Plan Review Details - Permit 18041025
Plan Review Stops For Permit 18041025
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-07-31 Cont ID  
Sent By jgomez Date 2018-07-31 Time 11:11 Rev Time 0.00
Received By jgomez Date 2018-07-30 Time 18:37 Sent To  
Notes
2018-07-30 18:38:33 
  
 REMAINDER:
 MASTER PERMIT WAS APPROVED WITH PROVISO. PROVIDE
 REQUIRED INFORMATION PRIOR TO INSPECTIONS TO AVOID
 CONFLICTS/DELAYS.
  
 2ND REVIEW
 DATE: FRI. FEB. 16/ 2018
 ACTION: BUILDING PROVISO
  
 1) NEW OUTSWING STOREFRONT DOORS AND TRANSOM TO BE A
 DEFERRED SUBMITTAL. SHEET A-4 DETAIL D4/A-4 INDICATES A
 NEW STOREFRONT GLAZING SYSTEM, DOOR, TRANSOM AND FRAME.
 A FLORIDA PRODUCT APPROVAL IS TO BE REVIEWED BY THE
 DESIGN PROFESSIONAL BEFORE BEING SUBMITTED TO THE
 JURISDICTION HAVING JURISDICTION FOR APPROVAL AND
 BEFORE INSTALLATION. THIS REVIEW SHOP DRAWINGS WERE
 SUBMITTED NO PRODUCT APPROVAL.
  
 107.3.4.2 DEFERRED SUBMITTALS. DOCUMENTS FOR DEFERRED
 SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL
 REVIEW THEM AND FORWARD THEM TO THE BUILDING OFFICIAL
 WITH A NOTATION INDICATING THAT THE DEFERRED SUBMITTAL
 DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL
 CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED
 SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE
 BUILDING OFFICIAL.
  
 2) WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION.
 2014 FBC-B 2204.1 WELDING
 2014 FBC-B 2204.2 BOLTING.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-05-16 Cont ID  
Sent By jgomez Date 2018-05-16 Time 15:36 Rev Time 0.00
Received By jgomez Date 2018-05-16 Time 12:32 Sent To  
Notes
2018-05-16 12:59:38 
 REVISION, BUILDING REVIEW COMMENTS
 CODE: FBC 5TH EDITION (2014).
  
 1- SECURITY GATE SOFFIT DETAIL D5/A-4: ATTACHMENT OF
 THE 2X8 WOOD BLOCKING TO THE EXISTING EXTERIOR WALL
 DOESN'T SEEM TO WORK THE WAY IS DRAWN. THE TWO 2X8 WOOD
 BLOCK DON'T SEEM TO BE CONNECTED TO THE SUPPORTING
 STRUCTURE. CHECK LENGTH OF FASTENERS AND EMBEDDED.
 REVISE AS REQUIRED. SEC. 1601.1 FBC.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
 REMAINDER:
 MASTER PERMIT WAS APPROVED WITH PROVISO. PROVIDE
 REQUIRED INFORMATION PRIOR TO INSPECTIONS TO AVOID
 CONFLICTS/DELAYS.
  
  
 2014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17100607
 ADD: 771 VILLAGE BLVD. SUITE: 502
 CONT: COMET CONSTRUCTION
 TEL: 561-672-8236
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. FEB. 16/ 2018
 ACTION: BUILDING PROVISO
  
 1) NEW OUTSWING STOREFRONT DOORS AND TRANSOM TO BE A
 DEFERRED SUBMITTAL. SHEET A-4 DETAIL D4/A-4 INDICATES A
 NEW STOREFRONT GLAZING SYSTEM, DOOR, TRANSOM AND FRAME.
 A FLORIDA PRODUCT APPROVAL IS TO BE REVIEWED BY THE
 DESIGN PROFESSIONAL BEFORE BEING SUBMITTED TO THE
 JURISDICTION HAVING JURISDICTION FOR APPROVAL AND
 BEFORE INSTALLATION. THIS REVIEW SHOP DRAWINGS WERE
 SUBMITTED NO PRODUCT APPROVAL.
  
 107.3.4.2 DEFERRED SUBMITTALS. DOCUMENTS FOR DEFERRED
 SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL
 REVIEW THEM AND FORWARD THEM TO THE BUILDING OFFICIAL
 WITH A NOTATION INDICATING THAT THE DEFERRED SUBMITTAL
 DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL
 CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED
 SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE
 BUILDING OFFICIAL.
  
 2) WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION.
 2014 FBC-B 2204.1 WELDING
 2014 FBC-B 2204.2 BOLTING.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-05-09 Cont ID  
Sent By ppetty Date 2018-05-09 Time 10:27 Rev Time 0.00
Received By jpearson Date 2018-05-09 Time 10:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-31 Cont ID  
Sent By jgomez Date 2018-07-31 Time 11:32 Rev Time 0.00
Received By jgomez Date 2018-07-23 Time 09:47 Sent To I
Notes
2018-07-25 09:47:14RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-16 Cont ID  
Sent By jgomez Date 2018-05-16 Time 15:43 Rev Time 0.00
Received By jgomez Date 2018-04-23 Time 13:57 Sent To I
Notes
2018-04-24 13:57:32B31

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-05-07 Cont ID  
Sent By ccole Date 2018-05-07 Time 08:09 Rev Time 0.00
Received By ccole Date 2018-05-07 Time 07:19 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2018-07-26 Cont ID  
Sent By eschneid Date 2018-07-26 Time 15:37 Rev Time 0.25
Received By eschneid Date 2018-07-26 Time 15:36 Sent To B
Notes
2018-07-26 15:37:46PASSED W/PROVISO
  
 PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY,
 THE NEW ROOFTOP MECHANICAL EQUIPMENT NEEDS TO BE
 SCREENED. THE CONTRACTOR AND ARCHITECT HAVE AGREED TO
 THIS REQUIREMENT.

Review Stop Z ZONING
Rev No 1 Status F Date 2018-05-15 Cont ID  
Sent By eschneid Date 2018-05-15 Time 11:13 Rev Time 0.25
Received By eschneid Date 2018-05-15 Time 11:07 Sent To  
Notes
2018-05-15 11:08:09FAILED
  
 1) RESOLUTION NO. 358-16 REQUIRES THAT WITHIN VILLAGE
 COMMONS, ALL NEW MECHANICAL EQUIPMENT, WHETHER GROUND
 OR ROOF MOUNTED, MUST BE SCREENED FROM VIEW OF THE
 PUBLIC. PLEASE PROVIDE VERIFICATION THAT THE NEW ROOF
 MOUNTED EQUIPMENT MEETS THIS REQUIREMENT.
  