Plan Review Details - Permit 18041078
Plan Review Stops For Permit 18041078
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-12-12 Cont ID  
Sent By cthroop Date 2019-12-12 Time 13:02 Rev Time 0.00
Received By cthroop Date 2019-12-12 Time 13:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-06-16 Cont ID  
Sent By shill Date 2018-06-16 Time 11:11 Rev Time 0.00
Received By shill Date 2018-06-16 Time 11:11 Sent To  
Notes
2018-06-16 11:12:32****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. VALUE IS TO INCLUDE LABOR, MATERIALS, OVERHEAD,
 PROFIT, FBC 109.
  
 WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-06-16 Cont ID  
Sent By shill Date 2018-05-01 Time 18:11 Rev Time 0.00
Received By shill Date 2018-05-01 Time 18:10 Sent To  
Notes
2018-05-02 14:58:01CHANGED STATUS FROM "PASS" TO "FAIL" TO PREVENT CARD
 PRINTING IN ERROR; NEED UPDATED VALUE
 6/16/18

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2019-12-12 Cont ID  
Sent By jleahy Date 2019-12-12 Time 12:36 Rev Time 0.00
Received By jleahy Date 2019-12-12 Time 12:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2018-06-13 Cont ID  
Sent By fgiaquin Date 2018-06-13 Time 06:15 Rev Time 0.00
Received By fgiaquin Date 2018-06-13 Time 05:39 Sent To B
Notes
2018-06-13 06:11:54ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NEC 600.6A(1) DISCONNECT REQUIRED WITHIN SIGHT OF
 SIGN. PLAN SHOWS DISCONNECT AND POWER SUPPLY BEHIND
 HOLLOW BLOCK WALL.
  
 2. TO MEET THE REQUIREMENTS OF NEC 600.6A(1) FOR THE
 DISCONNECTS A CONTRACTOR HOLDING AN EC OR ER LICENSE
 MUST PULL THE ELEC-SUB PERMIT AND PERFORM THE WORK.
 CONTRACTOR THAT HAS APPLIED FOR PERMIT ONLY CARRIES AN
 ES LICENSE AND IS BEYOND THEIR SCOPE OF WORK.
 F.S. 489.505 (#19) AND F.A.C. 61G6-7.001 SPECIALTY
 ELECTRICAL CONTRACTORS (#2 SIGN SPECIALTY CONTRACTOR)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-05-02 Cont ID  
Sent By jleahy Date 2018-05-02 Time 15:36 Rev Time 0.00
Received By jleahy Date 2018-05-02 Time 15:36 Sent To  
Notes
2018-05-02 15:40:22CONTRACT SUPPLIED DOES NOT SHOW HOW AMNY SIGNS ARE TO
 BE INSTALLED. CONTRACT ALSO DOES NOT INCLUDE LABOR.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-05-01 Cont ID  
Sent By fgiaquin Date 2018-05-01 Time 07:15 Rev Time 0.00
Received By fgiaquin Date 2018-05-01 Time 06:55 Sent To B
Notes
2018-05-01 07:14:31ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. FBC 105.1 (PERMITS AND INSPECTIONS REQUIRED.
 ELEC-SUB PERMIT REQURIED FOR EACH SIGN.
  
 2. CLARIFY IN SCOPE OF WORK WHICH SIGN IS FOR WHICH
 PERMIT.
  
 3. VALUE OF WIORK TOO LOW. PROVIDE COPY OF SIGNED
 CONTRACT WITH SCOPE AND VALUE OF WORK, TO INCLUDE ALL
 MATERIALS AND LABOR.
 FBC 109.3
  
 4. TIMECLOCK FOR SIGN MUST CONFORM TO FBC CE405.2.4 (IF
 INSTALLATION OF NEW TIMECLOCK IS NEEDED A SEPERATE
 ELECTRICAL PERMIT IS REQUIRED BY A CONTRACTOR HOLDING
 AN EC OR ER LICENSE.
  
