Plan Review Details - Permit 18041063
Plan Review Stops For Permit 18041063
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2018-05-14 Cont ID  
Sent By cthroop Date 2018-05-14 Time 16:02 Rev Time 0.00
Received By cthroop Date 2018-05-14 Time 07:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-08-06 Cont ID  
Sent By cthroop Date 2018-08-06 Time 15:59 Rev Time 0.00
Received By cthroop Date 2018-08-06 Time 15:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-07-20 Cont ID  
Sent By dbattles Date 2018-07-20 Time 15:49 Rev Time 0.00
Received By dbattles Date 2018-07-20 Time 15:49 Sent To  
Notes
2018-07-20 15:49:53****CORRECTIONS****
 W.P.B. PERMIT: 18041063 & 18041175 (MAIN HOUSE AND
 GARAGE)
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1.OK
  
 2.DRAINAGE PLAN PROVIDED NEEDS TO SHOW NUMERIC CHANGES
 IN ELEVATION THAT MEET REQUIRMENTS IN R401.3
 [FBC 107.3.5.3]LOWEST FINISHED FLOOR ELEVATION NEEDS TO
 BE ESTABLISHED SINCE IT IS NOT ON SURVEY OR PLANS.
 PIPING FROM SCUPPERS IS NOT REQUIRED IF GRADE WILL
 PROVIDE PROPER DRAINAGE. IF PIPING IS USED WE NEED TO
 SEE HOW IT IS PITCHED AND HOW IT RELEASES TO THE
 STREET.
 2-2. NO ELEVATIONS WERE PROVIDED. PLEASE ESTABLISH THE
 LOWEST FLOOR ELEVATION AND SUPPLY ELEVATIONS THAT WILL
 HELP US DETERMINE IF YOU ARE MEETING DRAINAGE
 REQUIREMENTS. THE EAST PROPERTY LINE, THE LOWEST FLOOR,
 THE TOP OF WALL, THE SIDEWALK AND THE STREET DRAIN
 WOULD BE A GOOD STARTING POINT. ALL ELEVATIONS SHOULD
 BE IN NAVD88.
  
 3-09 OK
  
 10.[ENERGY (RE402.1.2]THE ENERGY CALCS PROVIDED SHOW
 THE WALLS TO BE RATED AT R-14 WITH INT INSULATION. HOW
 WILL THIS R-RATING BE ACHIEVED AND PROVIDE THE
 DOCUMENTATION OF THE PRODUCT. ADJUST PLANS AND ENERGY
 CALCULATIONS TO MATCH.
 10-2. THE INSULATION SPEC PROVIDED WOULD NOT BE ABLE TO
 ACHIEVE THE R-VALUE INDICATED IN THE ENERGY
 CALCULATIONS. PLEASE UPDATE THE ENERGY CALCULATIONS TO
 BE BASED ON WHAT WILL BE PROVIDED FOR WALL R-VALUE.
  
 11-18 OK
  
 NOTE:
 ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF ADDITIONAL MATERIALS REQUESTED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-06-22 Cont ID  
Sent By cthroop Date 2018-06-22 Time 12:50 Rev Time 0.00
Received By cthroop Date 2018-06-22 Time 09:54 Sent To  
Notes
2018-06-22 12:52:49BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC R = FBC RESIDENTIAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1.OK
  
 2.DRAINAGE PLAN PROVIDED NEEDS TO SHOW NUMERIC CHANGES
 IN ELEVATION THAT MEET REQUIRMENTS IN R401.3
 [FBC 107.3.5.3]LOWEST FINISHED FLOOR ELEVATION NEEDS TO
 BE ESTABLISHED SINCE IT IS NOT ON SURVEY OR PLANS.
 PIPING FROM SCUPPERS IS NOT REQUIRED IF GRADE WILL
 PROVIDE PROPER DRAINAGE. IF PIPING IS USED WE NEED TO
 SEE HOW IT IS PITCHED AND HOW IT RELEASES TO THE
 STREET.
  
 3.THE REPORT PROVIDED IS GOOD, BUT PLEASE CHOOSE ONLY
 ONE TYPE OF ICYNENE. IT IS EITHER CLASSIC OR CLASSIC
 PLUS BECAUSE THEY REQUIRE DIFFERENT THICKNESS TO
 ACHIEVE R-30.
  
