Plan Review Details - Permit 18041018
Plan Review Stops For Permit 18041018
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-04-24 Cont ID  
Sent By jpearson Date 2018-04-24 Time 16:31 Rev Time 0.00
Received By jpearson Date 2018-04-24 Time 16:31 Sent To I
Notes
2018-04-24 16:31:28CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL PERMIT APPLICATION IS REQUIRED FOR THE
 SUB-PERMIT. PROVIDE ELECTRICAL PERMIT APPLICATION. WPB
 FBC 105.1
 2. PER LETTER IN FILES FROM VINCENT VECCHARELLA,
 ELECTRICAL WAS NOT INCLUDED IN THE ORIGINAL PERMIT
 APPLICATION. THEREFORE, THE COST OF MATERIALS AND LABOR
 FOR THIS INSTALLATION MUST BE STATED ON PERMIT
 APPLICATION. THE REVISION STATES THAT THERE IS NO
 INCREAS IN VALUE FOR THIS WORK, BUT THERE WOULD
 OBVIOUSLY BE COST ASSOCIATED WITH THIS. PROVIDE COPY OF
 SIGNED CONTRACT WITH SCOPE AND VALUE OF WORK, TO
 INCLUDE ALL MATERIALS AND LABOR. FBC 109.3
 3. PROVIDE LOAD CALCULATION FOR TRAILER. NEC 220
 4. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 5. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL.
 NEC 110.3, 110.9
 6. PROVIDE SITE PLAN SHOWING LOCATION OF SERVICE. WPB
 FBC 107.2.1
 7. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 8. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-04-24 Time   Rev Time 0.00
Received By lmarchan Date 2018-04-23 Time 11:43 Sent To  
Notes
2018-04-24 11:43:26REVISION ROUTED TO JPEARSON


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved