Plan Review Details - Permit 18041012
Plan Review Stops For Permit 18041012
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-07-05 Cont ID  
Sent By skennedy Date 2018-07-05 Time 14:44 Rev Time 0.00
Received By skennedy Date 2018-07-05 Time 14:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-05-27 Cont ID  
Sent By cthroop Date 2018-05-27 Time 11:09 Rev Time 0.00
Received By shill Date 2018-05-27 Time 10:54 Sent To  
Notes
2018-05-27 11:21:21****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 NOTE - ALTHOUGH THE IMPROVEMENTS HAVE BEEN INSTALLED
 WITHOUT A PERMIT, COMMENT LIST REFERS TO IMPROVEMENTS
 AS "PROPOSED". AN IMPROVEMENT BECOMES "EXISTING" WHEN A
 PERMIT IS ISSUED, CONSTRUCTION INSPECTED, AND FINAL
 INSPECTIONS OBTAINED.
  
 1. WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED
 SETS OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID.
  
 2. AS THE ORIGINAL PERMIT WAS FOR "TEMPORARY
 CONSTRUCTION TRAILERS" WHICH ARE EXEMPT FROM FLORIDA
 BUILDING CODE, BUT ACTUAL USE IS AS A LOUNGE
 (18021162/18041012), COMPLIANCE WITH ALL REQUIREMENTS
 OF THE FLORIDA BUILDING IS REQUIRED. A DESIGN
 PROFESSIONAL IS REQUIRED TO PROVIDE ALL INFORMATION,
 FS481. A SKETCH AND "MODSPACE" DRAWING WERE PROVIDED;
 THIS CANNOT BE USED TO DEMONSTRATE CODE COMPLIANCE. AN
 INCOMPLETE "LIFE SAFETY PLAN" WAS SUBMITTED; PLEASE
 REVISE THIS PLAN TO ADDRESS COMMENTS, OR HAVE ANOTHER
 DESIGN PROFESSIONAL PREPARE A PLAN.
  
 3. CONTACT PALM BEACH COUNTY IMPACT FEES, 561-233-5025.
 THEY WILL DETERMINE WHETHER OR NOT IMPACT FEES ARE
 REQUIRED. IF AN IMPACT FEE ASSESSMENT IS NOT REQUIRED,
 THEY CAN VERIFY THIS VIA EMAIL. IF THEY REQUIRE A
 REVIEW, AFTER ALL REVIEWS HAVE PASSED AND PLANS ARE
 STAMPED, TAKE THE PLANS TO PALM BEACH COUNTY. THE PLANS
 ARE TO BE STAMPED BY THEM AND THE RECEIPT SHOWING THAT
 FEES DUE WERE PAID, IF APPLICABLE, ARE TO BE PROVIDED
 TO BUILDING DIVISION.
  
 3. PROVIDE THE DCA APPROVAL FOR THE STRUCTURE. THIS
 STRUCTURE HAS BEEN REVIEWED BY THE STATE.
  
 4. REVISE SITE PLAN OR OTHER PLAN TO SHOW BUILDING TYPE
 (FBC CHAPTER 6), BUILDING AREA TO SHOW COMPLIANCE WITH
 FBC B CHAPTER 5.
  
 5. DESIGN PROFESSIONAL IS TO DETERMINE PROPOSED
 OCCUPANCY (APPEARS TO BE ASSEMBLY?), OCCUPANT LOAD. IF
 OCCUPANCY IS NOT CONSISTENT WITH THE DCA APPROVAL,
 MODIFICATIONS WILL BE REQUIRED.
  
 A COMPLETE REVIEW CANNOT BE DONE WITHOUT THE DCA
 APPROVAL. AFTER RECEIPT OF THE DCA STATE APPROVED PLAN,
 A REVIEW BY ALL TRADES WILL BE REQUIRED IF THE
 OCCUPANCY REVIEWED IS NOT THE SAME AS PROPOSED
 OCCUPANCY.
  