 END OF COMMENTS.
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN
 REVIEW COMMENTS. WHEN RESUBMITTING, IT IS HELPFUL TO
 PROVIDE A RESPONSE LETTER ADDRESSING
 EACH ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO
 THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 6TH
 EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 6TH EDITION, PART
 VIII ELECTRICAL
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 [email protected]
 561-657-1653

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-12-12 Cont ID  
Sent By cthroop Date 2019-12-12 Time 13:03 Rev Time 0.00
Received By cthroop Date 2019-12-10 Time 15:17 Sent To  
Notes
2019-12-11 15:17:23RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-06-16 Cont ID  
Sent By shill Date 2018-06-16 Time 11:12 Rev Time 0.00
Received By shill Date 2018-05-30 Time 15:29 Sent To  
Notes
2018-05-31 15:29:48RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-02 Cont ID  
Sent By jleahy Date 2018-05-02 Time 15:43 Rev Time 0.00
Received By jleahy Date 2018-04-24 Time 14:01 Sent To  
Notes
2018-05-01 18:11:37ON SH DESK
  
  
  
2018-04-25 14:01:54ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 3 Status P Date 2019-12-11 Cont ID  
Sent By awooten Date 2019-12-11 Time   Rev Time 0.00
Received By awooten Date 2019-12-11 Time   Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2018-06-05 Time   Rev Time 0.00
Received By awooten Date 2018-06-05 Time 14:01 Sent To E
Notes
2018-06-05 14:07:29*****************************ZONING REVIEW
 FAILED***********************
  
 THE DIMENSIONS ON THE RE-SUBMITTAL ARE TOO SMALL.
 PLEASE SUBMIT A COPY WITH AN INCREASED FONT. FURTHER
 COMMENTS MAY FOLLOW ADDITIONAL REVIEW.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2018-04-27 Cont ID  
Sent By awooten Date 2018-04-27 Time   Rev Time  
Received By awooten Date 2018-04-27 Time   Sent To E
Notes
2018-04-27 15:00:12*************************ZONING REVIEW
 FAILED********************************
  
 SIGNAGE WILL FOLLOW THE UNDERLYING ZONING OF COMMUNITY
 SERVICE.
  
 PURSUANT TO THE CURRENT SIGN CODE.
  
 SEC. 94-408. - SIGNS PERMITTED IN COMMERCIAL,
 INDUSTRIAL, COMMUNITY SERVICE, RECREATION AND OPEN
 SPACE AND CONSERVATION DISTRICTS.
  
 (F) SIGNS PERMITTED IN COMMUNITY SERVICE, RECREATION
 AND OPEN SPACE, CONSERVATION DISTRICTS. SIGNS PERMITTED
 IN COMMUNITY SERVICE, RECREATION AND OPEN SPACE,
 CONSERVATION DISTRICTS SHALL BE AS FOLLOWS:
  
 WALL MOUNTED SIGNS. THE REQUIREMENTS FOR WALL MOUNTED
 SIGNS SHALL BE AS FOLLOWS:
  
 A. CONTENT: THE NAME, LOGO AND ADDRESS OF THE BUILDING
 AND BUILDING OCCUPANTS TO WHICH THE SIGN IS AN
 ACCESSORY AND OTHER RELATED INFORMATION. IN ADDITION,
 SIGNS PERMITTED PURSUANT TO THIS SECTION MAY CONTAIN
 ANY NONCOMMERCIAL MESSAGE WHICH HAS NOT BEEN DECLARED
 BY A COURT OF COMPETENT JURISDICTION TO BE OBSCENE,
 DEFAMATORY, OR OTHERWISE CONTRARY TO LAW.
  
 B. MAXIMUM SUM TOTAL AREA OF ALL SIGNS MOUNTED ON THE
 FRONT FACADE OF A BUILDING: 75 PERCENT OF THE AREA
 PERMITTED BY SECTION 94-409. PLEASE DIMENSION THE
 FA?ADE OF THE BUILDING.
  
 C. MAXIMUM SUM TOTAL AREA OF ALL SIGNS MOUNTED ON A
 FACADE OTHER THAN FRONT FACADE: 75 PERCENT OF THE AREA
 PERMITTED BY SECTION 94-409.
  
 D. MAXIMUM NUMBER ON EACH BUILDING: ONE SIGN FOR EACH
 INDIVIDUAL BUSINESS OCCUPANT OF THE BUILDING, PLUS TWO
 ADDITIONAL SIGNS.
  
 E. MAXIMUM HEIGHT: NO HIGHER THAN THE BUILDING WALL ON
 WHICH IT IS MOUNTED.
  
 PLEASE LET ME KNOW WHAT QUESTIONS YOU MAY HAVE.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]