 NEW COMMENTS BELOW FROM FULL REVIEW:
  
 4.[FBC R301]CHANGE ADDRESS ON SURVEY TO SAY 620 PARK
 PLACE ON BOTH SURVEY SHEETS. THE SURVEYOR PUT 618 ON
 THE SHEET SHOWING HOUSE LAYOUT.
  
 5.[FBC R311.3.1]EGRESS LANDING SHALL NOT BE LESS THAN 1
 1/2" LOWER THAN THE TOP OF THRESHOLD. PROVIDE DIMENSION
 ON SECTION TO SHOW HOW YOU ARE MEETING CODE PROVISION.
  
 6.[FBC 107.3.5.3]SHOW SECTION CUTS ON PLAN SHEET A-1 TO
 CORRESPOND TO SECTIONS ON SHEET A-6, ADD NORTH ARROW TO
 A-1, ADD ELEVATION CALLOUTS ON A-1 TO CORRESPOND TO
 ELEVATION SHEET A-2, ADD ROOF PITCH TO ELEVATIONS AND
 SECTIONS AND CONSIDER ADDING WINDOW DESIGNATIONS TO
 ELEVATION SHEET A-2 TO MATCH DESIGNATIONS ON PLAN SHEET
 A-1.
  
 7.[FBC R318]INDICATE THE MEANS OF TERMITE PROTECTION
 PROPOSED AND REFERENCE SECTION R308 FOR STANDARDS.
  
 8.[FBC R308.1]ADD NOTE FOR SHOWER ENCLOSURES TO COMPLY
 WITH SAFETY GLASS STANDARDS.
  
 9.[FBC R403.1(3) ADD NOTE TO SECTIONS SHOWING
 REINFORCING TO PROVIDE MINIMUM COVER OF 3" FOR
 REINFORCING BARS.
  
 10.[ENERGY (RE402.1.2]THE ENERGY CALCS PROVIDED SHOW
 THE WALLS TO BE RATED AT R-14 WITH INT INSULATION. HOW
 WILL THIS R-RATING BE ACHIEVED AND PROVIDE THE
 DOCUMENTATION OF THE PRODUCT. ADJUST PLANS AND ENERGY
 CALCULATIONS TO MATCH.
  
 NOTICE OF ACCEPTANCE (N.O.A.):
  
 11.PRINT DRAWING SHEETS IN LANDSCAPE FORMAT TO FIT THE
 PAGE BETTER. SOME ARE LEDIBLE, BUT SOME PRESSURE CHARTS
 ARE TOO HARD TO READ.
 THIS APPLIES TO NOA 17-1023.09, 17-0630.08 AND
 17-0614.14.
  
 12.PROVIDE 2 COPIES OF N.O.A. FOR INTENDED MULL BAR TO
 BE USED IN BEDROOM, OFFICE, MASTER BATH AND VERIFY IF
 MULL IS BEING USED IN GARAGE 2ND FL WEST ELEVATION. THE
 ELEVATION SHOWS DIFFERENT THAN THE PLAN LOFT WEST ELEV.
 2ND FL. WINDOWS.
  
 13.HIGHLIGHT ANCHOR OPTION FOR APPLICABLE BUILDING
 SYSTEM BEING USED ON WINDOW AND DOOR N.O.A.'S.
  
 14.N.O.A. 14-0506.02 IS MISSING PRESSURE DATA. PLEASE
 INSERT MISSING SHEET(S). ALSO, CHECK THAT THIS IS THE
 INTENDED DOOR TYPE FOR THE SINGLE DOORS. THE DOOR
 SCHEDULE CALLS OUT HOLLOW METAL DOORS BUT THE N.O.A IS
 FOR FIBERGLASS. UPDATE DOOR SCEDULE TO MATCH N.O.A.
 BEING USED.
  
 15.SELECT WHICH TYPE OF UNDERLAYMENT IS TO BE INSTALLED
 PER N.O.A 15-0410.04.
  
 ROOFING COMMENTS:
  
 16.[FBC R903.2.1] SUBMIT FLASHING TYPE, GAGE AND
 ATTACHMENT DETAILS. PROVIDE SCUPPER DETAIL, SIZE AND
 ROOF AREA CALCULATION FOR FLAT ROOF DRAINAGE.
  
 17.[FBC R903.4]PROVIDE DRAINAGE SLOPE FOR FLAT ROOF.
  
