THE R-30 RATING PER
 APPROVED PLANS.
 R402.1.1 INSULATION AND FENESTRATION CRITERIA.
  
 4. PROVIDE LANDINGS AT EXTERIOR DOORS AND STAIR
 LANDINGS.
 R311.3 FLOORS AND LANDINGS AT EXTERIOR DOORS.
 THERE SHALL BE A LANDING OR FLOOR ON EACH SIDE OF EACH
 EXTERIOR DOOR. THE WIDTH OF EACH LANDING SHALL NOT BE
 LESS THAN THE DOOR SERVED. EVERY LANDING SHALL HAVE A
 MINIMUM DIMENSION OF 36 INCHES (914 MM) MEASURED IN THE
 DIRECTION OF TRAVEL. EXTERIOR LANDINGS SHALL BE
 PERMITTED TO HAVE A SLOPE NOT TO EXCEED 1/4 UNIT
 VERTICAL IN 12 UNITS HORIZONTAL (2-PERCENT).
  
 DUE TO THE DEFICIENCIES OF THIS PLAN, A COMPLETE AND
 THOROUGH REVIEW CANNOT BE PERFORMED AT THIS TIME. UPON
 RE-SUBMITTAL, ADDITIONAL COMMENTS MAY BE MADE.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-07-20 Cont ID  
Sent By jpearson Date 2018-07-20 Time 11:26 Rev Time 0.00
Received By jpearson Date 2018-07-20 Time 11:15 Sent To  
Notes
2018-07-20 11:15:49APPROVED WITH PROVISO ON PLAN.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-06-08 Cont ID  
Sent By ppetty Date 2018-06-08 Time 12:36 Rev Time 0.00
Received By ppetty Date 2018-06-08 Time 10:12 Sent To  
Notes
2018-06-08 11:27:47CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1,
 E3609.3; WPB FBC 107.2.1
 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; WPB FBC
 107.3.5; FBC RE E3706.2, E3902
 3. NOTE 16 STATES THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT
 APPLY TO TAMPER RESISTANT RECEPTACLES. ADDITIONALLY,
 THIS IS NOT THE CURRENT CODE. PROVIDE CORRECTION. NEC
 406.12; FBC RE E4002.14
 4. OK
 5. OK
 6. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
 7. IS EXISTING SERVICE BEING USED AS IS, OR BEING
 UPGRADED? PLAN DOES NOT SPECIFY. IF UPGRADING, PROVIDE
 AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH PANEL
 INCLUDING INFORMATION FROM THE POWER COMPANY STATING
 WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE
 SERVICE TO CONFIRM THE STATED AIC RATING OF THE SERVICE
 EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. NEC 110.9,
 110.10
 8. OK
 9. OK
 10. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THE PANEL FOR PANEL A. NEC 225.31,
 225.32
 11. PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR
 A BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH
 CIRCUIT. NEC 250.32; FBC RE3607.3
 12. IDENTIFY ALL LOCATION OF ELECTRICAL PANELS ON PLAN.
 FBC 107.2.1
  
 DUE TO EXCESSIVE LACK OF INFORMATION ON ELECTRICAL
 PLAN, FURTHER PLAN REVIEW COMMENTS ARE LIKELY.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER, CHIEF ELECTRICAL INSPECTOR
 561-805-6742
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-05-07 Cont ID  
Sent By jpearson Date 2018-05-07 Time 11:07 Rev Time 0.00
Received By jpearson Date 2018-05-07 Time 11:07 Sent To  
Notes
2018-05-07 11:07:48CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1,
 E3609.3; WPB FBC 107.2.1
 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; WPB FBC
 107.3.5; FBC RE E3706.2, E3902
 3. NOTE 16 STATES THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT
 APPLY TO TAMPER RESISTANT RECEPTACLES. ADDITIONALLY,
 THIS IS NOT THE CURRENT CODE. PROVIDE CORRECTION. NEC
 406.12; FBC RE E4002.14
 4. PROVIDE AN OUTLET FOR ANY WALL SPACE 24 INCHES OR
 GREATER WHERE REQUIRED TO MEET WALL SPACING
 REQUIREMENTS. PROVIDE CORRECTION. NEC 210.52; FBC RE
 E3901.2.1
 5. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP
 CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN.
 PROVIDE CORRECTION. NEC 210.11(C)(3), 210.52(D); FBC RE
 E3703.4, E3901.6
 6. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
 7. IS EXISTING SERVICE BEING USED AS IS, OR BEING
 UPGRADED? PLAN DOES NOT SPECIFY. IF UPGRADING, PROVIDE
 AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH PANEL
 INCLUDING INFORMATION FROM THE POWER COMPANY STATING
 WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE
 SERVICE TO CONFIRM THE STATED AIC RATING OF THE SERVICE
 EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. NEC 110.9,
 110.10
 8. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1
 9. GFCI PROTECTION IS REQUIRED FOR ALL OUTLETS IN
 GARAGE, INCLUDING GARAGE DOOR OPENER. PROVIDE
 CORRECTION. NEC 210.8; FBC RE E3902.2
 10. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THE PANEL FOR PANEL A. NEC 225.31,
 225.32
 11. PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR
 A BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH
 CIRCUIT. NEC 250.32; FBC RE3607.3
 12. IDENTIFY ALL LOCATION OF ELECTRICAL PANELS ON PLAN.
 FBC 107.2.1
  
