Plan Review Details - Permit 18041059
Plan Review Stops For Permit 18041059
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-05-08 Cont ID  
Sent By hmoser Date 2018-05-08 Time 14:39 Rev Time 0.00
Received By hmoser Date 2018-05-04 Time 13:07 Sent To I
Notes
2018-05-07 13:08:10RESUB ROUTED TO HMOSER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-02 Cont ID  
Sent By hmoser Date 2018-05-02 Time 14:45 Rev Time 0.00
Received By hmoser Date 2018-04-23 Time 09:37 Sent To  
Notes
2018-04-24 09:38:09MECH <5K

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-05-08 Cont ID  
Sent By hmoser Date 2018-05-08 Time 14:37 Rev Time 0.00
Received By hmoser Date 2018-05-08 Time 14:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-05-02 Cont ID  
Sent By hmoser Date 2018-05-02 Time 14:44 Rev Time 0.00
Received By hmoser Date 2018-05-02 Time 14:37 Sent To  
Notes
2018-05-02 14:44:51PLAN DENIED
 1) PROVIDE MORE INFORMATION ON KITCHEN HOOD
 LIKE CFM REFER TO SECTION 1503.4 MAKE UP AIR
 2) PROVIDE A SIGNATURE ON THE PLAN
 PER SECTION 107.2.1 FBC.
  
 PLAN REVIEW BY HAROLD MOSER