 18.[FBC R905.3.8]SUBMIT FLASHINF TYPE AND ATTACHMENT
 FOR CLAY TILE ROOF.
  
 19. [FBC R302.6] GARAGE SPACE TO BE SEPARATED FROM
 HABITABLE SPACE ABV. BY NOT LESS THAN 5/8-IN. TYPE X
 GYPSUM BOARD OR EQUIVALENT.
  
 NOTE:
 ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF ADDITIONAL MATERIALS REQUESTED

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-05-14 Cont ID  
Sent By cthroop Date 2018-05-14 Time 16:03 Rev Time 0.00
Received By cthroop Date 2018-05-14 Time 07:42 Sent To  
Notes
2018-05-14 16:10:34BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE SOILS REPORT WITH ORIGINAL SIGNATURE AND
 SEAL OF FLORIDA LICENSED PROFESSIONAL ENGINEER.
 PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE,
 DATE AND SEAL OF THE ENGINEER PER FL ADMIN. CODE RULE
 61G15-23.001.
  
 2. PROVIDE SITE DRAINAGE PLAN.
 FBC R401.3 SITE DRAINAGE
 PROVIDE TWO SETS OF A SITE DRAINAGE PLAN SHOWING
 COMPLIANCE WITH FBC R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD.
 LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES WITHIN THE FIRST 10 FEET.
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES OF FALL WITHIN 10
 FEET, DRAINS OR SWALES SHALL BE CONSTRUCTED TO ENSURE
 DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET OF THE BUILDING
 FOUNDATION SHALL BE SLOPED A MINIMUM OF
 2 PERCENT AWAY FROM THE BUILDING.
  
 3. PROVIDE ICC-ES REPORT FOR ICYNENE INSULATION. SELECT
 PRODUCT TO BE INSTALLED TO OBTAIN THE R-30 RATING PER
 APPROVED PLANS.
 R402.1.1 INSULATION AND FENESTRATION CRITERIA.
 THE BUILDING THERMAL ENVELOPE SHALL MEET THE
 REQUIREMENTS OF TABLE R402.1.1 BASED ON THE CLIMATE
 ZONE SPECIFIED IN CHAPTER 3.
  
 DUE TO THE DEFICIENCIES OF THIS PLAN, A COMPLETE AND
 THOROUGH REVIEW CANNOT BE PERFORMED AT THIS TIME. UPON
 RE-SUBMITTAL, ADDITIONAL COMMENTS MAY BE MADE.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-07-20 Cont ID  
Sent By ppetty Date 2018-07-19 Time 10:45 Rev Time 0.00
Received By jpearson Date 2018-07-20 Time 14:11 Sent To  
Notes
2018-07-19 10:45:30CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1,
 E3609.3; WPB FBC 107.2.1
 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; WPB FBC
 107.3.5; FBC RE E3706.2, E3902
 3. NOTE 16 STATES THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT
 APPLY TO TAMPER RESISTANT RECEPTACLES. ADDITIONALLY,
 THIS IS NOT THE CURRENT CODE. PROVIDE CORRECTION. NEC
 406.12; FBC RE E4002.14
 4. OK
 5. OK
 6. OK
 7. OK
 8. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
 9. IS EXISTING SERVICE BEING USED AS IS, OR BEING
 UPGRADED? PLAN DOES NOT SPECIFY. IF UPGRADING, PROVIDE
 AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH PANEL
 INCLUDING INFORMATION FROM THE POWER COMPANY STATING
 WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE
 SERVICE TO CONFIRM THE STATED AIC RATING OF THE SERVICE
 EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. NEC 110.9,
 110.10
 10. OK
 11. OK
 12. OK
 13. OK.
 14. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THE PANEL FOR PANEL A. NEC 225.31,
 225.32
 15. PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR
 A BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH
 CIRCUIT. NEC 250.32; FBC RE3607.3
 16. IDENTIFY ALL LOCATION OF ELECTRICAL PANELS ON PLAN.
 FBC 107.2.1
 17. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. FBC RE R314.3, R315.1; WPB FBC 107.2.1
 18. FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED
 GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL
 SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON
 THE EXTERIOR SIDE OF OUTDOOR ENTRANCES/EXITS WITH GRADE
 LEVEL ACCESS. PROVIDE CORRECTION. NEC 210.70(A)(2)(B),
 FBC RE E3903.3
 19. OK
 DUE TO EXCESSIVE LACK OF INFORMATION ON ELECTRICAL
 PLAN, FURTHER PLAN REVIEW COMMENTS ARE LIKELY.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER ,CHIEF ELECTRICAL INSPECTOR
 561-805-6742
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-06-08 Cont ID  
Sent By ppetty Date 2018-06-08 Time 10:22 Rev Time 0.00
Received By ppetty Date 2018-06-08 Time 10:16 Sent To  
Notes
2018-06-08 10:22:01CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1,
 E3609.3; WPB FBC 107.2.1
 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; WPB FBC
 107.3.5; FBC RE E3706.2, E3902
 3. NOTE 16 STATES THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT
 APPLY TO TAMPER RESISTANT RECEPTACLES. ADDITIONALLY,
 THIS IS NOT THE CURRENT CODE. PROVIDE CORRECTION. NEC
 406.12; FBC RE E4002.14
 4. OK
 5. OK
 6. OK
 7. OK
 8. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
 9. IS EXISTING SERVICE BEING USED AS IS, OR BEING
 UPGRADED? PLAN DOES NOT SPECIFY. IF UPGRADING, PROVIDE
 AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH PANEL
 INCLUDING INFORMATION FROM THE POWER COMPANY STATING
 WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE
 SERVICE TO CONFIRM THE STATED AIC RATING OF THE SERVICE
 EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. NEC 110.9,
 110.10
 10. OK
 11. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 12. OK
 13. OK.
 14. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THE PANEL FOR PANEL A. NEC 225.31,
 225.32
 15. PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR
 A BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH
 CIRCUIT. NEC 250.32; FBC RE3607.3
 16. IDENTIFY ALL LOCATION OF ELECTRICAL PANELS ON PLAN.
 FBC 107.2.1
 17. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. FBC RE R314.3, R315.1; WPB FBC 107.2.1
 18. FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED
 GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL
 SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON
 THE EXTERIOR SIDE OF OUTDOOR ENTRANCES/EXITS WITH GRADE
 LEVEL ACCESS. PROVIDE CORRECTION. NEC 210.70(A)(2)(B),
 FBC RE E3903.3
 19. ADDRESS ON PLAN NOT ON PERMIT APPLICATION.
 DUE TO EXCESSIVE LACK OF INFORMATION ON ELECTRICAL
 PLAN, FURTHER PLAN REVIEW COMMENTS ARE LIKELY.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER ,CHIEF ELECTRICAL INSPECTOR
 561-805-6742
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-05-03 Cont ID  
Sent By jpearson Date 2018-05-03 Time 17:09 Rev Time 0.00
Received By jpearson Date 2018-05-03 Time 13:23 Sent To  
Notes
2018-05-03 17:09:41CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1,
 E3609.3; WPB FBC 107.2.1
 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; WPB FBC
 107.3.5; FBC RE E3706.2, E3902
 3. NOTE 16 STATES THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT
 APPLY TO TAMPER RESISTANT RECEPTACLES. ADDITIONALLY,
 THIS IS NOT THE CURRENT CODE. PROVIDE CORRECTION. NEC
 406.12; FBC RE E4002.14
 4. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A
 TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST
 ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND
 NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE
 INSTALLED AT THE FRONT AND BACK OF THE DWELLING.
 PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE E3901.7
 5. PROVIDE AN OUTLET FOR ANY WALL SPACE 24 INCHES OR
 GREATER WHERE REQUIRED TO MEET WALL SPACING
 REQUIREMENTS. PROVIDE CORRECTION. NEC 210.52; FBC RE
 E3901.2.1
 6. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP
 CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN.
 PROVIDE CORRECTION. NEC 210.11(C)(3), 210.52(D); FBC RE
 E3703.4, E3901.6
 7. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C
 EQUIPMENT PER CODE. NEC 210.63; FBC RE E3901.12
 8. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
 9. IS EXISTING SERVICE BEING USED AS IS, OR BEING
 UPGRADED? PLAN DOES NOT SPECIFY. IF UPGRADING, PROVIDE
 AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH PANEL
 INCLUDING INFORMATION FROM THE POWER COMPANY STATING
 WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE
 SERVICE TO CONFIRM THE STATED AIC RATING OF THE SERVICE
 EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. NEC 110.9,
 110.10
 10. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1
 11. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 12. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE
 SUITABLE FOR DAMP LOCATIONS. PROVIDE CORRECTION. NEC
 410.10(D); FBC RE E4003.11
 13. PER CODE: LIGHTING WITH OPEN OR PARTIALLY ENCLOSED
 LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT
 BE PERMITTED IN CLOTHES CLOSETS. PROVIDE CORRECTION.
 NEC 410.16; FBC RE E4003.12
 14. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THE PANEL FOR PANEL A. NEC 225.31,
 225.32
 15. PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR
 A BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH
 CIRCUIT. NEC 250.32; FBC RE3607.3
 16. IDENTIFY ALL LOCATION OF ELECTRICAL PANELS ON PLAN.
 FBC 107.2.1
 17. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. FBC RE R314.3, R315.1; WPB FBC 107.2.1
 18. FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED
 GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL
 SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON
 THE EXTERIOR SIDE OF OUTDOOR ENTRANCES/EXITS WITH GRADE
 LEVEL ACCESS. PROVIDE CORRECTION. NEC 210.70(A)(2)(B),
 FBC RE E3903.3
  
