Plan Review Details - Permit 18040929
Plan Review Stops For Permit 18040929
Review Stop G GAS REVIEW
Rev No 2 Status P Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By bbennett Date 2018-05-24 Time 10:30 Sent To  
Notes
2018-05-24 10:31:4805/24/18 REVIEW PASSED ON MASTER PERMIT # 18040928 PER
 TIM LARGE

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-05-01 Cont ID  
Sent By tklarge Date 2018-05-01 Time 12:28 Rev Time 0.00
Received By tklarge Date 2018-05-01 Time 12:28 Sent To  
Notes
2018-05-01 12:28:081) THE SITE PLAN SHOWS A GAS GRILL. THE PIPE SIZE OF
 EACH SECTION OF GAS PIPING SHALL BE DETERMINED USING
 THE LONGEST LENGTH OF PIPING FROM THE POINT OF DELIVERY
 TO THE MOST REMOTE OUTLET AND THE LOAD ON THE SECTION.
 SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER) TO THE MOST REMOTE OUTLET IN THE BUILDING AND /
 OR SYSTEM PER THE 2017 FBC-FUEL GAS SEC.402.4.1,
 402.4.2, OR 2017 FBC-RES. SEC. G 2413.4.1,
 G2413.4.2.2017 FBC-FUEL GAS SEC. 402.4.1.
 2) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED FOR
 THE GRILL AND THE SIZE OF THE PIPE. WPB AMENDMENTS TO
 FBC SEC.107.2.1.
 3) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS
 SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37)
 OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES
 G2413.4 (1 ) THROUGH G2413.4 (21).
 4) SUBMIT MANUF. SPECIFICATIONS FOR THE GRILL. FGC
 SEC.305.1, FBC-RES. SEC.G2408.1.
 5) INDICATE ON THE PLAN IF THE GRILL IS LOCATED UNDER A
 ROOF. WPB AMEND. TO FBC SEC. 107.2.1.
 6) THE DESCRIPTION OF WORK ON THE GAS APPLICATION NOTES
 AN EXISTING NATURAL GAS METER BUT THE PLANS SHOW A NEW
 NATURAL GAS METER AND THE SITE PLAN SHOWS A "FUTURE
 POSSIBLE NG METER SITE.". WHICH IS IT? CLARIFY. WPB
 AMEND. TO FBC SEC. 107.2.1.
 7) SPECIFICATIONS FOR A GAS PRESSURE REGULATOR HAVE
 BEEN SUBMITTED. IF THIS IS A LESS THAN 2 PSI SYSTEM,
 WHY THE REGULATORS? CLARIFY.
 8) THE GAS PLAN REFERENCES TABLE 402.4 (21) OF THE 2017
 FUEL GAS CODE AND COPIES OF THE SAME TABLE HAVE BEEN
 SUBMITTED WHICH IS FOR PE PIPE WITH A PRESSURE DROP OF
 0.5 IN. W.C. BUT SIZING TABLES FROM GASTITE HAVE ALSO
 BEEN SUBMITTED WITH A LENGTH OF 30 FEET IDENTIFIED AND
 A PIPE SIZE OF 1 INCH. THE GAS PLAN SHOWS A DISTANCE OF
 10 FEET AND 3/4 INCH PE. IN ADDITION, THE TABLE FROM
 GASTITE IS FOR A PRESSURE DROP OF 6.0 IN. W.C. AT THIS
 POINT, I HAVE ABSOLUTELY NO IDEA OF WHAT TABLE IS BEING
 USED TO SIZE THIS SYSTEM. SUBMIT TWO COPIES OF THE GAS
 SIZING TABLES BEING USED TO DESIGN THIS SYSTEM AND THE
 GAS PLAN SHALL ALSO REFLECT THE CORRECT SIZING TABLES.
 REMOVE ALL SIZING TABLES THAT DO NOT APPLY. WPB AMEND.
 TO FBC SEC. 107.2.1.
 9) A SIZING TABLE FOR A 2 PSI SYSTEM HAS BEEN SUBMITTED
 BUT THE GAS PLAN SHOWS A LESS THAN 2 PSI SYSTEM. WHICH
 IS IT? CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-01 Cont ID  
Sent By tklarge Date 2018-05-01 Time 12:27 Rev Time 0.00
Received By tklarge Date 2018-05-01 Time 12:27 Sent To  
Notes
***NONE***