Plan Review Details - Permit 18041127
| Plan Review Stops For Permit 18041127 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2018-05-15 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-05-15 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-05-14 |
Time |
15:32 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2018-04-27 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-04-27 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-04-26 |
Time |
15:38 |
Sent To |
I |
|
| Notes |
| 2018-04-27 09:12:03 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THE PROPOSED PROJECT INDICATES THE USE OF FLEX DROP | | | PIPING. THE EXISTING SYSTEM APPEARS TO A TYPICAL ARM | | | OVER. | | | | | | THERE IS NO HYDRAULIC CALCULATION SUBMITTED THAT SHOWS | | | THAT THE NEW FLEX DROPS WILL BE SUPPORTED BY THE | | | EXISTING SYSTEM DESIGN. | | | | | | PLEASE PROVIDE CALCULATIONS DETAILS. | | | | | | | | | 2) THE SCOPE OF WORK INDICATES TWO RELOCATED HEADS, THE | | | DRAWING SHOWS THREE. WHICH IS CORRECT? | | | | | | PLEASE REVIEW AND CORRECT ACCORDINGLY. | | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-05-15 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2018-05-15 |
Time |
11:03 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2018-05-08 |
Time |
10:43 |
Sent To |
|
|
| Notes |
| 2018-05-09 10:43:18 | RESUB ROUTED TO FIRE INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-04-27 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2018-04-27 |
Time |
15:12 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2018-04-25 |
Time |
11:35 |
Sent To |
|
|
| Notes |
| 2018-04-26 11:35:21 | ROUTED TO FIRE INBOX |
|
|
|