 DUE TO EXCESSIVE LACK OF INFORMATION ON ELECTRICAL
 PLAN, FURTHER PLAN REVIEW COMMENTS ARE LIKELY.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2018-07-26 Cont ID  
Sent By lcrespo Date 2018-07-26 Time 13:32 Rev Time 0.00
Received By lcrespo Date 2018-07-26 Time 13:32 Sent To  
Notes
2018-07-26 13:33:3507/26/18 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER
  
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-06-13 Cont ID  
Sent By lcrespo Date 2018-06-13 Time 07:18 Rev Time 0.00
Received By lcrespo Date 2018-06-13 Time 07:18 Sent To  
Notes
2018-06-13 07:19:002ND GAS REVIEW**DENIED** WITH COMMENTS NOTE - A
 COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS TIME AND
 ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED UPON
 THE RE-REVIEW OF SUBMITTED CORRECTIONS. SOME COMMENT
 MAY NOT APPLY BUT ARE PROVIDED FOR REFERENCES.
  
 1. WATER HEATER WILL REQUIRE A SEPARATE IGNITION SOURCE
 AND IT IS BEING LABELED ON AS A ELECTRICAL LOAD, PLEASE
 REMOVE AND ADD A SEPARATE CIRCUIT FOR IGNITION ON
 TANKLESS, WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 2. A SECOND REQUEST FOR FIREPLACE ON MANUFACTURES
 SPECIFICATION, FBC FG R2434.1 GENERAL.
 3. SHOW 2 PSI REGULATOR ON ISOMETRIC AND ALL REGULATORS
 DOWNSTREAM, SHOW THE LOCATION OF ALL MP (STEP-DOWN)
 REGULATORS. A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR ON ISOMETRIC.
 2017 FBC FUEL GAS RES. SEC. G2420.4. SUBMIT
 MANUFACTURER?S SPECIFICATIONS FOR THE PRESSURE
 REGULATORS. REGULATORS INSTALLED ON THE EXTERIOR OF THE
 BUILDING SHALL BE APPROVED FOR OUTDOOR INSTALLATION.
 2017 FBC FUEL GAS RES. SEC. G2421.1.
 4. TYPE OF GAS (LP OR NATURAL) NEED TO BE LABELED ON
 ISOMETRIC. WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 5. SECOND REQUEST, PLEASE SUBMIT A DETAIL SHOWING THE
 TYPE, LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE
 THE ROOF AND ANCHORING DETAILS OF THE GAS VENT(S) PER
 2017 FBC FUEL GAS SECS. 502 THRU 505 OR 2017 FBC FUEL
 GAS RES. SECS. G2426 THRU G2429.1
 6. SECOND REQUEST, PLEASE SUBMIT TWO COPIES OF THE
 APPLICABLE SIZING TABLES USED TO SIZE THE GAS SYSTEM OR
 PLACE A NOTE ON THE PLANS/DRAWINGS SPECIFYING WHICH
 SIZING TABLE(S) FROM THE GAS CODE OR ANOTHER STANDARD
 THAT WAS USED IN THE DESIGN OF THIS GAS SYSTEM. REFER
 TO THE 2017 FBC FUEL GAS RES. SEC. G2412.4, G2412.8,
 G2413.1, G2413.2, & G2413.3.
 7. SECOND REQUEST, SUBMIT COMBUSTION AIR CALCULATIONS
 FOR DRYER GAS APPLIANCES. WHERE IS COMBUSTION AIR
 PROVIDED BY THE BUILDING?S MECHANICAL VENTILATION
 SYSTEM, THE SYSTEM SHALL PROVIDE THE SPECIFIED
 COMBUSTION AIR RATE IN ADDITION TO THE REQUIRED
 VENTILATION AIR? 2017 FBC R G2407.9.3. COMBINED
 COMBUSTION AIR AND VENTILATION AIR SYSTEM.
  