 THE PLANS FOR THE ISSUED PERMIT WERE NOT AVAILABLE TO
 ME AT TIME OF REVIEW. PLEASE NOTE THAT THE DCA PLAN FOR
 ONE OF THE OTHER PERMITS, 18021164, WAS SUBMITTED BUT
 IS NOT LEGIBLE. IF SIMILAR APPROVAL WITH SIMILAR ISSUE
 (NOT LEGIBLE) WAS PROVIDED FOR THIS PERMIT AS WELL,
 PROVIDE A COMPLETELY LEGIBLE APPROVAL.
  
 6. IT IS NOT CLEAR HOW THE PROPOSED DECK COMPLIES WITH
 FBC ACCESSIBLILITY. ARE THE BOARDS T&G? HOW LARGE ARE
 THE GAPS, SEE FBC A 302.3. A STRUCTURAL PLAN WAS
 PROVIDED, BUT AN ARCHITECTURAL TYPE PLAN IS REQUIRED TO
 SHOW COMPLIANCE WITH ACCESSIBLE ROUTE AND DECK LAYOUT.
 WHICH DIRECTION ARE THE BOARDS INSTALLED AT THE RAMP
 TURNS; IT APPEARS THAT THE USER WILL TRAVEL IN BOTH
 DIRECTIONS TO MAKE THE TURN, NOT CLEAR HOW BOARDS WILL
 COMPLY.
  
 7. PROVIDE PLANS FOR THE PROPOSED DECK: FLOOR PLAN,
 SECTIONS, DETAIL TO SHOW ELEVATION CHANGE AT DOORS, FBC
 107.
  
 8. A VALUE OF $0 WAS PROVIDED FOR THIS REVISION. A
 VALUE OF $10K WAS PROVIDED AT TIME OF PERMIT ISSUANCE
 FOR A TEMPORARY CONSTRUCTION TRAILER. PROVIDE CONTRACT
 AMOUNT, FBC 109. IF AMOUNT EXCEEDS THE AMOUNT IN THE
 ICC VALUATION TABLES, A VALUE ADJUSTMENT TO THE TABLES
 WILL BE DONE AFTER OCCUPANCY CLASSIFICATION AND
 BUILDING TYPE ARE DETERMINED.
  
 9. PRIOR TO RESUBMITTING, PLEASE SCHEDULE AN
 APPOINTMENT FOR A PRE-SCREEN TO ENSURE THAT ALL
 INFORMATION REQUIRED IS PROVIDED. IF THIS IS A CHANGE
 OF OCCUPANCY (FROM BUSINESS TO ANOTHER OCCUPANCY),
 PLEASE ADVISE.
  
 10. ALL THREE REVISIONS INDICATE THAT "DECKING DETAIL"
 IS INCLUDED IN SCOPE. CLARIFY. THE DECK WHICH CONNECTS
 THE STRUCTURES SHOULD BE INCLUDED ON ONE OF THE
 REVISIONS OR BE A SEPARATE PERMIT.
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-07-06 Cont ID  
Sent By scaldero Date 2018-07-06 Time 10:48 Rev Time 0.00
Received By scaldero Date 2018-07-06 Time 10:47 Sent To I
Notes
2018-07-06 10:48:08PERMIT # 18041012
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) PER PLANS PROVIDED, OCCUPANCY LOAD OF EACH TRAILER
 IS 14 PERSONS, MAXIMUM. ALTERATIONS TO THIS OCCUPANCY
 LOAD SHALL BE REQUESTED IN WRITING, AND SUBMITTED TO
 THE OFFICE OF THE FIRE MARSHAL FOR APPROVAL.
  
 2) PER PLANS PROVIDED, THE "INTENDED OCCUPANCY LOAD" OF
 THE DECK AREA IS SET AT 65 PERSONS AND IS HEREBY THE
 APPROVED OCCUPANCY LOAD. THE "DESIGNED OCCUPANCY LOAD"
 OF 190 PERSONS DOES NOT APPEAR TO COMPLY WITH ANY OF
 THE OCCUPANT LOAD FACTORS AS LISTED UNDER NFPA 101,
 CHAPTER 7. OCCUPANT LOAD OF 190 IS NOT APPROVED.
  