 DUE TO EXCESSIVE LACK OF INFORMATION ON ELECTRICAL
 PLAN, FURTHER PLAN REVIEW COMMENTS ARE LIKELY.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2018-07-17 Cont ID  
Sent By fmittner Date 2018-07-17 Time 14:01 Rev Time 0.00
Received By fmittner Date 2018-07-17 Time 14:01 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2018-06-12 Cont ID  
Sent By fmittner Date 2018-06-12 Time 12:02 Rev Time 0.00
Received By fmittner Date 2018-06-12 Time 12:02 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2018-05-02 Cont ID  
Sent By fmittner Date 2018-05-02 Time 16:14 Rev Time 0.00
Received By fmittner Date 2018-05-02 Time 16:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-07-26 Cont ID  
Sent By lcrespo Date 2018-07-26 Time 13:46 Rev Time 0.00
Received By lcrespo Date 2018-06-28 Time 16:01 Sent To  
Notes
2018-06-28 16:01:34R30
 *TRAVELLING WITH 18041063*

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-06-22 Cont ID  
Sent By cthroop Date 2018-06-22 Time 09:58 Rev Time 0.00
Received By cthroop Date 2018-06-01 Time 15:10 Sent To I
Notes
2018-06-04 15:10:41R24
 **TRAVELLING WITH 18041063**

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-14 Cont ID  
Sent By cthroop Date 2018-05-14 Time 16:14 Rev Time 0.00
Received By cthroop Date 2018-04-23 Time 14:29 Sent To I
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2018-05-14 Cont ID  
Sent By cthroop Date 2018-05-14 Time 16:13 Rev Time 0.00
Received By cthroop Date 2018-05-14 Time 07:39 Sent To  
Notes
2018-05-14 16:14:21NO NOTES
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-05-02 Cont ID  
Sent By cmontell Date 2018-05-02 Time 12:58 Rev Time 0.00
Received By cmontell Date 2018-05-02 Time 12:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-07-26 Cont ID  
Sent By lcrespo Date 2018-07-26 Time 13:46 Rev Time 0.00
Received By lcrespo Date 2018-07-26 Time 13:46 Sent To  
Notes
2018-07-26 13:46:4307/26/18 DENIED GAS, PLUMBING APPROVED SENT TO
 PROCESSING, LAC

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-07-26 Cont ID  
Sent By lcrespo Date 2018-06-13 Time 07:30 Rev Time 0.00
Received By lcrespo Date 2018-06-13 Time 07:30 Sent To  
Notes
2018-06-13 07:30:3106/13/18 DENIED GAS, PLUMBING APPROVED PUT BACK IN
 R24,LAC

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-05-08 Cont ID  
Sent By lcrespo Date 2018-05-08 Time 08:26 Rev Time 0.00
Received By lcrespo Date 2018-05-08 Time 08:26 Sent To  
Notes
2018-05-08 08:28:0105/07/18 DEINIED BY PLUMBING AND COMENTS ON PERMIT
 18041063, LAC

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2018-08-06 Cont ID  
Sent By cthroop Date 2018-08-06 Time 16:01 Rev Time 0.00
Received By cthroop Date 2018-08-06 Time 16:00 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2018-06-22 Cont ID  
Sent By cthroop Date 2018-06-22 Time 09:58 Rev Time 0.00
Received By cthroop Date 2018-06-22 Time 09:56 Sent To  
Notes
2018-06-22 10:00:21SEE COMMENTS ON 18041063. CT

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2018-05-14 Cont ID  
Sent By cthroop Date 2018-05-14 Time 16:14 Rev Time 0.00
Received By cthroop Date 2018-05-14 Time 07:39 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2018-07-17 Cont ID  
Sent By fmittner Date 2018-07-17 Time 14:01 Rev Time 0.00
Received By fmittner Date 2018-07-17 Time 14:01 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2018-06-12 Cont ID  
Sent By fmittner Date 2018-06-12 Time 12:02 Rev Time 0.00
Received By fmittner Date 2018-06-12 Time 12:02 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-05-02 Cont ID  
Sent By fmittner Date 2018-05-02 Time 16:13 Rev Time 0.00
Received By fmittner Date 2018-05-02 Time 16:13 Sent To  
Notes
***NONE***