 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS NOTE - A
 COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS TIME AND
 ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED UPON
 THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-05-08 Cont ID  
Sent By lcrespo Date 2018-05-08 Time 08:29 Rev Time 0.00
Received By lcrespo Date 2018-05-05 Time 07:41 Sent To  
Notes
2018-05-08 08:20:101ST GAS REVIEW**DENIED** WITH COMMENTS NOTE - A
 COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS TIME AND
 ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED UPON
 THE RE-REVIEW OF SUBMITTED CORRECTIONS. SOME COMMENT
 MAY NOT APPLY BUT ARE PROVIDED FOR REFERENCES.
  
 1. THERE IS A GAS OVEN, STOVE, TANKLESS WATER HEATER. A
 DRYER ON THE PLAN IS IT NOT LABELED AS GAS AND THERE IS
 NO ELECTRIC CIRCUIT ASSIGNED TO IT. IF IT IS GAS PLEASE
 CLARIFY BY LABELING ON PLAN, PAGE A-7. GAS APPLIANCES
 SHALL BE LISTED AND LABELED. SUBMIT MANUFACTURER?S
 SPECIFICATION SHEETS/INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH 2017 FBC FUEL GAS
 RES. SEC. G2408.1.
  
 2. THE FIREPLACE IS IT WOOD BURNING OR FUEL, PLEASE
 PROVIDE MANUFACTURE SPECIFICATION AND IS IT A VENTED
 FIREPLACE, FBC FG R2434.1 GENERAL.
  
 3. SUBMIT TWO COPIES FOR INSTALLATION CLEARANCES FROM
 THE TANKLESS INSTALLATION MANUAL. THE MANUAL REQUIRES A
 CLEARANCE OF EITHER 4 FEET OR 12 INCHES FROM ANY
 OPERABLE WINDOWS OR DOORS. SHOW THE LOCATION OF ALL
 OPERABLE WINDOWS AND DOORS ON THE PLAN AND THE DISTANCE
 OF THE TANKLESS WATER HEATER FROM EACH. WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1. INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 4. SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE
 APPLIANCE. COMPLY WITH 2017 FBC FUEL GAS RES. TABLE
 G2413.4 (12) SCHEDULE 40 METALLIC PIPE FOR THE PROPER
 PIPE SIZE AND BTU LOAD.
  
 5. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC FUEL
 GAS RES SECS. G2413.4.1, G2413.4.2.
  
 6. GAS RISER DIAGRAM REQUIRED WPB AMENDMENTS TO THE FBC
 SEC. 107.3.5.3 (12) RESIDENTIAL GAS.
  
 7. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 8. TYPE OF GAS (LP OR NATURAL). WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 9. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. 2017 FBC FUEL GAS RES. SEC.
 G2420.4.
  
 10. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2017 FBC
 FUEL GAS SEC. 402.4.1 OR 2017 FBC FUEL GAS RES. SEC.
 G2413.4.1.
  
 11. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC FUEL GAS
 RES. SEC. G2413.
  
 12. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE,
 TERMINATION POINT, HEIGHT ABOVE THE ROOF AND ANCHORING
 DETAILS OF THE GAS VENT(S) PER 2017 FBC FUEL GAS SECS.
 502 THRU 505 OR 2017 FBC FUEL GAS RES. SECS. G2426 THRU
 G2429.1
  
 13. SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR ANOTHER STANDARD THAT WAS USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC FUEL
 GAS RES. SEC. G2412.4, G2412.8, G2413.1, G2413.2, &
 G2413.3.
  
 14. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2017 FBC FUEL GAS RES. SEC. G2421.1.
  
 15. SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED
 GAS APPLIANCES. WHERE IS COMBUSTION AIR PROVIDED BY THE
 BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR? 2017 FBC R
 G2407.9.3. COMBINED COMBUSTION AIR AND VENTILATION AIR
 SYSTEM.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 [email protected]
 561-805-6720
  

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2018-07-17 Cont ID  
Sent By fmittner Date 2018-07-17 Time 14:01 Rev Time 0.00
Received By fmittner Date 2018-07-17 Time 14:01 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2018-06-12 Cont ID  
Sent By fmittner Date 2018-06-12 Time 12:02 Rev Time 0.00
Received By fmittner Date 2018-06-12 Time 12:02 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2018-05-02 Cont ID  
Sent By fmittner Date 2018-05-02 Time 16:13 Rev Time 0.00
Received By fmittner Date 2018-05-02 Time 16:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By cpuell Date 2018-08-03 Time 10:38 Sent To  
Notes
2018-08-06 10:39:22IMPACT FEES ONLY, GIVEN TO CTHROOP

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-07-26 Cont ID  
Sent By lcrespo Date 2018-07-26 Time 13:33 Rev Time 0.00
Received By lcrespo Date 2018-06-28 Time 15:59 Sent To  
Notes
2018-06-28 15:59:55R30
 *TRAVELLING WITH 18041175*

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-06-22 Cont ID  
Sent By cthroop Date 2018-06-22 Time 12:54 Rev Time 0.00
Received By cthroop Date 2018-06-01 Time 15:09 Sent To I
Notes
2018-06-04 15:09:52R24

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-14 Cont ID  
Sent By cthroop Date 2018-05-14 Time 16:10 Rev Time 0.00
Received By cthroop Date 2018-04-23 Time 09:17 Sent To I
Notes
2018-04-24 09:17:11R12

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2018-08-06 Cont ID  
Sent By cthroop Date 2018-08-06 Time 15:57 Rev Time 0.00
Received By cthroop Date 2018-08-06 Time 15:57 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-05-14 Cont ID  
Sent By cthroop Date 2018-05-14 Time 16:02 Rev Time 0.00
Received By cthroop Date 2018-05-14 Time 07:42 Sent To  
Notes
2018-05-14 16:03:31BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-04-30 Cont ID  
Sent By cmontell Date 2018-04-30 Time 15:12 Rev Time 0.00
Received By cmontell Date 2018-04-30 Time 14:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-07-26 Cont ID  
Sent By lcrespo Date 2018-07-26 Time 13:34 Rev Time 0.00
Received By lcrespo Date 2018-07-26 Time 13:33 Sent To  
Notes
2018-07-26 13:38:1907/26/18 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-06-13 Cont ID  
Sent By lcrespo Date 2018-06-13 Time 07:25 Rev Time 0.00
Received By lcrespo Date 2018-06-13 Time 07:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-05-08 Cont ID  
Sent By lcrespo Date 2018-05-08 Time 08:29 Rev Time 0.00
Received By lcrespo Date 2018-05-04 Time 07:13 Sent To  
Notes
2018-05-08 08:16:401ST PLUMBING REVIEW**DENIED** WITH COMMENTS NOTE - A
 COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS TIME AND
 ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED UPON
 THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE PVC PIPE 4" IS SHOWN (A-3) IN THE PLUMBING
 ISOMETRIC AND THE FIXTURE DRAIN WILL ALLOW THE PIPE TO
 BE 3" BECAUSE OF WALL AND SPACE YOU MAY CONSIDER TO
 CHANGE THEM ACCORDING TO WHAT CODE ALLOWS. UP STAIN ON
 MAIN BUILDING YOU HAVE A WASHING MACHINE THAT SHOWS IT
 WITH AN AIR ADMITTANCE VALVE AS PER MANUFACTURES
 SPECIFICATION, IT REQUIRES A 3" SIZE PIPE ON AN AAV AND
 IT IS RECOMMENDED BY MOST WASHING MACHINES MANUFACTURE
 BECAUSE OF SOAP SUDS.
  
 2. ROMAN TUB STANDALONE REQUIRED A CONTROL VALVE BY A
 WATER TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3, EXCEPT WHERE SUCH PROTECTION IS
 OTHERWISE PROVIDED BY A COMBINATION TUB/SHOWER VALVE IN
 ACCORDANCE WITH SECTION P2708.4. FBC R 2713.3 BATHTUB
 AND WHIRLPOOL BATHTUB VALVES. PLEASE SHOW LOCATION OR
 NOTE ON THE PLAN.
  