 3) THE PROVIDED SEATING/FURNITURE PLAN OF 4 TABLES AND
 16 CHAIRS IS THE APPROVED FURNITURE PLAN FOR THE DECK
 AREA. ALTERATIONS TO THIS FURNITURE PLAN SHALL BE
 REQUESTED IN WRITING, AND SUBMITTED TO THE OFFICE OF
 THE FIRE MARSHAL FOR APPROVAL.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-05-10 Cont ID  
Sent By scaldero Date 2018-05-10 Time 13:29 Rev Time 0.00
Received By scaldero Date 2018-05-10 Time 13:19 Sent To B
Notes
2018-05-10 13:29:14PERMIT # 18041012
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
  
 1) THE WOOD PLATFORM CURRENTLY IN PLACE TO CONNECT ALL
 THREE TRAILERS IS CONSIDERED A STRUCTURE AND THEREFORE,
 DOES NOT MEET THE SEPERATION REQUIREMENTS OF THE CODE
 REFERENCED BELOW.
 PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION,
 ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2:
 TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF
 COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE
 CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS,
 TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1.
 PER TABLE 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 2) PLEASE PROVIDE THE DETAILS REGARDING THE MATERIAL
 USED FOR THE PLATFORM. IS THE MATERIAL FIRE RETARDENT
 OR HAS IT BEEN TREATED WITH FIRE RETARDENT? PLEASE
 INCLUDE THE MANUFACTURER'S SPECIFICATIONS FOR THE
 MATERIAL AND/OR THE FIRE RETARDENT USED.
  
 3)A FIRE FINAL (131) INSPECTION IS REQUIRED FOR THIS
 PERMIT. BECAUSE THE TRAILER IS ALREADY INSTALLED AND IN
 USE, THE INSPECTION SHALL BE SCHEDULED (VIA THE
 AUTOMATED PERMIT SCHEDULING SYSTEM) IMMEDIATELY UPON
 ISSUANCE OF THIS PERMIT.
  
 4) THE MASTER PERMIT (18021162) IS FOR THE INSTALLATION
 OF A CONSTRUCTION TRAILER. THERE IS NO PERMIT ISSUED
 FOR THE INSTALLATION OF THE 76X48 FOOT PLATFORM. PLEASE
 ENSURE THAT IF ONE IS REQUIRED, PER THE FBC, THAT IT IS
 APPLIED FOR AND OBTAINED.
  
 5) PLEASE PROVIDE THE OCCUPANT LOAD CALCULATION AND
 TOTAL OCCUPANT LOAD FOR THIS TRAILER. PLEASE NOTE THAT
 OCCUPANCY EXCEEDING 49 PERSONS REQUIRES PANIC HARDWARE
 ON ALL MEANS OF EGRESS DOORS.
  
 6) EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-27 Cont ID  
Sent By shill Date 2018-05-27 Time 11:21 Rev Time 0.00
Received By shill Date 2018-04-23 Time 12:50 Sent To  
Notes
2018-04-24 12:50:26REVISION ROUTED TO ZONING INBOX

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2018-07-05 Cont ID  
Sent By skennedy Date 2018-07-05 Time 14:44 Rev Time 0.00
Received By skennedy Date 2018-07-05 Time 14:44 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-05-27 Cont ID  
Sent By shill Date 2018-05-27 Time 11:04 Rev Time 0.00
Received By shill Date 2018-05-27 Time 11:04 Sent To  
Notes
2018-05-27 11:04:17SEE BUILDING REVIEW
  

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By pgreilic Date 2018-05-01 Time   Rev Time 0.00
Received By pgreilic Date 2018-05-01 Time 14:27 Sent To FIRE
Notes
2018-05-01 14:27:36PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]