 3. ON SECOND BUILDING SHOW AN OUTSIDE SHOWER PLEASE
 LABEL AND GIVE IT MORE DETAILS. IS THERE HOT WATER
 COMING FROM THE MAIN HOUSE OR DOES THIS BUILDING HAS
 ITS OWN WATER HEATER. IF COMING UNDERGROUND TO FEED HOT
 WATER FROM THE MAIN HEATING SOURCE IT MUST BE INSULATED
 WITH AN R-3 PER FBC RE 403.5.3
  
 4. PLUMBING WATER RISER DIAGRAM REQUIRED WPB AMENDMENTS
 TO THE FBC SEC. 107.3.5.3 (11) RESIDENTIAL PLUMBING
  
 5. THE LOFT HAS A NOTE FOR FUTURE PLUMBING ON THE
 SECOND FLOOR AND THERE IS A BATHROOM DOWN STAIR ON THE
 FIRST FLOOR EACH BUILDING SHALL HAVE ITS OWN VENT
 SYSTEM THOROUGH ROOF AND AN AIR ADMITTANCE VALVE WILL
 NOT BE TO CODE. OPTION ONE IS TO VENT THE DOWNSTAIRS
 BATH THROUGH THE ROOF AND LATER THE OTHER BATHROOM MAY
 BE INSTALLED OR PLUMB THE 2ND-FLOOR BATHROOM SO THE
 SYSTEM IS ALL DONE AT THAT POINT. THE VENT SYSTEM
 SERVING EACH BUILDING DRAIN SHALL HAVE NOT LESS THAN
 ONE VENT PIPE THAT EXTENDS TO THE OUTDOORS. 2017 FBC R
 3102.1 REQUIRED VENT EXTENSION.
  
 6. GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN
 THIS SUBMITTAL PACKAGE AT THIS TIME. A GAS PLAN REVIEW
 HAS NOT BEEN PERFORMED AT THIS TIME. A SEPARATE GAS
 PERMIT AND PLANS WILL BE REQUIRED FOR A CONTRACTOR TO
 PERFORM THE RELATED WORK. PROVIDE COMPLETE PLANS AND
 GAS RISER THAT REFLECTS THE ENTIRE SCOPE OF GAS WORK TO
 BE DONE. WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 [email protected]
 561-805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2018-08-06 Cont ID  
Sent By cthroop Date 2018-08-06 Time 15:58 Rev Time 0.00
Received By cthroop Date 2018-08-06 Time 15:58 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2018-06-22 Cont ID  
Sent By cthroop Date 2018-06-22 Time 12:53 Rev Time 0.00
Received By cthroop Date 2018-06-22 Time 09:55 Sent To  
Notes
2018-06-22 12:54:15BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 ROOFING COMMENTS:
  
 16.[FBC R903.2.1] SUBMIT FLASHING TYPE, GAGE AND
 ATTACHMENT DETAILS. PROVIDE SCUPPER DETAIL, SIZE AND
 ROOF AREA CALCULATION FOR FLAT ROOF DRAINAGE.
  
 17.[FBC R903.4]PROVIDE DRAINAGE SLOPE FOR FLAT ROOF.
  
 18.[FBC R905.3.8]SUBMIT FLASHING TYPE AND ATTACHMENT
 FOR CLAY TILE ROOF.
  
 NOTE:
 ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF ADDITIONAL MATERIALS REQUESTED.
  
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2018-05-14 Cont ID  
Sent By cthroop Date 2018-05-14 Time 16:02 Rev Time 0.00
Received By cthroop Date 2018-05-14 Time 07:42 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2018-07-17 Cont ID  
Sent By fmittner Date 2018-07-17 Time 14:01 Rev Time 0.00
Received By fmittner Date 2018-07-17 Time 14:01 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2018-06-12 Cont ID  
Sent By fmittner Date 2018-06-12 Time 12:02 Rev Time 0.00
Received By fmittner Date 2018-06-12 Time 12:02 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-05-02 Cont ID  
Sent By LL Date 2018-05-02 Time 16:12 Rev Time 0.00
Received By fmittner Date 2018-05-02 Time 16:12 Sent To  
Notes
***NONE***